You are on page 1of 1

514.1.3 Openings provided for replacing air by the manufacturer. [NFPA 9604:11.

2-41
exhausted through ventilating equipment shall
not be restricted by covers, dampers, or any 514.2.3 The year of manufacture and the date of
other means that would reduce the operating installation of the fusible links shall be marked
efficiency of the exhaust system. [NFPA on the system inspection tag. The tag shall be
96:11.1.31 signed or initialed by the installer'
lNFPA96:11.2.5I
514.1.4 lnstructions for manually operating the
fire extinguishing system shall be posted Other detection devices not including fusible
conspicuously in the kitchen and shall be links and automatic sprinklers shall be serviced
reviewed periodically with employees by the or replaced in accordance with the
management. [NFPA 96:1 1.1.4] manufacturer's recommendations. [NFPA 96-
04:11.2.61
514.1.5 Listed exhaust hoods shall be operated
514.2.4Where automatic bulb type sprinklers or
in accordance with the terms of their listings and
spray nozzles are used and annual examination
the manufacturer's instructions' [NFPA
shows no buildup of grease or other material on
96:11.1.51
the sprinkler or spray nozzles, annual replace-
ment shall not be required. INFPA 96:11.2.71
514.1.6 Cooking equipment shall not be oper-
ated while its fire extinguishing system or 514.2.5|f required, certificates of inspection and
exhaust system is nonoperational or otherwise
maintenance shall be forwarded to the Authority
impaired. INFPA 96:1 1.1.6]
Having Jurisdiction. [NFPA 96:1 1.2.8]
514.1.7 Secondary filtration and pollution control
equipment shall be operated in accordance with 514.3 lnspection for Grease Buildup.
the terms of its listing and the manufacturer's
recommendations. [NFPA 96:1 1.1.7] 5'14.3.1 The entire exhaust system shall be
inspected for grease buildup by a properly
5{4.1.8 lnspection and maintenance of equip- trained, qualified, and certified company or
ment allowed in
Section 512-3.1 shall be person(s) acceptable to the Authority Having
conducted by properly trained and qualified Jurisdiction in accordance with Table 54.
persons at a
frequency determined by the
manufacturer's instructions or equipment 514.4 Gleaning of Exhaust Systems.
listing.[NFPA 9O: t t .t .41
514.4.1 Upon inspection, if the exhaust system
514.2 Inspection. Maintenance of the fire is found to be contaminated with deposits from
extinguishing systems and listed exhaust hoods grease laden vapors, the contaminated portions
containing a constant or fire activated water system of the exhaust system shall be cleaned by a
that is listed to extinguish a fire in the grease properly trained, qualified, and certified
removal devices, hood exhaust plenums, and company or person(s) acceptable to the
exhaust ducts shall be made by properly trained, Authority Having Jurisdiction. [NFPA 96:11.6.1]
,
qualified, and certified person(s) or company accept-
able to the Authority Having Jurisdiction at least 514.4.2 Hoods, grease removal devices, fans,
every six (6) months. [NFPA 96:11.2.1] ducts, and other appurtenances shall .be
cleaned to remove combustible contaminants
514.2.1 All actuation components, including prior to surfaces becoming heavily contaminated
remote manual pull stations, mechanical or elec- with grease or oily sludge. [NFPA 96:11.6.2]
trical devices, detectors, actuators, and fire
actuated dampers, shall be checked for proper 514.4.3 At the start of the cleaning process,
operation during the inspection in accordance electrical switches that could be activated
with the manufacturer's listed procedures. ln; accidentally shall be locked out' [NFPA
addition to these requirements, the specific 96:11.6.31
inspection requirements of the applicable NFPA
standard shall also be followed. INFPA 96- 514.4.4 Components of the fire suppression
04:11.2.2 11.2.31 system shall not be rendered inoperable during
the cleaning process. INFPA 96:11.6.4]
514.2.2 Fusible links (including fusible links on
fire damper assemblies) and automatic sprinkler 514.4.5 Fire extinguishing systems shall be
heads shall be replaced at least semiannually, permitted to be rendered inoperable during the
or more frequently if necessary where required cleaning process where serviced by properly

94 2012 PHILIPPINE MECHANICAL ENGINEERING CODE

You might also like