APPROVED: BY: A.HASANI AT: 03.02.18 DRAWING NO.: Sh. No.: 000
STANDARD: - FULMEN REF.: E/2344 GE30OMR=ZOOG CONT 0001
DWG NO. PART SH. NO. REVISION TITLE
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
1- TECHNICAL SPECIFICATION
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
DIRECT
TRANSFER TRIP
DISTANCE
ROTECTION DC FAIL/ RECEIVED CBF STAGE2 SF6 PRESSURE LOW -
PROTECTION PSB
RELAY FAULTY SUB II (CH.NO.3 & NO.4.) OPERATED FIRST STAGE
OPERATED
TRIP
(BACKUP)
LINE CVT MCB/FUSE TELEPROTECTION T.C.S 1or2 RELAY LOCKOUT RELAY C.B-QA1 BLOCK DUE
FAIL CHANNEL FAULTY COIL OPERATED OPERATED TO LOSS OF SF6
CB/DS/MARSHALING
SOTF CB-QA1 SPRING URGENT
A/R DEFINITE TRIP BOX HEATING
PROTECTION TRIP CHARGE FAIL NON URGENT
SUPPLY FAIL
BLANK
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
CHECKED F.GHAZI 03.02.18 CONSULTING ENGINEERS: ALARM WINDOWS DWG. NO. 4100
FULMEN REF.: APPROVED A.HASANI 03.02.18 ANACO 132 KV LINE =E01&=E03 GE30OMR=ZOOG CONT.
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
74
75 C.B-QA1 IN LOCAL MODE(+W) X +W R
76 C.B-QA1 LOCKOUT RESET COMMAND (+YV) X X TO(+R)
77 C.B-QA1 LOCKOUT RESET COMMAND (+R) X
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93 CB/DS MOTOR SUPPLY FAIL(+R) X X X
94
95
96 CB-QA1 SPRING CHARGE FAIL (+R) X X X
97
98
99 OPERATION DC SUPPLY FAIL (+W)
100 CONTROL DC SUPPLY FAIL (+W)
101 CONTROL /OPERATION DC SUPPLY FAIL (+W) X X X
102
103 SF6 PRESSURE LOW - FIRST STAGE (+R) X X X
104 C.B-QA1 BLOCK DUE TO LOSS OF SF6 (+R) X X X
105
106
107
108
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
109
110 DS-QB1 CLOSE COMMAND FROM SCADA (+YV) X TO (+W)
111 DS-QB1 OPEN COMMAND FROM SCADA (+YV) X TO (+W)
112
113 CB-QA1 CLOSE COMMAND FROM SCADA (+YV) X TO (+W)
114 CB-QA1 OPEN COMMAND FROM SCADA (+YV) X TO (+W)
115
116 DS-QB9 CLOSE COMMAND FROM SCADA (+YV) X TO (+W)
117 DS-QB9 OPEN COMMAND FROM SCADA (+YV) X TO (+W)
118 AUTO RECLOSER OFF (+W) X X
119 AUTO RECLOSER ON (+W) X X
120 AUTO RECLOSER CB TRIP LOCKOUT (+R) X X
121
122 AUTO RECLOSER IN SERVICE (+R) X X
123 AUTO RECLOSER IN PROGRESS (+R) X X
124 AUTO RECLOSER OUT OF SERVICE (+R) X X
125 AUTO RECLOSER BLOCKED (+R) X
126 LINE CURRENT (PH.A) (+R) X
127 LINE CURRENT (PH.B) (+R) X
128 LINE CURRENT (PH.C) (+R) X
129 NEUTRAL CURRENT (+R) X
130 LINE VOLTAGE (PH.A)(+R) X
131 LINE VOLTAGE (PH.B) (+R) X
132 LINE VOLTAGE (PH.C) (+R) X
133
134 LINE VOLTAGE Vab (+R) X
135 LINE VOLTAGE Vbc (+R) X
136 LINE VOLTAGE Vca (+R) X
137
138 CB SYNCHRO CALLING FROM SCADA (+YV) X TO (+W)
