Point of ● Run CPU ● DI120~150

TCD - 133 DOOR OPEN LOCK REPETITION DEFECT Application


Detection ○ Speed CPU ● DI180~420

[Meaning] When door doesn’t open 3 consecutive times at stop. [Actions to take]

1. Check Landing Door Status (LDS)


Check all aspects of Landing Door open/close status.
(Sill gap, landing door bend)
[Diagram]
SWD_General_O 2. Check Car Door Status (CDS)
SWD_Is_StopSWD_I[VI_DOLS] [VO_OPEN] 1) Check open/close status of Car Door.
2) Check OLS SET values.
0X480FB 0x4802D 0x48083

3. Check open/close status of Car and Landing Door fitted.


TMC_Check(OPEN_LOCK_DETECT_
TIMER,FINISH_STATE) 4. Verify if DMC CUT of machine box is set to
NORMAL position.
xxx

5. Verify that OPEN command is sent.


TMC_Check(CLOSE_LOCK_
Row2 and line13 of DOA-100 LCD is 1 means that
DETECT_TIMER,FINISH_STATE) SWD_General_S open command is being made, and DMV-16 voltage
DCD_Door
ACD_Door_Code
[DC_DCO]
[SW_GS_OPEN_ZONE] is 0.7V ± 0.1V means that current TR turns on and open
[A_AUTO_DOOR_CLOSE] check_out command is being normally outputted.
xxx xxx
xxx 48E79H 48188H
6. Check DOLS wiring and input buffer operation (0x5026)
1) When door fully opens and strikes DOLS, row3 and
check_out line15 of DOA-100 LCD becomes 1. When R2LD RELAY
TMC_Start LED becomes OFF, DOLS input is normal.
(OPEN_LOCK_DETECT_TIMER) 2) If no changes are found, check voltage of wiring course up to
xxx
DOLS input buffer.
(For detail circuit, refer to 3x02228 I/O C[2])
TMC_Check(OPEN_LOCK_ ERS_Check 3) In door open, 0V of input buffer INB-02 voltage is normal.
DETECT_TIMER,FINISH_STATE) (ER_OPEN_LOCK)
TCD 132
7. Check CDS(Car Door Switch) input buffer (0x5018)
xxx xxx For detail circuit, refer to 3x02219 CTL C[4].
open_lock_3_counter++>=3
TCD 133 8. Check LDS(Landing Door Switch) input buffer(0x5019).
For detail circuit, refer to 3x02220 CTL C[5] and
xxx
3x02227 I/O C[1] .