Professional Documents
Culture Documents
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.
0.2 SUMMARY
0.3 SUBMITTALS
A. Product Data: Include rated capacities; shipping, installed, and operating weights; furnished
specialties; and accessories for each model indicated. Include a schedule showing drawing
designation, room location, number furnished, model number, size, and accessories
furnished.
B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loadings,
required clearances, method of field assembly, components, and location and size of each
field connection.
1. Wiring Diagrams: Detail wiring for power, signal, and control systems and
differentiate between manufacturer-installed and field-installed wiring.
C. Coordination Drawings: Reflected ceiling plans drawn to scale and coordinating air outlets
with other items installed in ceilings.
D. Maintenance Data: List of parts for each type of air terminal and troubleshooting
maintenance guide to include in the maintenance manuals specified in Division 1.
A. Product Options: Drawings and schedules indicate requirements of air terminals and are
based on specific systems selected. Other manufacturers' systems with equal performance
characteristics may be considered. Refer to Division 1 Section "Product Requirements."
B. Listing and Labeling: Provide electrically operated air terminals specified in this Section
that are listed and labeled.
C. NFPA Compliance: Install air terminals according to NFPA 90A, "Standard for the
Installation of Air Conditioning and Ventilating Systems."
D. Comply with listed and labeled as defined in latest and relevant IEC standard, by a testing
agency acceptable to the Engineer.
E. The maximum noise level for any ceiling mounted item shall not exceed NC 35. Units shall
meet the airborne and radiated sound-power level (PWL) requirements scheduled, to attain
the specified NC levels. An 18-dB space attenuation shall be assumed in all octave bands or
as recommended by the manufacturer with consideration given to downstream duct
construction and configuration in determining airborne NC levels. Sound levels shall be
tested in accordance with ANSI S12.23
PART 2 - PRODUCTS
A. Configuration: Factory built and calibrated with controls mounted on unit, pressure
independent, factory set and field adjustable volume-damper assembly, suitable for single
duct applications.
1. Each unit shall have factory set air volumes and numbered corresponding to contract
drawings.
2. Control components shall be factory mounted by air terminal manufacturer inside a
protective metal enclosure. All power control wiring shall be wired to factory
mounted terminal box.
C. Casings: Unit casing shall be constructed of galvanized steel not lighter than 0.85 mm (22
gage) or aluminum sheet not lighter than 1.3 mm (18 gage)
1. Octopus connector: Factory installed, lined air distribution terminal. Provide where
flexible duct connections to terminals are shown on the drawings. Provide butterfly-
balancing damper, with locking means, in connectors with more than one outlet.
D. Casing Lining: Suitable to provide required acoustic performance, thermal insulation and
prevent sweating. Minimum of 13 mm thick, neoprene- or vinyl-coated, fibrous-glass
insulation; 24-kg/cu. m density, complying with NFPA 90A requirements and UL 181
erosion requirements. Secure lining to prevent delamination, sagging, or settling.
1. Coat liner surfaces and edges with erosion-resistant coating or cover with perforated
metal so that the air stream will not detach material.
E. Plenum Air Inlets: Round stub connections or S-slip and drive connections for duct
attachment.
G. Access: Removable panels to permit access to dampers and other parts requiring service,
adjustment, or maintenance; with airtight gasket and quarter-turn latches and shall require
no tool other than a screwdriver to remove.
H. Volume Damper: Construct of galvanized steel with peripheral gasket and self-lubricating
bearings.
1. Low Velocity Boxes: Inlet valve shall be self-seating, and leakage in full closed
position shall not exceed 2 percent of unit rated capacity against inlet pressure of 2
inch wg (500 pascal) with all outlets sealed shut and inlets fully open.
2. Variable Air Volume Units (VAV): DDC controlled, variable air volume, with field
adjustable maximum and minimum set points complete with the following:
3. Constant volume single duct. Units shall contain within the casing a mechanical
constant-air volume control designed to operate by inlet air pressure without outside
power. Regulators shall be constructed of nonferrous parts and shall be guaranteed to
maintain delivered air volume at plus or minus 5 percent of unit specified airflow
subjected to inlet pressure up to 1500 pa (6 inches water gage).
L. Controls: DDC type, microprocessor-based controls with integral airflow transducer and
room temperature sensor. DDC controller shall be furnished by VAC instrumentation and
controls manufacturer specified under other Division 15 Sections, mounted and calibrated
by the VAV manufacturer to meet the design parameters and to provide control with the
following features:
M. .Tests: Reports for High-Pressure Ductwork, Low Pressure Ductwork, Variable and
Constant Volume Boxes shall include sound ratings submitted in terms of discharge sound-
power levels in each of the second through sixth octave bands for specified or indicated inlet
pressure ranges. A nominal space Noise Criteria (NC) index shall be shown for at least
three operating points, including ratings at design, maximum, and minimum volume
operation.
1. Coat liner surfaces and edges with erosion-resistant coating or cover with perforated
metal.
D. Plenum Air Inlets: Round stub connections or S-slip and drive connections for duct
attachment.
F. Access: Removable panels to permit access to dampers and other parts requiring service,
adjustment, or maintenance; with airtight gasket and quarter-turn latches.
G. Volume Damper: Construct of galvanized steel with peripheral gasket and self-lubricating
bearings.
J. Factory-mounted and -wired controls: Mount electrical components in control box with
removable cover. Incorporate single-point electrical connection to power source.
K. Control Panel Enclosure: IP 21 to IEC 60529, with access panel sealed from airflow and
mounted on side of unit.
1. With central system fan operating in occupied mode, sequence the controls as
follows:
2. With central system fan operating in unoccupied mode, sequence the controls as
follows:
3. With central system fan operating in unoccupied mode, sequence the controls as
follows:
A. Testing Requirements: Test and rate air terminals according to ARI 880, "Industry Standard
for Air Terminals."
B. Identification: Label each air terminal with plan number, nominal airflow, maximum and
minimum factory-set airflows, coil type, and ARI certification seal.
PART 3 - EXECUTION
0.1 INSTALLATION
A. Install air terminals level and plumb, according to manufacturer's written instructions,
rough-in drawings, original design, and referenced standards; and maintain sufficient
clearance for normal service and maintenance.
0.2 CONNECTIONS
C. Ground equipment.
A. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and
equipment.
0.4 CLEANING
A. After completing system installation, including outlet fittings and devices, inspect exposed
finish. Remove burrs, dirt, and construction debris, and repair damaged finishes.
0.5 COMMISSIONING
A. Verify that installation of each air terminal is according to the Contract Documents.
B. Check that inlet duct connections are as recommended by air terminal manufacturer to
achieve proper performance.
0.6 DEMONSTRATION