139 CB SYNCHRO CANCELING FROM SCADA (+YV) X TO (+W)
140
141
142
143
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
AUX/GR TRANS
PROTECTION DC FAIL CB/DS/MARSHALING
UV/OV PROTECTION TRANS PRESURE TRANS OIL LEVEL PRESSURE RELIEF AUX/GR TRANS OIL CBF SRAGE 1
RELAY FAULTY SUB Ⅱ BOX HEATING SUPPLY
TRIP RELIEF TRIP ALARM TRIP TEMP HIGH ALARM OPERATED
FAIL
DIFFERENTIAL RELAY TRANS OVER FLUX TRANS TRANS BUCHHOLZ AUX/GR TRANS CBF SRAGE 2
T.C.S 1OR2 OPERATED CB SPRING CHARGE FAIL
TRIP TRIP BUCHHOLZ TRIP ALARM BUCHHOLZ TRIP OPERATED
TRANS
TRANS THERMAL TRANS OIL/WINDING AUX/GR TRANS OIL OLTC OIL LEVEL SF6 PRESSURE LOW CB SF6 PRESSURE LOW-
REF TRIP(HV/LV) OIL/WINDING
OVER LOAD TEMP HIGH ALARM TEMP HIGH TRIP ALARM BLOCK FIRST STAGE
TEMP HIGH TRIP
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
CHECKED F.GHAZI 03.02.18 CONSULTING ENGINEERS: ALARM WINDOWS DWG. NO. 4200
FULMEN REF.: APPROVED A.HASANI 03.02.18 ANACO 132/20KV TRANSFORMER =E02&E04 GE30OMR=ZOOG CONT.
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
41
42 TRANS OIL LEVEL ALARM (+R) X X
43 TRANS. BUCHHOLZ ALARM (+R) X X
44 TRANS. WINDING TEMP HIGH ALARM (HV) (+R)
45 TRANS. WINDING TEMP HIGH ALARM (LV) (+R)
46 TRANS. OIL TEMP HIGH ALARM (+R)
47 TRANS. OIL/ WINDING TEMP HIGH ALARM (+R) X X
48 TRANS. MECHANICAL PROTECTION ALARM (+R) X
49
50
51 TRANS. COOLING FAN FAILURE (+R) X X
52 H/L/S FAILURE (+R)
53 CONTROL POWER FAILURE (+R)
54 TRANS. CUBICLE AC SUPPLY FAIL (+R) X X X
55
56
57
58
59 AUX./GR.TRANS. PRESSURE RELIEF TRIP (+R) X X X
60 AUX./GR.TRANS. BUCHHOLZ TRIP (+R) X X X
61 AUX./GR.TRANS. OIL TEMP HIGH TRIP (+R) X X X
62 AUX./GR.TRANS. MECHANICAL PROT. TRIP (+R) X
63
64
65 AUX./GR.TRANS. OIL LEVEL ALARM (+R) X X
66 AUX./GR. TRANS. BUCHHOLZ ALARM (+R) X X
67 AUX./GR.TRANS. OIL TEMP. HIGH ALARM (+R) X X
68 AUX./GR. TRANS. MECHANICAL ALARM (+R) X
69
70
71 T.C.S 1or2 OPERATED (HV) (+R) X X X
72
73
74
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
75
76 OLTC OIL LEVEL ALARM (+R) X X X
77
78
79
80
81
82
83 CONTROL DC SUPPLY FAIL (+W) X X X
84
85
86 LOCKOUT RELAY OPERATED HV (+R) X X X
87
88
89 CB/DS/MARSHALING BOX HEATING SUPPLY FAIL (+R) X X X
90
91
92 CB SPRING CHARGE FAIL(HV)(+R) X X X
93 SF6 PRESSURE LOW CB BLOCK (HV)(+R) X X X
94
95
96
97
98
99
100 CB/DS MOTOR SUPPLY FAIL (+SV) X X X
101 CB SPRING CHARGE FAIL (+SV)
102 C.B BLOCK DUE TO LOSS OF SF6 (+SV)
103 CB BLOCK- LOSS OF SF6/SPRING CHARGE FAIL (+SV) X X X
104 CBF STAGE 1 OPERATED (+R) X X X
105 CBF STAGE 2 OPERATED (+R) X X X X
