Professional Documents
Culture Documents
CEILING ROSE
1 GANG 1 WAY
SWITCH
CONSUMER UNIT
1
TWO WAY SWITCHING
CEILING ROSE
1 GANG 2 WAY
SWITCH
1 GANG 2 WAY
SWITCH
CONSUMER UNIT
2
INTERMEDIATE SWITCHING
CEILING ROSE
1 GANG 2 WAY
SWITCH
INTERMEDIATE
SWITCH
1 GANG 2 WAY
SWITCH
3
JOINT BOX METHOD
1 GANG 1 WAY
SWITCH
4
ONE WAY & 2 WAY + INTERMEDIATE
SWITCHING
5
No. 7 a (part 2)
Instruction to Trainee
First produce the wiring diagrams for the ‘3’ stages of the lighting circuit.
Then on a wooden board layout the 3 surface light switch boxes, 1 round
lighting pattress and 1 two way 63 amp consumers unit. Then surface wire
and clip in 1.0mm2 thermoplastic PVC and c.p.c cables to produce the
lighting circuit shown below. The circuit should be tested and marked after
each of the ‘3’ stages. All cables should be clipped straight, flat and have
acceptable bending radius.
Stage 2 : Light ‘A’ switched via switch ‘1’ and ‘2’ (2 way switching)
Stage 3 : Light ‘A’ switched via switch ‘1’, ‘2’ and ‘3’ (2 way and
intermediate switching)
6
TESTING
Why Test
All circuits require testing to prove that they operate correctly, are
safe to use and all equipment is correctly selected and erected.
Continuity of C.P.C
Polarity
Proves that the circuit switch and fuse within the line conductor.
Insulation Resistance
This test proves that the insulation of the circuit conductors has not
broken down through age or during installation.
7
Test Sequence for Combined Continuity of CPC & Polarity
• Check battery
• Set to ohms
• Test link
• Link line and c.p.c in the consumers unit of the circuit under
test
8
Positioning the Link for Continuity Test
The link is inserted within the consumers unit between line and
c.p.c of the circuit that requires testing. Great care must be taken to
remove the link before energizing the consumer unit.
9
COMBINED CONTINUITY OF CPC AND POLARITY OF A LIGHTING
CIRCUIT
Stage 1
Test between switching live and cpc at the furthest lighting point record the highest reading in ohms
under the box headed R1 + R2. Next operate switch (es) to prove polarity of that lighting point
leaving the switch (es) in the on position.
10
COMBINED CONTINUITY OF CPC AND POLARITY OF A LIGHTING
CIRCUIT
Stage 2
The test at the switch (es) of the furthest lighting point will prove continuity to this point this test is
required during an initial inspection or where metal switch plates are used on lighting circuits.
11
COMBINED CONTINUITY OF CPC AND POLARITY OF A LIGHTING
CIRCUIT
Stage 3
Repeat test for all other lighting points on that circuit in order to prove polarity leaving each lighting
point in the on position.
12
COMBINED CONTINUITY OF CPC AND POLARITY OF A LIGHTING
CIRCUIT
Stage 4
The test at the switch (es) of all the lighting point to prove continuity to this point this test is required
during an initial inspection or where metal switch plates are used on lighting circuits.
13
COMBINED CONTINUITY OF CPC AND POLARITY OF A LIGHTING
CIRCUIT
Stage 5
The test at the switch (es) of all the lighting point to prove continuity to this point this test is required
during an initial inspection or where metal switch plates are used on lighting circuits.
14
Continuity of c.p.c and polarity when the lamp holder is an
Edison screw type
15
Test Sequence for Insulation Resistance for Circuits that are
not Additionally Protected by RCD’s or RCBO’s
• Check battery
Test Results
Circuit description Fuse size Cable size Continuity Ω Insulation
resistance
Polarity
16
INSULATION RESISTANCE TEST
Stage 1
Test between live conductors
17
Stage 2
Test between line conductor and earthing conductor
Stage 3
Test between neutral conductor and earthing conductor
18
Test Sequence for Insulation Resistance for Circuits that are
Additionally Protected by a Main RCD’s Switch (students
come up with list)
• Check battery
Stage 1
• Test between out going line and neutral record reading in
megohms (minimum of 1 megohm)
Stage 2
• Test between out going line and c.p.c record reading in
megohms (minimum of 1 megohm)
Stage 3
• Test between out going neutral and c.p.c record reading in
megohms (minimum of 1 megohm)
19
Stage 4
• At the tails test between live conductors (line and neutral)
Stage 5
• At the tails test between line and earthing conductor
Stage 6
• At the tails test between neutral and earthing conductor
Test Results
Circuit description Fuse size Cable size Continuity Ω Insulation
resistance
Polarity
Stage 1
Testing from the disconnected circuit between line and neutral
conductors
20
Stage 2
Testing from the disconnected circuit between line and c.p.c
conductors
Stage 3
Testing from the disconnected circuit between neutral and c.p.c
conductors
21
Stage 4
Testing at the tails test between live conductors (line and
neutral) with the main switch off
Stage 5
Testing at the tails test between line and earthing conductors
with the main switch off
22
Stage 6
Testing at the tails test between neutral and earthing conductors
with the main switch off
23
Exercise No. 7 a (part 2)
24
Exercise No. 7 a (part 2)
25
Exercise No. 7 a (part 2)
26
Exercise No. 7 a (part 2)
27
Exercise No. 7 a (part 3)
Instruction to Trainee
On a wooden board layout the 3 surface light switch boxes, 3 round
lighting pattress and 1 two way 63 amp consumers unit. Then surface
wire and clip in 1.0mm2 thermoplastic PVC and c.p.c cables to produce
the lighting circuit shown below. The circuit should be tested and marked
after each of the ‘3’ stages. All cables should be clipped straight, flat and
have acceptable bending radius.
28
Exercise No. 7 a (part 3)
29
Exercise No. 7 a (part 3)
30
Exercise No. 7 a (part 3)
31
Exercise No. 7 a (part 3)
32
PERMITTED CABLE ROUTES
Cable Routing
33
2 PLATE ONE WAY SWITCHING
1 GANG 1 WAY
SWITCH
34
2 PLATE 2 WAY SWITCHING
35
2 PLATE 2 WAY AND INTERMEDIATE SWITCHING
36