HVAC QUICK LOAD PROGRAM

COMPANY: DATE: Mar 11, 2023


PROJECT: PROJ. NO.:

MONTH TIME OUTDOOR AIR TEMPERATURES INDOOR AIR TEMP


AHU #
(1-12) (7am-6pm) SUMMER WINTER RH = 50.0% RH
AHU-1 hqlp 5 94.0°F db 74.0°F wb 12.0°F 72.0°F db 60.1°F wb
AHU TYPE HOURS OF
"U" VALUES GLASS SAFETY FACTORS
BLOWTHRU = BT 0PERATION
DRAWTHRU = DT (12, 16, 24) WALL ROOF GLASS BARE SHADED
DT 24 0.10 0.08 1.13 0.80 0.65

GLASS SOLAR HEAT GAIN


INT SHADE ? AREA PEAK
24 HR SHADE SAFETY
EXPOSURE SOLAR BTU/HR
(Y/N) (SQ.FT.) STORAGE FACTOR FACTOR
HEAT GAIN
N N 100 0 0.80 0.80 1.10 0
N S 100 4 0.45 0.80 1.10 158
N E 100 2 0.20 0.80 1.10 35
N W 100 6 0.48 0.80 1.10 253
N NE 100 1 0.17 0.80 1.10 15
N NW 100 7 0.40 0.80 1.10 246
N SE 100 3 0.27 0.80 1.10 71
N SW 100 5 0.51 0.80 1.10 224
SKYLIGHT HORIZ. 100 8 1.00 1.00 1.10 880
SUB-TOTAL = 1,884

TRANSMISSION HEAT GAIN


AREA EQUIVALEN TEMP.
SAFETY
EXPOSURE T TEMP. CORRECTIO "U" VALUE BTU/HR
(SQ.FT.) FACTOR
DIFF. N
WALL: N 100 #N/A 10 0.10 1.10 #N/A
WALL: S 100 13 10 0.10 1.10 253
WALL: E 100 13 10 0.10 1.10 253
WALL: W 100 34 10 0.10 1.10 484
WALL: NE 100 13 10 0.10 1.10 253
WALL: NW 100 13 10 0.10 1.10 253
WALL: SE 100 15 10 0.10 1.10 275
WALL: SW 100 35 10 0.10 1.10 495
ROOF: HORIZ. 100 43 10 0.04 1.10 233
GLASS: 900 22 1.13 1.10 24,611
PARTITION: 100 10 0.20 1.10 220
SUB-TOTAL = 27,760

INTERNAL HEAT GAIN


QUANTITY WATTS PER CONVERT MULTIPLIER SAFETY
BTU/HR
OR SQ.FT. SQ.FT. FACTOR FACTOR FACTOR
NO. OF PEOPLE: 10 @ 250 BTH PER PERSON 1.10 2,750
FLUOR. LIGHTS (SF): 1000 2.00 3.413 80% 1.10 6,007
INCAN. LIGHTS (SF): 1000 0.25 3.413 100% 1.10 939
POWER (SF): 1000 2.00 3.413 100% 1.10 7,509
EQUIPMENT (SF): 1000 2.00 3.413 100% 1.10 7,509
INFILTRATION SENSIBLE: 100 CFM 22.0°F 1.08 1.10 2,624
SUB-TOTAL = 27,337
ROOM SENSIBLE HEAT GAIN
HVAC QUICK LOAD PROGRAM
COMPANY: DATE: Mar 11, 2023
PROJECT: PROJ. NO.:

TOTAL STATIC = 2.00 in. wg ROOM SENSIBLE HEAT (BTU/HR)= 56,981


AIRFLOW @ 20.0°F TEMP. DIFF. = 2627 CFM
MOTOR SIZE = 1.4 BRAKE HORSEPOWER
MOTOR HEAT RISE = 1.2°F HEAT GAIN FROM MOTOR (BTH/HR) = 3,506
SUB-TOTAL = 60,487

RETURN AIR HEAT GAIN


AREA EQUIVALEN TEMP.
SAFETY
EXPOSURE T TEMP. CORRECTIO "U" VALUE BTU/HR
(SQ.FT.) FACTOR
DIFF. N
WALL: N 10 #N/A 10 0.10 1.10 #N/A
WALL: S 10 13 10 0.10 1.10 25
WALL: E 10 13 10 0.10 1.10 25
WALL: W 10 34 10 0.10 1.10 48
WALL: NE 10 13 10 0.10 1.10 25
WALL: NW 10 13 10 0.10 1.10 25
WALL: SE 10 15 10 0.10 1.10 28
WALL: SW 10 35 10 0.10 1.10 50
ROOF: HORIZ. 100 43 10 0.04 1.10 233
LIGHTS: (FLUOR.) 1000 2.0 W/SF 3.413 20% 1.10 1,502
MOTOR BHP: 1.4 BHP HEAT GAIN FROM MOTOR = 0
SUB-TOTAL = 2,004

OUTSIDE AIR HEAT GAIN


CFM PER TEMP. MULTIPLIER SAFETY
CFM BTU/HR
PERSON DIFFERENCE FACTOR FACTOR
O/A SENSIBLE: 375 3750 22.0°F 1.08 1.10 98,418