106
107 SF6 PRESSURE LOW - FIRST STAGE (+R) X X X
108
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
109
110
111
112
113 CB-QA1 CLOSE COMMAND FROM SCADA (+YV) X TO (+W)
114 CB-QA1 OPEN COMMAND FROM SCADA (+YV) X TO (+W)
115
116
117 DS-QB1 CLOSE COMMAND FROM SCADA (+YV) X TO (+W)
118 DS-QB1 OPEN COMMAND FROM SCADA (+YV) X TO (+W)
119
120
121
122
123 DS-QB1 CLOSE POS (+W) X
124 DS-QB1 OPEN POS (+W) X
125
126
127 CB-QA1 CLOSE POS (+W) X
128 CB-QA1 OPEN POS (+W) X
129
130
131
132
133
134 C.B-QA1 IN LOCAL MODE(+W) X +W R
135 C.B-QA1 LOCKOUT RESET COMMAND (+YV) X X TO(+R)
136 C.B-QA1 LOCKOUT RESET COMMAND (+R) X
137
138 FEEDER CURRNT PH.A (+R) X
139 FEEDER CURRNT PH.B (+R) X
140 FEEDER CURRNT PH.C (+R0 X
141 NEUTRAL CURRENT 9+R) X
142
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
BB.2 FREQUENCY
132KV BUSBAR CONTROL DC BB.1 FREQUENCY
LOAD SHEDDING
PROTECTION TRIP SUPPLY FAIL LOAD SHEDDING ST.3
ST.4
DS/MARSHALING
132KV BB1&BB2 BB.2 FREQUENCY
BOX HEATING SPARE
CVT FAIL LOAD SHEDDING ST.1
SUPPLY FAIL
NON URGENT
BLANK
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
CHECKED F.GHAZI 03.02.18 CONSULTING ENGINEERS: ALARM WINDOWS DWG. NO. 4300
FULMEN REF.: APPROVED A.HASANI 03.02.18 ANACO 132KV BUS COUPLER GE30OMR=ZOOG CONT.
1
2 PROTECTION DC SUPPLY FAIL (+R)
3 BB.P RELAY FAULTY (+R)
4 UNDER VOLTAGE RELAY B.B.1 FAULTY (+R)
5 UNDER VOLTAGE RELAY B.B.2 FAULTY (+R)
6 PROTECTION DC SUPPLY FAIL / RELAY FAULTY (+R) X X X
7
8
9
10
11 132KV BUSBAR PROTECTION TRIP (+R) X X X X
12
13
14 UV/OV PROTECTION TRIP (B.B.1) (+R) X
15 UV/OV PROTECTION TRIP (B.B.2) (+R) X
16 UV/OV PROTECTION TRIP (+R) X X X
17
18 SUB/SCADA SWITCH IN SUB POSITION (+W) X
19 SUB/SCADA SWITCH IN SCADA POSITION (+W) X
20
21
22
23
24 132KV BB.1 CVT FAIL (+R) X
25 132KV BB.2 CVT FAIL (+R) X
26 132KV BB.1&BB.2 CVT FAIL (+R) X X
27
28 BUSBAR CT SUPERVISION ALARM (+R) X X X
29
30
31 D.S MOTOR SUPPLY FAIL (+SV) X X X
32
33 CONTROL DC SUPPLY FAIL (+SV) X X X
34
35
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
36
37
38
39
40 DS/MARSHALING BOX HEATING SUPPLY FAIL (+SV) X X X
41 DS/QB5 D.S CLOSE POS (+W) X X
42 DS/QB5 D.S OPEN POS (+W) X X
43
44
45 QB5 D.S OPEN COMMAND FROM SCADA (+YV) X TO(+W)
46 QB5 D.S CLOSE COMMAND FROM SCADA (+YV) X TO(+W)
47
48
49
50 BB.1 FREQUENCY LOAD SHEDDING ST.1 (+R) X X X X
51 BB.1 FREQUENCY LOAD SHEDDING ST.2 (+R) X X X X
52 BB.1 FREQUENCY LOAD SHEDDING ST.3 (+R) X X X X
53 BB.1 FREQUENCY LOAD SHEDDING ST.4 (+R) X X X X
54
55
