Velosi Certification LLC

Abu Dhabi Business Hub,


ICAD -1, Mussafah
P.O Box 114182, Abu Dhabi, UAE
Tel No.: +971 2 550 2600
Fax No.: +971 2 550 2601

ULTRASONIC EXAMINATION REPORT


Client : FAB TECH ABUDHABI LLC/ TATA PROJECTS LIMITED
Project : EPC of Aviation Fuel Depot at Al Bateen Executive
Date:19-04-2018
Airport
Location : MUSSAFAH Report No. VEL/UT/2018/018

Mark No: As mentioned below Procedure No : L4-UAE-048B (Rev 4) Applicable Code: AWS D1.1

Job No: 1377 Acceptance Criteria: AWS D1.1 Table 6.2

Stage of Test: FINAL Material: S355JR / S275JR Material Thickness: As Given Below

Calibration Block: V1 & V2 Reference Block: V1 Welding Process: SMAW

Equipment: USM 35 X Equipment Sr.No: 11868a Surface Condition: SMOOTH

Calibration Date : 29-03-2018 Calibration Due Date : 28-03-2019

Inspection Technique: PULSE ECHO – CONTACT METHOD Heat Treatment: N/A

Cable Type : LEMO TO MICRO DOT Cable Length : 2 METER

Reject Control: LOW Damping: LOW Couplant: CELLULOSE


Probe Transfer Gain
Probe Probe Frequency Reference Scanning Range (in
Size Correction (PRL)
Type Angle in MHz Reflector dB mm)
(in mm) dB dB
2ND BACK
TR Ø10 0° 4MHz - 40 +6 0-50
REFLCTION 80%
ANGLE 8X9 70° 4MHz 1.5mm Dia SDH - 63 +6 0- 100

Welder Joints Flange Web Type Of Observati


S.N AREA Mark No Qt. Profile Result
ID ID THK(mm) THK(mm) Joint on
Aviation PFC15
Gas CS-59- 0x75x
1 1 W-80 J1 11.5mm 8.0mm Butt NSD Acceptable
Shelter CO5 18

Aviation PFC15
Gas CS-59- 0x75x
2 1 W-80 J2 10.0mm 5.5mm Butt NSD Acceptable
Shelter PU1 18

REMARKS: - UT was carried out on the above mentioned weld joints to check the entire weld discontinuity.

OBSERVATION: NO relevant indication observed, accepted as per specification.

LEGEND: NRI- No Recordable Indication, ACC- Acceptable, NAC- Not Acceptable, N/A- Not Applicable

Level II NDT Inspector Reviewed by Level III

Name: PANKAJ SHARMA Name: Vikas Chandra

Signature: Signature:

Date: 19-04-2018 Date: 20-04-2018

L5-UAE-043 Rev No. 2 Rev Date 06-01-2017 Page 1 of 2


Velosi Certification LLC
Abu Dhabi Business Hub,
ICAD -1, Mussafah
P.O Box 114182, Abu Dhabi, UAE
Tel No.: +971 2 550 2600
Fax No.: +971 2 550 2601

ULTRASONIC EXAMINATION REPORT

Client : FAB TECH ABUDHABI LLC/ TATA PROJECTS LIMITED


Project : EPC of Aviation Fuel Depot at Al Bateen Executive
Date:19-04-2018
Airport
Location : MUSSAFAH Report No. VEL/UT/2018/018

Mark No: As mentioned below Procedure No : L4-UAE-048B (Rev 4) Applicable Code: AWS D1.1

Job No: 1377 Acceptance Criteria: AWS D1.1 Table 6.2

Stage of Test: FINAL Material: S355JR / S275JR Material Thickness: As Given Below

Calibration Block: V1 & V2 Reference Block: V1 Welding Process: SMAW

Equipment: USM 35 X Equipment Sr.No: 11868a Surface Condition: SMOOTH

Calibration Date : 29-03-2018 Calibration Due Date : 28-03-2019

Inspection Technique: PULSE ECHO – CONTACT METHOD Heat Treatment: N/A

Cable Type : LEMO TO MICRO DOT Cable Length : 2 METER

Reject Control: LOW Damping: LOW Couplant: CELLULOSE


Probe Transfer Gain
Probe Probe Frequency Reference Scanning Range (in
Size Correction (PRL)
Type Angle in MHz Reflector dB mm)
(in mm) dB dB
2ND BACK
TR Ø10 0° 4MHz - 40 +6 0-50
REFLCTION 80%
ANGLE 8X9 70° 4MHz 1.5mm Dia SDH - 63 +6 0- 150

Welder Joints Flange Web Type Of Observati


S.N AREA Mark No Qt. Profile Result
ID ID THK(mm) THK(mm) Joint on
Aviation PFC15
Gas CS-59- 0x75x
3 1 W-80 J3 10.0mm 5.5mm Butt NSD Acceptable
Shelter PU1 18

Aviation PFC15
Gas CS-59- 0x75x
4 1 W-80 J4 10.0mm 5.5mm Butt NSD Acceptable
Shelter PU2 18

REMARKS: - UT was carried out on the above mentioned weld joints to check the entire weld discontinuity.

OBSERVATION: NO relevant indication observed, accepted as per specification.

LEGEND: NRI- No Recordable Indication, ACC- Acceptable, NAC- Not Acceptable, N/A- Not Applicable

Level II NDT Inspector Reviewed by Level III

Name: PANKAJ SHARMA Name: Vikas Chandra

Signature: Signature:

Date:19-04-2018 Date: 20-04-2018

L5-UAE-043 Rev No. 2 Rev Date 06-01-2017 Page 2 of 2