Professional Documents
Culture Documents
Abstract-- The electrical energy is easily controllable resurrection energy and the necessity of the voltage
compared with other energy. In addition, the electrical descent measures increase along with the introduction of
energy has an advantageous feature for environment. The the vehicle where the transfer of the high-power is needed,
electrical energy is also used as the driving energy of the and the power storage facility is expected measures
rolling stock in railway. On the other hand, to supply the against such a problem.
electric energy with stability, the power supply system needs
to have a sufficient supply capacity for demand. The
feature of the electric power used in electric railways is that II. HISTORY OF ENERGY STORAGE SYSTEM
the peak power is large and the average power is low. This (BATTERY POST)
is a factor of the power cost increase. Moreover, electric In Japan, the electrification for railway was started, the
railway is increasing effective use for the resurrection battery posts were installed soon which operated in
energy of the vehicle and the necessity of the voltage descent
parallel with rotary converters for the purpose of
measures. In addition, an electric railway needs effective use
of regenerating energy from rolling stock for energy suppressing energy demand [1]. The power supply
conservation, and the measure against a voltage drop. To circumstances used to be bad at that time, the load for a
apply the energy storage system to electric railways is one short time was supplied by the battery, and the
method to solve these problems. This paper describes the improvement of the load factor was measured by driving
example of application and future view of the energy storage the battery and the rotary converter in parallel between
system for DC-electric railway in Japan. commuting time. It was installed the Maruyama
substation and the Yagasaki substation of the arrow in the
Index Terms²Electric railway, Energy storage system, Usui pass, which is located in the Shinetsu line in 1912.
Battery post, Lithium Ion battery, Nickel-metal hydride Moreover, it was installed the Kawasaki substation and
batteries, Flywheel, EDLC, SMES
the Oimachi substation which is located in the Keihin line,
and the Eiraku-cho substation and the Harajuku
I. INTRODUCTION
substation which is located in the Yamanote line in 1914.
Various approaches have been made as "Law As for space required for installation, the battery room
concerning the rational use of energy" is provided in was, for instance, 430m2, the transformation of electrical
Japan since oil crises. In addition, after 1973, the energy equipment room was 350m2, and in the Maruyama
improvement of the co-efficiency of performance that substation, the battery room was wider. It was abolished
exceeded 30% was achieved. Moreover, the revision of from imports the battery and the operation and
law concerning rational use of energy was enforced along maintenance difficult, and the improvement also of the
with the decision of the Kyoto protocol accomplishment power supply circumstances moreover the substation's
of a goal plan in 2005 in April, 2006. As a result, the being strengthened in 1927 though these battery posts
decision of the conservation of energy plan and the report were used for about 15 years.
of the amount of the energy use were obligated to the
transportation entrepreneur and the shipper more than a Table I
constant scale in the transportation section. In this law, Battery Post
introduction of a clean energy vehicle and the modal shift Line
Shinetsu line
Yamanote line / Keihin line
(Usui pass)
to mass transportation with few environmental impacts
Substation Maruyama Yagasaki Eiraku-cho Harajuku Oimachi Kawasaki
are demanded. In such the situation, in the automobile
Electrification year 1912 1909 1914
industry, development of an electric vehicle, a fuel-cell
Battery use period
vehicle, etc. is progressing and especially development of 1912/1928 1912/1927 1914/1921 1914/1922 1914/1927 1914/1925
an electric power storage medium is remarkable. On the Voltage 624 (V) 624 (V) 576 (V) 576 (V) 576 (V) 1150 (V)
other hand, the power storage facility of the vehicle and Capacity 1332 (A/h) 1332 (A/h) 1000 (A/h) 1000 (A/h) 1000 (A/h) 1000 (A/h)
posts that do not require a large investment such as power batteries, and Electric Double Layer Capacitors (EDLCs)
lines supplied from generators, and substation are installed for the actual electrified railway system
equipments. For the fundamental study, Japan national because of those utility.
railway (JNR) installed temporally a lead-acid battery Figure 1 shows the relationship between duration of
post at the Nakajima station on the Kabe line in 1980, and charge/discharge by the above-mentioned storage media
various examinations were carried out. The post and requested functionalities.
supervised feeding voltage. When the voltage was lower
than a set value, the battery was discharged, and if it
became high, it was charged. The post consisted of 792
cells; its max voltage was 1,584V. The examination had
been continued for three years. The post had operated
effectively for the voltage drop compensation. The post
used a thyristor as a switch between the feeding line and
the lead-acid batteries.