56 BB.2 FREQUENCY LOAD SHEDDING ST.1 (+R) X X X X
57 BB.2 FREQUENCY LOAD SHEDDING ST.2 (+R) X X X X
58 BB.2 FREQUENCY LOAD SHEDDING ST.3 (+R) X X X X
59 BB.2 FREQUENCY LOAD SHEDDING ST.4 (+R) X X X X
60
61
62
63
64 BB.1 UNDER FREQUENCY TRIP (+R)
65 BB.2 UNDER FREQUENCY TRIP 9+R)
66 BB.1&BB.2 UNDER FREQUENCY TRIP (+R) X X X X
67
68
69
70
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
LOCKOUT RELAY
PT MCB FAIL FAIL
OPERATED
BLACK
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
CHECKED F.GHAZI 03.02.18 CONSULTING ENGINEERS: ALARM WINDOWS DWG. NO. 6100
FULMEN REF.: APPROVED A.HASANI 03.02.18 ANACO 20KV INCOMING GE30OMR=ZOOG CONT.
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
LOCKOUT RELAY
O/C , E/F TRIP
OPERATED
20KV BB.1 PT
SPARE
MCB/FUSE FAIL
20KV BB.2 PT
MCB/FUSE FAIL URGENT
NON URGENT
BLANK
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
CHECKED F.GHAZI 03.02.18 CONSULTING ENGINEERS: ALARM WINDOWS DWG. NO. 6200
FULMEN REF.: APPROVED A.HASANI 03.02.18 ANACO 20KV BUS COUPLER GE30OMR=ZOOG CONT.
1
2
3 O.C , E.F RELAY FAULTY (+R) X X X
4
5
6
7
8
9
10 INST.& INV. TIME O/C TRIP (+R)
11 INST.& INV. TIME E/F TRIP (+R)
12 O/C , E/F TRIP (+R) X X X X
13
14
15
16
17
18
19
20
21
22 CB SPRING CHARGE FAIL (+SWG) X X X
23
24 20KV BB.1 PT MCB/FUSE FAIL (+SWG) X X X
25 20KV BB.2 PT MCB/FUSE FAIL (+SWG) X X X
26
27 T.C.S RELAY OPERATED (+R) X X X
28
29 LOCK OUT RELAY OPERATED (+R) X X X
30
31 CB MOTOR SUPPLY FAIL (+SWG) X X X
32
33
34
35
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
36
37
38 CB-QA1 OPEN POS (+W) X X
39 CB-QA1 CLOSE POS (+W) X X
40
41
42 CB-QA1 CLOSE COMMAND FROM SCADA(+YV) X TO(+W)
43 CB-QA1 OPEN COMMAND FROM SCADA (+YV) X TO(+W)
44
45
46
47 C.B-QA1 IN LOCAL (+W) X
48 C.B-QA1 LOCKOUT RESET (+YV) X
49
50
51
52 CB-QA1 IN SERVICE X X
53 CB-QA1 OUT OF SERVICE X X
54
55 20KV COUPLER CURRENT PH.A(+R) X
56 20KV COUPLER CURRENT PH.B(+R) X
57 20KV COUPLER CURRENT PH.C(+R) X
58 20KV NEUTRAL CURRENT (+R) X
59
60 20KV BB.1 COUPLER VOLTAGE PH.A(+SWG) X
61 20KV BB.1 COUPLER VOLTAGE PH.B(+SWG) X
62 20KV BB.1 COUPLER VOLTAGE PH.C(+SWG) X
63
64 20KV BB.2 COUPLER VOLTAGE PH.A(+SWG) X
65 20KV BB.2 COUPLER VOLTAGE PH.B(+SWG) X
66 20KV BB.2 COUPLER VOLTAGE PH.C(+SWG) X
67
68
69
70
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
BLANK
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
CHECKED F.GHAZI 03.02.18 CONSULTING ENGINEERS: ALARM WINDOWS DWG. NO. 6300
FULMEN REF.: APPROVED A.HASANI 03.02.18 ANACO 20KV OUTGOING GE30OMR=ZOOG CONT.
