Professional Documents
Culture Documents
Start mode
Run mode
1117 Page 1
03. Start, Stop and running-in W220
Shutdown mode
Active when :
– a stop is requested by the operator
– a fault comes out (see chap. 23).
The sequence of the shutdown is as follows :
· K2 (stop) relay switched off and Genset Circuit Breaker
will be tripped by the Genset Control Panel (GCP).
· Gas pressure control stops and gas line supply is closed.
· Engine gas injection stopped at 100 rpm.
· Ignition stopped at 50 rpm.
· The Gas will be burnt during engine deceleration.
Stop mode
· Active when the engine is totally stopped.
· Validated when Wecs checks no Shutdown or Emergency
modes.
· K2 relay will be energized again on Wecs cabinet.
Emergency mode
Active when :
· « Emergency Stop » button is pressed on GCP or WECS
panel.
· a fault has been detected (see chap. 23).
Resulting effects :
· Stop relay and breaker trip
· Emergency stop relay trip
· Gas line supply closed (V12 / V13)
· Gas injection stopped
· Ignition powered off
· Gas pressure control stopped
· Ignition and gas injection no more possible
· Back to « Stop mode » after operator’s fault reset & ac-
knowledgment.
Page 2 1117
W220 Start, Stop and running-in 03.
03.1.2. Preheating
See appendix 1.
03.1.3. Pre-lubricating
See appendix 2.
A W220 is allowed to start if the following condition is fulfilled :
PT271and PT201 > 100 mbar more than 5 seconds.
1117 Page 3
03. Start, Stop and running-in W220
This test is done to check the gastightness of the gas shut off valve, and
check if the pressure sensors are ok. If the test results are satisfying, a
Start impulsion is sent to the Wecs.
Genset Gas line Instrumentation :
6
6
NC NO NO
6 6
PO6
Gas pipe feeder
to engine
P02 V06 V12 V13
Fig. 03-1
Page 4 1117
W220 Start, Stop and running-in 03.
Engine stopped
Pump failure
Preheating or
pump ON Water HT presure
PT 401<180 mbar
TE 402
< 45 ° C
Fig. 03-2
1117 Page 5
03. Start, Stop and running-in W220
Engine
stopped End
Prelubricating pump ON
during 3 min OR until
the engine passed in run mode Prelub pump fault (breaker down)
Prelubricating failure
Prelubricaring failure
Start allowed
Go to start procedure
fig. 03-3
Page 6 1117
W220 Start, Stop and running-in 03.
Start
request OK
End
Timer 5s
Fig. 03-4
1117 Page 7
03. Start, Stop and running-in W220
Start request OK
Injection gas
Ventilation
turns OK Start attempt failed
1 to 5 Rpm
End
Valve V13 opened
Fig. 03-5
Page 8 1117
W220 Start, Stop and running-in 03.
Stop mode
Ventilation request
Circuit breaker ON
Flow switch ON
Valve close
End ventilation
Fan circuit breaker OFF
Flow switch OFF
Valve close
Fig. 03-6
1117 Page 9
03. Start, Stop and running-in W220
Start order
Starting conditons :
- Earthing disconnector open Start pre ventilation
- Tripping alarm not active See fig-03-6
- Shutdown alarm not active
- No remote startblock
- Starting air pressure>12 or 20 bar
- Wecs ready to start :
- Plc-wecs communication Pre ventilation
- Turning gear disengaged Ventilation failure
OK
- Ht water>40 °C
- Post ventilation exhaust gas line
Start prelubriating
See fig-03-3
Start failure
Starter ON (CV321)
timer starter too long
End
Starter OFF
Engine speed = 50 Rpm OK
Engine start
Fig. 03-7
Page 10 1117
W220 Start, Stop and running-in 03.
Engine started
Loading 1MW/mn
AVR excitation rated
speed -200 Rpm
Normal operation
Shutdown
Rated speed
Shutdown
Breaker close
Fig. 03-8
1117 Page 11
03. Start, Stop and running-in W220
Stop order
Unloading 1MW/mn
Power = 0
Unloading failure
Timer = 240S
Shutdown
Breaker open
Cooling run
Idle speed 800 Rpm 1 to 5 min
Stop engine
Fig. 03-9
If immediate stop = go to the step "open breaker " and " engine stop"
without completing the unloading and cooling run procedure.
If electrical stop = go to the step "open breaker" and follow the normal
procedure.
If delayed stop = go to the step "breaker open" and follow the normal
procedure.
Page 12 1117
W220 Start, Stop and running-in 03.
03.2. Starting
Before starting the engine, check that :
1 The lubricating oil level is correct.
2 The gas circuit is in working order :
· Pressure relief unit in service (correct pressure)
· Gas circuit main valve open.
3 The low-temperature and high-temperature coolant circuits
are in working order (correct pressure, preheating and pre-circu-
lation of water sufficient to warm up the engine).
4 The starting air line pressure is open.
5 The starting air system contains no condensate.
6 The drain hole of the charge air cooler is open, no leakage
7 Check that the alarm and stop devices are in working order.
Caution : The shaft driven water pump must be degassed (manual bleed on
pump body) or the air pocket in the pump will prevent the coolant
from circulating.