3118
The 2010 International Power Electronics Conference
3119
The 2010 International Power Electronics Conference
maximum current. The figure (b) indicates that A. Keihin Electric Express Railway (Flywheel)
charge/discharge current is regulated in order to suppress The railway vehicles capable of regeneration have been
a large fluctuation of charge/discharge condition around developed since 1970s. The vehicles are a mainstream because
the range of charge voltage or discharge voltage. The the regenerating energy can transmit to powering energy.
figure (c) indicates that standby current and maximum However, if there are no powering vehicles adjacent to the
discharge current can be varied besides the type (b). The regenerating vehicles, the regenerative energy cannot be used
type (c) is easy to adjust the state of charge (SOC) during effectively for any loads, and regenerative power lapse occurs.
standby and discharge mode. Stabilizing SOC contributes As a measure for regenerative power lapse, a large-sized
to suppress degradation of charge/discharge flywheel has been installed at the Zushi post in the Keihin
characteristics. Therefore, if stable SOC is extremely Electric Express Railway, which stored regenerative energy as
needed for the media, the type (c) is appropriate. mechanical energy, and emitted electric energy to powering
The feeding voltage is apt to reflect powering or vehicles. The equipment consists of a flywheel, an exchange
regenerating of electric cars. However, this principle generator motor, and a converter. It was reported as a result of
cannot work effectively in every time. Therefore, there is the verification examination that the energy-saving effect was
room to inquire about the control method, and new 12%. The equipment was built in 1988, it has continued
method for charge/discharge regulation is expected. operating.
IV. EXAMPLES OF APPLICATION IN JAPAN B. West Japan Railway Company (Lithium Ion Battery)
After 1988, the energy storage system was applied to The energy storage system using lithium ion batteries
the railway in Japan [3]. Table III shows the specification was installed in the Shin-Hikida substation of the
of the energy storage system applied to the railway after Hokuriku lines of West Japan Railway Company in
1988. The specification of the energy storage system autumn, 2006. Electrification of the lines was converted
experimentally applied to Table IV after 1988 is shown. from AC to DC at that time. The company had already
Energy storage systems applying batteries are apt to have developed substation support equipment, which
large energy, on the other hand, applying flywheel or compensated short-time voltage drop effectively. The
EDLC are apt to have large power. energy storage system was based on the characteristics of
the equipment. The system was also aimed for stabilizing
Table III feeding voltage by absorbing regenerative power. The
Rated capacity of energy storage system for practical use system has also considered the characteristic of
Rated Rated regenerative power regulation.
Installation Storage
Company power energy
year medium
(kW) (kWh) C. Kobe Municipal Transportation Bureau (Lithium Ion
Keihin Electric Express
1988 Flywheel 2,000 25 Battery)
Railway
West Japan Railway
2006
Lithium
1,050 140
Kobe Municipal Transportation Bureau carried out the
Company ion battery
Kagoshima City Lithium
verification test of the energy storage system applying
Transport Bureau
2007
ion battery
250 18.1 lithium ion battery in the Myodani substation of the
Kobe Municipal
2007
Lithium
1,000 37.4 Seishin-Yamate Line in May, 2005. The section, which
Transportation Bureau ion battery
Seibu Railway Co., Ltd. 2007 EDLC 2,560 6.875
slope is 2.9%, continues for approximately 4km. To use
electric brake, regenerative power absorption system is
indispensable for the section; therefore, inverter
Table IV
equipments are installed at every substation on this line.
Rated capacity of energy storage system for examination
Rated Rated
The test was focused on operating energy storage system
Storage and inverter equipment in parallel, or operating the
Company power energy
medium
(kW) (kWh) system individually. We confirmed that there was no
Nagoya Railroad Co., Lithium ion
500 18.7 negative interference between the system and inverter
Ltd. battery equipment, and the system had the same effect as inverter
Osaka Municipal nickel-metal
Transportation Bureau hydride battery
5,600 576 system. Based on the verification results, the actual
system has been installed in the Itayado substation of the
same line in February, 2007. The rated capacity was
Current main purposes of applying fixed energy twice as much as that applied for the verification test.
storage system are divided into two in general. The one The actual system brought effect of energy reduction,
is for voltage drop compensation; another is for which was more than 310 MWh per year.
regenerative power absorption. In cases where two
substations are distant from each other, voltage drop D. Kagoshima City Transportation Bureau (Lithium Ion
compensation by the system is more effective. In Battery)
addition, in cases where the number of trains is less Kagoshima City Transport Bureau has introduced new-
comparatively and a long slope exists, regenerative power type electric vehicles with regard to the reinforcement of
absorption by the system is effective. However, reduction transport capacity. The reinforcement and a high rate of
of primary energy demand in the substation will become operating air-conditioning equipment in summer season
more important purpose of applying the system in the might cause a number of feeding voltage drops during
future. rush hours. Therefore, two energy storage systems
3120
The 2010 International Power Electronics Conference
applying lithium ion batteries were installed at the The resistance equipment compensates the charge of
Sakurajimasanbashidori Station and the Nakasudori EDLCs. When the EDLC voltage reaches the maximum,
Station in order to compensate the voltage drop and the switch for resistance equipment turns on and
utilize regenerative power. The systems have commenced regenerative current flows to the equipment.
to operate commercially since March, 2007. The scale of
the system was so compact that it enabled to set the 2000
December, 2007.
-500
Discharge
-1000
The location and height between the Agano and the -1500
Shomaru substation, where the systems have been 0 5
Time (min)
10 15
prevent regeneration power lapse, and the introduction of 1250 Shomaru feeding voltage
Shomaru EDLC voltage
variable-voltage and variable-frequency drive vehicles, 1000
750
which can regenerate have been able to be applied for this 500
section. 0 5
Time (min)
10 15
1500
Agano Shomaru
Shomaru current (A)
St.