1
2 O/C , E/F TRIP (+R) X X X X
3
4 SENSITIVE E/F TRIP (+R) X X X X
5
6 CB SPRING CHARGE FAIL (+SWG) X X X
7
8
9
10
11 AUTO RECLOSER IN PROGRESS (+R) X X +W Y
12
13
14 CB MOTOR SUPPLY FAIL (+SWG) X X X
15 T.C.S RELAY OPERATED (+R) X X X
16
17 PROTECTION DC FAIL/RELAY FAULTY (+R) X X X
18
19 CB-QA2 OPEN POS (+W) X
20 CB-QA2 CLOSE POS (+W) X
21
22 ES-QC9 OPEN POS (+W) X
23 ES-QC9 CLOSE POS (+W) X
24
25
26 C.B-QA2 IN LOCAL (+W) X
27 C.B-QA2 LOCKOUT RESET FROM SCADA (+YV) X TO(+R)
28
29
30
31 CB-QA2 CLOSE COMMAND (+YV) X TO(+W)
32 CB-QA2 OPEN COMMAND FROM SCADA (+YV) X TO(+W)
33
34
35
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
36
37
38
39
40 A/R OPERATED(+R) X X X
41 A/R UNSUCCESSFUL(+R) X X X
42 A/R ON/OFF S.SW IN ON POSITION (+W) X X
43 A/R ON/OFF S.SW IN OFF POSITION (+W) X X
44
45
46 CB-QA2 IN SERVICE (+SWG) X X
47 CB-QA2 OUT OF SERVICE (+SWG) X X
48
49
50
51
52 LOCK OUT RELAY OPERATED (+R) X X X
53
54
55
56 CURRENT PH.A (+R) X
57 CURRENT PH.B (+R) X
58 CURRENT PH.C (+R) X
59 NEUTRAL CURRENT (+R) X
60
61
62
63
64
65
66
67
68
69
70
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
110V DC 110VDC
EVENT RECORDER ALARM DC SUPPLY
INCOMING PANEL VOLTAGE
TROUBLE FAIL
MCCB FAIL FAULT
OUTDOOR
48V DC BATTERY FAUL RECORDER INDOOR PANELS
PANELS AC
CHARGER FAILURE TROUBLE AC SUPPLY FAIL
SUPPLY FAIL
URGENT
SDH TELECOM LVAC DC SUPPLY
SYSTEM FAULTY FAIL NON URGENT
BLACK
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
CHECKED F.GHAZI 03.02.18 CONSULTING ENGINEERS: ALARM WINDOWS DWG. NO. 9900
FULMEN REF.: APPROVED A.HASANI 03.02.18 ANACO GENERAL / COMMON GE30OMR=ZOOG CONT.
