PART 1 GENERAL
1.3 SUBMITTALS
A. See Section 01 3000 - Administrative Requirements for submittal procedures.
B. Product Data: Provide data on filter media, filter performance data, filter assembly and filter
frames, dimensions, motor locations and electrical characteristics and connection
requirements.
C. Shop Drawings: Indicate filter assembly and filter frames, dimensions, motor locations, and
electrical characteristics and connection requirements.
D. Samples: Submit two samples of replacement filter media of each type and each filter frame.
E. Manufacturer's Installation Instructions: Indicate assembly and change-out procedures.
F. Operation and Maintenance Data: Include instructions for operation, changing, and periodic
cleaning.
G. Maintenance Materials: Furnish the following for Employer/Owner's use in maintenance of
project.
1. See Section 01 6000 - Product Requirements, for additional provisions.
2. Extra Filters: One set of each type and size.
PART 2 PRODUCTS
A. Construction
1. Provide factory-assembled units of sufficient structural strength to be supported from
ends without intermediate support. Ship units completely assembled.
B. Cabinet:
1. Material and Finish: Aluminized steel cabinet with stainless steel riveted construction and
white insert color selection powder coated finish.
2. Mounting: Provide for suspended mounting
3. Service Access: Removable screen and removable bottom access panel.
C. Motors
1. 1/5-HP, 1680 rpm, single phase, 2-speed, ODP, direct drive, resilient mounted,
continuous duty, with internal thermal-overload protection and permanently lubricated
sealed ball bearings.
D. Fans:
1. Balanced forward curved cross flow, tangential type, made of aluminum with flexible hubs
and mounted in matched fan scrolls constructed of material used in constructing cabinet.
E. Discharge Nozzles:
1. Provide uniform velocity across width of air curtain.
2. Aperture: 2.375 in (6 cm) slot by width of air curtain.
F. Vanes
1. 1.5 in (3.8 cm) minimum height; constructed of airfoil-shaped aluminum extrusions;
adjustable plus or minus 20 degrees to deflect airflow.
G. Inlet:
I. Controls:
1. Switching: Manual Switch: Factory installed “High-Off-Low” switch. Remote mount 3
position rotary cam High-Off-Low switch.
2. Basic Control Package: Air curtain turns on when door is opened and shuts off when door
is closed.
J. Mounting Accessories:
1. Provide brackets and other mounting accessories as required to permit installation and
proper functioning of air curtain to meet project conditions of use.
PART 3 EXECUTION
3.1 INSTALLATION
A. Install air cleaning devices in accordance with manufacturer's instructions.
B. Prevent passage of unfiltered air around filters with felt, rubber, or neoprene gaskets.
C. Install filter gage static pressure tips upstream and downstream of filters. Mount filter gages on
outside of filter housing or filter plenum, in accessible position. Adjust and level.
D. Do not operate fan system until filters (temporary or permanent) are in place. Replace
temporary filters used during construction and testing, with clean set.
END OF SECTION