Note 1 : All covers and protective panels must be fitted before starting the en-
gine. These covers may be occasionally removed for measurement
and checking purposes, but must be re-fitted immediately afterwards.
Note 2 : Before starting the engine, make sure that possible maintenance and
service operations have been finished and that all persons have left
the engine room and other risk areas.
Note 3 : Avoid running the engine on low loads. Misfiring may cause unburned
gas explosion in the exhaust system
Note 4 : It is possible to restart the engine is possible once the ventilation se-
quence of the exhaust system is finished. The exhaust system is
equipped with automatic ventilation and will stay open for a while af-
ter the stop. During this time, the start will be blocked.
Note 5: Despite the safety system, there is always a risk of gas explosion. To
avoid any possible accidents, no one must remain in the engine room
and boiler/silencer room during engine start.
1117 Page 13
03. Start, Stop and running-in W220
Warning : Never attempt to re-start the engine before the flywheel has come to a
complete stop.
Page 14 1117
W220 Start, Stop and running-in 03.
03.3. Stopping
03.3.1. General information
Caution : When overhauling the engine, make sure that the automatic starting
system and the pre-lubricating oil pump have been properly discon-
nected.
1117 Page 15
03. Start, Stop and running-in W220
Page 16 1117
W220 Start, Stop and running-in 03.
Caution : In some situations, you can have condensation in charge air cooler. In
consequence, water leakage at charge air cooler telltale hole can ap-
pear. That doesn't mean that the charge air cooler is damaged.
Example : If the ambient air temperature is 35°C and the relative hu-
midity is 80 % the water content in the air can be read from the diagram
(0.029 kg water/kg dry air). If the air manifold pressure (receiver pres-
sure) under these conditions is 2.5 bar, i.e. absolute air pressure in the
air manifold is abt. 3.5 bar (ambient pressure + air manifold pressure),
the dew point will be 55°C ( from diag.). If the air temperature in the air
manifold is only 45°C, the air can only contain 0.018 kg/kg (from diag.).
The difference, 0.011 kg/kg (0.029-0.018) will appear as condensed
water.
Fig. 03-10
1117 Page 17
03. Start, Stop and running-in W220
03.4.3. General
· There is no automatic supervision or control arrange-
ment that can replace an experienced engineer’s observa-
tions. LOOK at and LISTEN to the engine !
· Strong gas blow-by past the pistons is one of the most dan-
gerous things that can occur in an engine. If gas blow-by is
suspected, check the crankcase pressure. If the pressure
exceeds 30 mm H2O, check the crankcase venting system,
if in order, do a boroscope liner inspection.
Page 18 1117
W220 Start, Stop and running-in 03.
1117 Page 19
03. Start, Stop and running-in W220
Page 20 1117
W220 Start, Stop and running-in 03.
Note : Turn the crankshaft to feed oil to all connecting rods and valve rock-
ers.
Caution : Rags or tools left in the engine block, incorrectly tightened screws or
nuts, and worn self-locking nuts may cause total breakdown.
1117 Page 21
03. Start, Stop and running-in W220
Page 22 1117
W220 Start, Stop and running-in 03.
03.9. Running-in
The running programe below must be followed :
· After piston overhaul.
· After piston rings, pistons, liners, conrod bearing or main
bearing replacing.
This program is given for information only.
The engine may be run-in with the normal lubricating oil specified for
the engine.
Note : If your engine nominal speed is 1200 rpm, never exceed this value dur-
ing engine running-in.
1117 Page 23
03. Start, Stop and running-in W220
Fig. 03-11
Page 24 1117
W220 Start, Stop and running-in 03.
* After the first step at 800 rpm during 5 minutes, you must stop the en-
gine. Open visiting doors and verify conrods, bearings, ….
Note the oil and the HT water temperatures. Check the conrods tem-
peratures. The conrods temperatures should be 50°C ± 5 after 5 min-
utes of engine running. Normally, the maximal temperature gap
between the conrods is 5°C. If there is a problem, don’t continue the
running-in without founding the reason (call your Wärtsilä France
Representative).
* You must stop the engine after the first step at 1200 rpm. Open visit-
ing doors and verify conrods, bearings, ….
Note the oil and the HT water temperatures. Verify the conrods tem-
peratures, typically, the conrods temperatures should be at 80°C ± 5.
Normally, the maximal temperatures gap is 5°C between the conrods.
If there is a problem, do not continue the running-in without finding
the reason (call your Wärtsilä France Representative).
* Restart the engine and go to Rated Speed (1200 rpm or 1500 rpm)
step by step (see picture above).
* When the engine is at Rated Speed, the load running-in can start.
Warning : Do not stay more than 1 minute at 1500 rpm without load. When you
increase or decrease the load, proceed in lots of steps.
* After the step at full load, the running-in sequence is finished. Stop
the engine and do the standard controls : rocker arm clearances, oil fil-
ters changing, fluids level checking. After that, you can use normally
the engine.
Fig. 03-12]
1117 Page 25
03. Start, Stop and running-in W220
Page 26 1117
W220 Start, Stop and running-in 03.
325 1500 0
326 1500 0
1117 Page 27