1
2 110V DC BATTERY CHARGER FAILURE (+NK) X X X X
3
4
5
6
7 110V DC INCOMING MCCB FAIL (+NK) X X X X
8
9
10 48V DC BATTERY CHARGER FAILURE (+NQ) X X X X
11
12
13
14
15 48V DC INCOMING MCCB FAIL (+NQ) X X X X
16
17
18
19
20
21 FIRE DETECTION ALARM (FIRE ALARM PANEL)
22 FIRE FIGHTING ALARM (FIRE ALARM PANEL)
23 FIRE ALARM (FIRE ALARM PANEL) X X
24
25 SDH TELECOM SYSTEM FAULTY (+SDH) X X X
26
27
28
29 AC SUPPLY OF SWITCHGEAR FAULTY (+SWG)
30 AC ALARM SUPERVISION VOLTAGE FAULTY (+SWG)
31 20 KV SWITCHGEAR AC SUPPLY FAILURE (+SWG) X X X
32
33
34
35
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
36
37 110VDC PANEL VOLTAGE FAULT X X X
38
39
40 EVENT RECORDER TROUBLE (+XP21) X X X
41
42 FAUL RECORDER TROUBLE (+XP11) X X X
43
44
45 LVAC INCOMMING 1 U/V OPERATED (+NE)
46 LVAC INCOMMING 2 U/V OPERATED (+NE)
47 LVAC INCOMMING UV OPERATED (+NE) X X X
48
49 LOSS OF CONTROL SUPPLY-CBs (+NE)
50 LOSS OF MOTOR SUPPLY-CBs (+NE)
51 LVAC DC SUPPLY FAIL (+NE) X X X
52
53
54 LVAC INCOMMING CB-Q01 TRIP (+NE)
55 LVAC INCOMMING CB-Q02 TRIP (+NE)
56 LVAC INCOMMING CB-Q03 TRIP (+NE)
57 LVAC INCOMMING CBs TRIP (+NE) X X X
58
59 ALARM DC SUPPLY FAIL +W) X X X
60
61 INDOOR PANELS AC SUPPLY FAIL (+R) X X X
62 OUTDOOR PANELS AC SUPPLY FAIL (+R) X X X
63
64
65 LVAC OUTGOING FEEDRES MCB/MCCB TRIP (+R) X X X
66
67 LVDC OUTGOING MCB TRIP (+R) X X X
68
69
70 LOSS OF SYNCH SUPPLY/SYNCH. RELAY FAULTY (+W) X X X
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
71
72
73 LVDC CB/Q1 OPEN POS (+NK) X
74 LVDC CB/Q1 CLOSE POS (+NK) X
75
76 LVAC CB/Q01 OPEN POS (+NE) X
77 LVAC CB/Q01 CLOSE POS (+NE) X
78
79 LVAC CB/Q02 OPEN POS (+NE) X
80 LVAC CB/Q02 CLOSE POS (+NE) X
81
82 LVAC CB/Q03 OPEN POS (+NE) X
83 LVAC CB/Q03 CLOSE POS (+NE) X
84
85 SYNCHRONIZER SELECTOR SWITCH IN ON POSSITION (+W) X
86 SYNCHRONIZER SELECTOR SWITCH IN MANUAL POSITION (+W) X
87 SYNCHRONIZER SELECTOR SWITCH IN BYPASS POSSITION (+W) X
88
89
90
91 SYNCHRONIZER SELECTOR SWITCH ON COMMAND FROM SCADA (+YV) X TO(+W)
92 SYNCHRONIZER SELECTOR SWITCH OFF COMMAND FROM SCADA (+YV) X TO(+W)
93
94
95
96 LVAC AUTO/MANUAL SELECTOR SWITCH IN AUTO POSITION X
97 LVAC AUTO/MANUAL SELECTOR SWITCH IN MANUAL POSITION X
98
99 LVAC PRIORITY SELECTOR SWITCH IN T1 POSITION X X
100 LVAC PRIORITY SELECTOR SWITCH IN T2 POSITION X X
101
102
103
104
105
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
CHECKED F.GHAZI 03.02.18 CONSULTING ENGINEERS: DWG. NO. 9903
FULMEN REF.: APPROVED A.HASANI 03.02.18 ANACO GENERAL / COMMON GE30OMR=ZOOG CONT.
