CONTROL FOR DOUBLE SIDE ENTRY (BLOWER ON FOR BOTH SIDE ENTRY)

LOGIC
EMERGENCY SWITCH – 1 NOS PROVIDED (INSIDE THE CABINET)
PRESSING EMERGENCY SWITCH - BOTH THE DOOR GETS UNLOCKED, NO
INTERLOCKING,
NO BLOWER ON/OFF
BLOWER TIME –ADJUSTABLE (0-3 MINS) AS PER REQUIRMENT
ANY DOOR OPENS – TUBELIGHT GETS ON AND GETS OFF AFTER THE CYCLE GETS
COMPLETE
NOTE : IF CYCLE IS NOT FOLLOWED, CYCLE WILL BE REST IN 30 SEC

NOMENCLATURE :
D1: ENTRY DOOR OF AIRSHOWER
D2: EXIT DOOR OF AIRSHOWER

DOOR OPEN AND CLOSE WILL BE SENSE BY WHITE DOOR SENSORS- PROVIDED
FOR BOTH THE DOOR ENTRY(D1) AND EXIT(D2)
DOORS WILL BE LOCK WITH MAGNETIC LOCK – PROVIDED FOR BOTH THE DOOR
ENTRY (D1) AND EXIT (D2)

INTERLOCKING FOR BOTH THE DOORS :


ENTRY DOOR OPENS – EXIT DOOR CLOSE
EXIT DOOR OPENS – ENTRY DOOR CLOSE

1ST CYCLE– (ENTRY TO EXIT)


 DOOR D1 AND D2 BOTH ARE IN CLOSE AND UNLOCK CONDITION –
(NORMAL CONDITION)
 AS ENTRY DOOR (D1) IS OPEN EXIT DOOR (D2) GETS LOCK AND
TUBELIGHTS GETS ON
 AFTER THE CLOSING OF ENTRY DOOR BOTH THE DOORS D1 AND D2 ARE
LOCKED.
 BLOWER GETS ON FOR THE RESPECTIVE VARIABLE SET TIME (0-3 MINS)
 AFTER THE COMPLETION OF SET TIME - BLOWER GETS OFF AND EXIT
DOOR IS UNLOCKED.
(AT THAT TIME ENTRY DOOR IS IN LOCK CONDITION)
 AFTER THAT USER WILL OPEN THE EXIT DOOR AND GO OUT.
 AFTER THE CLOSING OF EXIT DOOR THE ENTRY DOOR WILL ALSO GET
UNLOCK AND TUBELIGHT WILL GET OFF
(NOW BOTH THE DOORS WILL BE IN CLOSE AND UNLOCK CONDITION) –
NORMAL CONDITION
1ST CYCLE GETS COMPLETE

CLEAN ROOMS AIR FILTRATION CONTAMINATION CONTROL EQUIPMETNS TURNKEY PROJECTS


2ND CYCLE– (EXIT TO ENTRY)
 DOOR D2 AND D1 BOTH ARE IN CLOSE AND UNLOCK CONDITION –
(NORMAL CONDITION)
 AS EXIT DOOR (D2) IS OPEN ENTRY DOOR (D1) GETS LOCK AND
TUBELIGHTS GETS ON
 AFTER THE CLOSING OF EXIT DOOR BOTH THE DOORS D2 AND D1 ARE
LOCKED.
 BLOWER GETS ON FOR THE RESPECTIVE VARIABLE SET TIME (0-3 MINS)
 AFTER THE COMPLETION OF SET TIME - BLOWER GETS OFF AND ENTRY
DOOR IS UNLOCKED.
(AT THAT TIME EXIT DOOR IS IN LOCK CONDITION)
 AFTER THAT USER WILL OPEN THE ENTRY DOOR AND GO OUT.
 AFTER THE CLOSING OF ENTRY DOOR THE EXIT DOOR WILL ALSO GET
UNLOCK AND TUBELIGHT WILL GET OFF
(NOW BOTH THE DOORS WILL BE IN CLOSE AND UNLOCK CONDITION) –
NORMAL CONDITION
2ND CYCLE GETS COMPLETE.

CLEAN ROOMS AIR FILTRATION CONTAMINATION CONTROL EQUIPMETNS TURNKEY PROJECTS


Airshower Logic Both side Entry

Timer Required : YES (Adjustable)


Nomenclature : D1 – Entry Door, D2 - Exit Door
Any door opens : Tube-light ON
Emergency switch : Inside the cabinet
Note : To bypass the cycle 30 sec reset time is provided.

From ENTRY SIDE :

Sr Entry door Exit door lock Tube light


State Blower
no. lock D1 D2
1. Power ON    

2. Entry Door D1 opened    

3. Entry Door D1 closed    


Time delay complete (0-5 Min 
4.   
Variable)
5. Exit Door D2 opened    

6. Exit Door D2 closed    

From EXIT SIDE :

Sr Entry door Exit door lock Tube light


State Blower
no. lock D1 D2
1. Power ON    

2. Exit Door D2 opened    

3. Exit Door D2 closed    

Time delay complete (0-5 Min 


4.   
Variable)
5. Exit Door D1 opened    

6. Exit Door D1 closed    

CLEAN ROOMS AIR FILTRATION CONTAMINATION CONTROL EQUIPMETNS TURNKEY PROJECTS