You are on page 1of 1

LOW VOLTAGE POWER CABLES

300/500 V, NYMHY (Cu-f/PVC/PVC)


0.6/1 (1.2) kV, NYYHY (Cu-f/PVC/PVC)
( Flexible Copper Conductor,PVC Insulated,PVC Outer Sheated )
Standard Specification : SNI 04-6629.5 ; SNI IEC 60502-1, IEC 60227
*For Insulation colour can be based on Customer Request or Follow Standard.

NHYMHY & NYYHY


PHYSICAL PROPERTIES ELECTRICAL PROPERTIES
Conductor Max. Current - Carrying
Capacity at 30 °C * Max. Short
Nom Cross Approx. Overall Approx. Cable Max. DC Max. AC L Circuit Current
NYMHY NYYHY Section Area Diameter Weight Resistance
at 20 °C
Resistance
at 70 °C
in air in pipe at 1 Second

mm² mm kg/km ohm/km ohm/km mH/km A A kA


2 x 0,75 6.42 60 24.500 14.478 0.349 14 10 0.11
2 x 1,5 7.72 91 12.100 8.866 0.327 21 16 0.21
2 x 2,5 8.96 131 7.410 5.516 0.326 28 21 0.36
2 x 4 11.60 216 4.610 3.685 0.285 39 29 0.57
2 x 6 12.96 283 3.080 2.190 0.271 50 37 0.86
Flexible Copper Conductor Flexible Copper Conductor
2 x 10 17.84 512 1.830 1.376 0.269 74 55 1.43
2 x 16 20.04 702 1.150 0.870 0.256 98 - 2.29
2 x 25 25.48 1,085 0.727 0.627 0.247 136 - 3.58
PVC Insulated PVC Insulated 2 x 35 26.80 1,305 0.524 0.464 0.243 163 - 5.01
2 x 50 32.20 1,842 0.387 0.060 0.239 204 - 7.15
3 x 0,75 6.79 71 24.500 14.478 0.349 12 9 0.11
3 x 1,5 8.39 113 12.100 8.866 0.327 18 13 0.21
PVC Outer Sheated PVC Outer Sheated 3 x 2,5 9.69 164 7.410 5.516 0.326 24 18 0.36
3 x 4 12.29 262 4.610 3.685 0.285 33 24 0.57
3 x 6 13.74 348 3.080 2.190 0.271 42 31 0.86
3 x 10 19.02 629 1.830 1.376 0.269 62 46 1.43
3 x 16 21.17 869 1.150 0.870 0.256 82 - 2.29
3 x 25 27.02 1,341 0.727 0.627 0.247 114 - 3.58
3 x 35 28.43 1,642 0.524 0.464 0.243 136 - 5.01
3 x 50 34.23 2,317 0.387 0.060 0.239 172 - 7.15
4 x 0,75 7.41 85 24.500 14.478 0.349 12 9 0.11
4 x 1,5 9.38 142 12.100 8.866 0.327 16 12 0.21
4 x 2,5 10.60 200 7.410 5.516 0.326 21 16 0.36
4 x 4 13.67 326 4.610 3.685 0.285 29 22 0.57
4 x 6 15.07 428 3.080 2.190 0.271 37 28 0.86
4 x 10 20.96 833 1.830 1.376 0.268 56 42 1.43
4 x 16 23.31 1,159 1.150 0.870 0.256 73 - 2.29
4 x 25 29.85 1,809 0.727 0.627 0.247 102 - 3.58
4 x 35 31.41 2,213 0.524 0.464 0.243 123 - 5.01
4 x 50 38.30 3,185 0.387 0.060 0.239 156 - 7.15
*Further information about derating factors for arrangement can be found on supplementary technical information.

Application Standard Packing


Permanent installation in conduit or exposed • 1.5 - 10 sqmm in coil @ 100 m
wiring in dry room • 16 - 50 wooden drum @ 1000 m or @ 2000 m
• Length Tolerance per drum ± 2%

Special Features on Request


• Anti termite
• Anti Rodent
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category

44 - Sutrado Kabel Catalogue Sutrado Kabel Catalogue - 45