AVR PANEL AC
SPARE SPARE SPARE
SUPPLY FAIL
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED A.TAEFI 03.02.18 A.R.W.A SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN A.TAEFI 03.02.18 ARDABIL REGIONAL WATER AUTHORITY 132/20 KV SUBSTATION SH.NO.
CHECKED F.GHAZI 03.02.18 CONSULTING ENGINEERS: ALARM WINDOWS DWG. NO. 9910
FULMEN REF.: APPROVED A.HASANI 03.02.18 ANACO AVR GE30OMR=ZOOG CONT.
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED M.HAMIDI 04.11.13 M.R.E.C SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN M.HAMIDI 04.11.13 MAZANDARAN REGIONAL ELECTRIC CO. 132/20 KV SUBSTATION SH.NO.
34
35
36 AVR2 CONTROL IN AUTO MODE (+AVR) X X +AVR B
37 AVR2 CONTROL IN MANUAL MODE (+AVR) X X +AVR G
38
39
40 AVR OPERATION MODE IN INDIVIDUAL (+AVR) X X
41
42 AVR1 OPERATION MODE IN MASTER (+AVR) X X
43 AVR2 OPERATION MODE IN MASTER (+AVR) X X
44
45
46 RAISE COMMAND TO OLTC 1 FROM SCADA (+AVR) X X TO(+AVR)
47 LOWER COMMAND TO OLTC 1 FROM SCADA (+AVR) X X TO(+AVR)
48 OLTC1 EMERGENCY STOP FROM SCADA (+AVR) X X TO(+AVR)
49
50
51
52 RAISE COMMAND TO OLTC 2 SCADA (+AVR) X X TO(+AVR)
53 LOWER COMMAND TO OLTC 2 SCADA (+AVR) X X TO(+AVR)
54 OLTC2 EMERGENCY STOP SCADA (+AVR) X X TO(+AVR)
55
56
57
58
59
60
61
62
63
64
65
66
67
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED M.HAMIDI 04.11.13 M.R.E.C SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN M.HAMIDI 04.11.13 MAZANDARAN REGIONAL ELECTRIC CO. 132/20 KV SUBSTATION SH.NO.
68
69
70 AVR1 IN MASTER POSITION FROM SCADA X X
71 AVR1 IN SLAVE POSITION FROM SCADA X X
72
73
74 AVR2 IN MASTER POSITION FROM SCADA X X
75 AVR2 IN SLAVE POSITION FROM SCADA X X
76
77
78 AVR1 IN PARALLEL POSITION FROM SCADA X X
79 AVR1 IN INDIVITUAL POSITION FROM SCADA X X
80
81
82 AVR2 IN PARALLEL POSITION FROM SCADA X X
83 AVR2 IN INDIVITUAL POSITION FROM SCADA X X
84
85
86 AVR1 IN AUTO POSITION FROM SCADA X X
87 AVR1 IN MANUAL POSITION FROM SCADA X X
88
89
90 AVR2 IN AUTO POSITION FROM SCADA X X
91 AVR2 IN MANUAL POSITION FROM SCADA X X
92
93
94
95
96
97
98
99
100
101
0 A.TAEFI A.HASANI 03.02.18 ORIGINAL ISSUE DESIGNED M.HAMIDI 04.11.13 M.R.E.C SIGNALING LIST OMRANI 4 ZONE
1 A.TAEFI A.HASANI 12.03.18 DUE TO ANACO COMMENTS DRAWN M.HAMIDI 04.11.13 MAZANDARAN REGIONAL ELECTRIC CO. 132/20 KV SUBSTATION SH.NO.