200 Nishi-Agano
150 Agano St. Energy storage system
(Shomaru substation)
characteristics
St.
100 Higashi-Agano
3121
The 2010 International Power Electronics Conference
(d) The regenerative energy charged by the both systems The government assumed that it noted it continuously
was 7.7kWh, and the discharge energy was 5.9kWh. separated SMES, Flywheel, and EDLC from the
About 77% of the regenerative energy was reused examination of the rechargeable battery, and investigated
effectively. technology trends and the form of use.
Through the characteristics, we confirmed that the When a new rechargeable batteries such as lithium-ion
systems worked effectively in regard to reducing primary batteries and nickel-metal hydride batteries is began to be
energy consumption. used, the government judged that the prior regulation of
the entire energy storage system including the
F. Osaka Municipal Transportation Bureau (Nickel-
rechargeable battery had to reconsider (the comparison
Metal Hydride Battery)
with the power plant is based).
In Osaka Municipal Transportation Bureau, the energy The government concluded it as follows after the case
storage system applying a mass nickel-metal hydride with the safety of the energy storage system had been
battery was temporally set at the Komagawa substation in considered (a function, structure, an accident example).
the Tanimachi line. The verification tests were conducted (1) Position in electricity enterprises law.
when only test electric vehicles ran and when actual The energy storage system is not considered the
trains were in operation for the purpose of reducing power plant, and considers equip with one by the
primary energy consumption. The system need not composition of the power plant, the substation, and
chopper system which regulates charge/discharge of the demand equipment, etc.
energy storage media. The battery is directly charged to (2) Authorization and notification of construction plan,
feeding voltage. The system equipped with larger power and method of prior restriction.
and energy than others. The system could contribute to The entrepreneur observes a technological standard etc.
the reduction of primary energy consumption through the and the security of the energy system is maintained.
charge/discharge. Participation by a prior restriction of the country is
G. Nagoya Railroad Co., Ltd. (Lithium Ion Battery) made a minimum.
The nasty accident due to the deficient energy storage
The feeding voltage near the Shin-Anjo station of the
system had not occurred.
Nagoya line typically drops much because the station is The notification object of the installation plan is
distant from any DC substations. However, installation assumed to be the energy storage system with an
of a new substation near the station has some problems
especially large capacity (10,000kW×8h). Because
concerning space, cost, and incidental factors. Therefore,
some rechargeable battery with large capacity is put to
verification test was conducted by connecting an energy practical use.
storage system adjacent to the station for the purpose of (3) Technological standard of energy storage system.
confirming substitution for substation. The capacity of
The rechargeable battery used as a power supply of
the system was half that of one applied for the actual
using regularly detects abnormalities such as the
system shown in the preceding paragraph C. Prior to the overvoltage and overcurrent, and separates the circuit
verification test conducted, inductive obstruction tests for by the breaker. The device with high interior
signal system or train radio was emphasized. The effects
temperature separates the circuit by the breaker when
of compensating voltage drop and eliminating energy
detecting an abnormal interior temperature.
demand were evaluated by the test. If the rated power of
the system would be beyond 2,000kW, those effects were
VI. CONCLUSION
expected to be 45V, 1000MWh per year, respectively.
If an initial cost of the energy storage system and the
V. SECURITY REGULATION electricity cost that can be saved by the energy storage
system are compared, it is understood that an economical
The lead-acid storage battery has been equipped with
advantage of the energy storage system is limited.
to the power plant and the substation, etc. for emergency However, when electric power compensation is required
purposes. Equipment that uses a new rechargeable at locations without installation of a power line, energy
battery is equipment that accompanies the power plant.
storage system is going to have an economical advantage.
On the other hand, the government thought that this
We should consider protective methods, maintenance
equipment was a power plant because it is necessary to and security of the energy storage system. Moreover, it is
confirm the safety by prior regulation (Authorization of necessary to prepare technical standards for the electric
construction plan and inspection before the uses) up to
power storage system.
now.
The authors considered that the energy storage system
However, because a use results and a technical would be applicable to electric railways for the purpose
knowledge of the NAS battery, the zinc bromide battery, of electric power compensation in the future. Therefore,
and the redox flow cell had been accumulated, the
it is desirous to establish a control method and prepare a
government judged that it was able to secure safety even
pertinent law.
if it did not restrict it. Therefore, the lead-acid storage
battery and the rechargeable battery were excluded from
the definition of power plant in 2000.
3122
The 2010 International Power Electronics Conference
REFERENCES
[1] Railway Electrification Committee, ³History of Electric
Railways technology development´, Railway
Electrification Committee, 1983, pp.120-122.
[2] A.Okui, ³DC-Substation that absorbed regenerative
electric power´ Japan Railway Electrical Engineering
Association, vol.15, No.1, 2004, pp37-43.
[3] T. Konishi, H. Morimoto, T. Aihara, M. Tsutakawa,
³Fixed Energy Storage Technology Applied for DC
Electrified Railway´, IEEJ Trans 2010; 5:1-8, 2010.
3123