GRAND TOTAL SENSIBLE HEAT (BTU/HR) = 160,910

LATENT HEAT GAIN


CFM
DELTA MULTIPLIER SAFETY
OUTSIDE BTU/HR
GRAINS FACTOR FACTOR
AIR
OUTSIDE AIR LATENT: 3750 36 0.68 1.10 100,337
INFILTRATION LATENT: 100 36 0.68 1.10 2,676
PEOPLE LATENT: 10 PEOPLE @ 200 BTH PER PERSON 1.10 2,200
SUB-TOTAL = 105,213

GRAND TOTAL LATENT HEAT (BTH/HR) = 105,213

ROOM SENSIBLE HEAT RATIO = 0.96 GRAND TOTAL HEAT (BTU/HR) = 266,123
TOTAL SENSIBLE HEAT RATIO = 0.60 TONNAGE = 22.2
ENTERING ENTHALPY = 42.9 BTU/LB ENTERING AIR TEMPERATURE = 103.4°F
LEAVING ENTHALPY = 20.4 BTU/LB LEAVING AIR TEMPERATURE = 50.8°F
HVAC QUICK LOAD PROGRAM
COMPANY: DATE: Mar 11, 2023
PROJECT: PROJ. NO.:

TRANSMISSION HEAT LOSS


AREA EQUIVALENT SAFETY
EXPOSURE "U" VALUE BTU/HR
(SQ.FT.) TEMP. DIFF. FACTOR
WALL: N 100 60 0.10 1.20 720
WALL: S 100 60 0.10 1.20 720
WALL: E 100 60 0.10 1.20 720
WALL: W 100 60 0.10 1.20 720
ROOF: INCLUDED IN PLENUM HEAT
GLASS: 900 60 1.13 1.20 73,224
PARTITION: 100 60 0.20 1.20 1,440
SUB-TOTAL = 77,544

INTERNAL HEAT LOSS


TEMP.
MULTIPLIER
CFM DIFFERENC BTU/HR
FACTOR
E

INFILTRATION SENSIBLE: 100 CFM 60.0°F 1.08 6,507


SUBTOTAL = 6,507

ROOM SENSIBLE HEAT GAIN


TOTAL STATIC = 2.00 in. wg ROOM SENSIBLE HEAT (BTU/HR)= 84,051
AIRFLOW @ 20.0°F TEMP. DIFF. = 2627 CFM
MOTOR SIZE = 1.4 BRAKE HORSEPOWER
MOTOR HEAT RISE = 1.2°F HEAT GAIN FROM MOTOR (BTH/HR) = (3,506)
SUB-TOTAL = 80,545

RETURN AIR HEAT LOSS


AREA TEMP. SAFETY
EXPOSURE "U" VALUE BTU/HR
(SQ.FT.) DIFFERENCE FACTOR
WALL: N 10 SF 60 0.10 1.20 72
WALL: S 10 SF 60 0.10 1.20 72
WALL: E 10 SF 60 0.10 1.20 72
WALL: W 10 SF 60 0.10 1.20 72
ROOF: HORIZ. 100 SF 60 0.08 1.20 576
LIGHTS: (FLUOR.) 1000 SF 2.0 W/SF 3.413 20% 1,365
MOTOR BHP: 1.4 BHP HEAT GAIN FROM MOTOR = 0
SUB-TOTAL = 2,229

OUTSIDE AIR HEAT LOSS


TEMP. MULTIPLIER SAFETY
CFM BTU/HR
DIFFERENCE FACTOR FACTOR
OUTSIDE AIR: 3750 60.0°F 1.08 1.20 292,815

GRAND TOTAL LOSS (BTU/HR) = 292,815


Instructions for using the HVAC Quick Load Program

1 Information is required anywhere "red" text is shown or there is a yellow-highlighted cell.


2 Fill in your company name/your name, the project name and project number (if appropriate.)
3 The date autofills with the current day.
4 Once all the other inputs are in, you run through the months (i.e. 1 through 12) to get the
highest sensible and total load. Then, leaving the month alone, run through the times (i.e.
7, 8, 9, 19, 11, 12, 1, 2, 3, 4, 5, 6) to see which one returns the highest sensible and total
load.
5 Also, try different combinations of Indoor Air dry bulb and wet bulb to get your required
Indoor Air Relative Humidity. I have shown 72°F/60.08°F to get a resulting 50%RH.
6 In the Hours of Operation block only use "12", "16", or "24" for the input.
7 Int. Shade? denotes internal shading. If you are certain the building will have (and use)
internal shading devices, then put a "Y" in the cell. Otherwise leave the "N".
8 For the "Exposures", the only inputs you can use are "N", "S", "E", "W", "NE", "SE", "SW",
& "NW". Future updates will have more options.
9 Run through the program a few times to get a "feel" for how it works. If you find anything
that is not working like it should, let me know. Also, if you want to make suggestions to
improve the "use-ability" of this quick load program, please do so. I would like to refine
this product and update accordingly.