You are on page 1of 7

EASEMENTS ▪ No building shall be constructed unless it adjoins

EASEMENT IS PUBLIC LAND or has direct access to a public space, yard, or


▪ Situated outside of private property limits road on at least one side.
▪ Should be equally enjoyed by all members of the ▪ Interior or rear lots shall have an access road with
community a minimum width of 3.00m. Provide a 4.00m wide
▪ The only uses allowed are those that support its public chaflan at the intersection with the main RROW.
recreational character

MINIMUM EASEMENTS

THREE RROW LEVELS


▪ RROW above grade
▪ RROW at grade
▪ RROW below grade

RROW

VIEW CORRIDORS + SIGHTLINES


▪ The carriageway shall be free of structures,
particularly commercial signs that will impede the view
corridor and sightlines within the RROW
▪ To dignify important public/historical buildings, all
forms of commercial signs intruding into the RROW
leading to or away said structures shall be disallowed

RROW ABOVE GRADE


▪ From the finished surface of the roadway all the
way up to the air
▪ If utilized for whatever purpose, the use or air
rights must be compensated for (leased from the
government)
▪ Minimum clear height: 4.27m from crown of
carriageway
ACCESS TO PROPERTY RROW AT GRADE
▪ From natural grade line to the finished surface of
the carriageway or sidewalk
▪ Generally utilized for the movement of the general
public (motorists and pedestrians)
▪ If utilized for whatever purpose, proponent must
lease/pay the government

RROW BELOW GRADE


▪ From finished surface of roadway all the way
down into the ground
▪ If utilized for whatever purpose, proponent must
lease/pay the government

SIDEWALKS DRIVEWAYS ACROSS SIDEWALKS


▪ The local planning authority shall determine which ▪ If curb height = 200mm or lower, the driveway and
streets shall have an open sidewalk or an arcaded the sidewalk shall be on the same plane. Provide
sidewalk, or a combination of both entry ramp of slope 1/3 to ¼ connecting the
▪ For a RROW width of 9.00m or more, the carriageway to the sidewalk/curb.
minimum sidewalk width shall be 1.20m on each
side of the RROW. For RROW less than 9.00m,
refer to Table VIII.G.3

DRIVEWAYS ACROSS SIDEWALKS


▪ If curb height = greater than 200mm, a curb
cutout for the driveway may be allowed and the
driveway may be constructed along the entire
width of the sidewalk. The sidewalk and the
driveway shall be joined by a ramp with a slope of
not more than 1/8.

GRADE OF SIDEWALKS
▪ As much as possible, sidewalks shall be level and of
uniform grade throughout the length of the street
▪ When the street slope does not exceed 1/12, the
sidewalk shall follow the street slope
▪ When the street slope is 1/10, the sidewalk shall be
maintained level for every 20-40 meters of run, each
level joined by a ramp of a slope not exceeding 1/6.
PLANTING STRIPS
▪ Sidewalks 2.00m or more in width shall include on
RULE 10
its outer side a planting strip of not less than Building Projections Over Public
800mm wide up to a maximum of 1/3 of the
sidewalk width Streets
▪ The planting strip is meant to separate the curb
from the sidewalk, and must always be placed
ARE PROJECTIONS BEYOND THE
near the curbline.
PROPERTY LINE ALLOWED?
▪ No. Unless otherwise allowed by the Code.

PROJECTIONS INTO THE RROW


▪ National roads or public highways: footings
located at least 2.40m below grade may project
300mm (maximum) beyond the property line
▪ Public sidewalk: Foundations may encroach
500mm into the sidewalk if top of foundation is at
least 600mm below grade

PROJECTIONS INTO THE RROW


▪ In all cases, these projections shall not obstruct
any utilities/services, unless the owner is willing to
pay for the rerouting of said utilities/services

RULE 9 SANITATION
BASIC SANITATION PROVISIONS BALCONIES
▪ All buildings shall be provided with the ff: ▪ Clearance between sidewalk grade and lowest
▪ Adequate and potable water supply portion of balcony = 3.00m minimum
▪ Adequate plumbing installation
▪ Suitable wastewater treatment/disposal system ARCADES
▪ Storm water drainage ▪ Arcades may be constructed on sidewalks of
streets whenever allowed or required by existing
WATER SOURCE building and zoning regulations.
▪ Potable water shall be sourced from the existing ▪ Arcades shall be at least 3.00m above the
municipal waterworks system whenever possible sidewalk grade.

WATER QUALITY
▪ Shall conform to the criteria in the National
Standards for Drinking Water

WASTE DISPOSAL SYSTEM


▪ Sanitary sewage from buildings shall be
discharged directly into the nearest street sanitary
sewer main
▪ If no sanitary sewerage system is available, septic
tanks may be used

STORM DRAINAGE DOORS + WINDOWS


▪ Rainwater drainage shall not discharge into the ▪ Unless at least 2.40m above the pavement, no
sanitary system door or window shall project beyond the property
line when fully opened or upon opening.
NATIONAL PLUMBING CODE
▪ All plumbing installations (water supply and CHAFLANS
drainage) shall conform to the National Plumbing ▪ Every corner building or fence on a public street
Code less than 3.60m wide shall be truncated at the
corner to form a chaflan.
▪ The chaflan shall be at least 4.00m wide
RULE 11
Protection of Pedestrians

PROTECTION OF PEDESTRIANS
▪ No person shall use or occupy a street or sidewalk
RULE 12
for the performance of work except in accordance General Design Requirements
with this rule
▪ No work shall be performed adjacent to a public
way unless pedestrians are protected as specified EXCAVATIONS
in this rule ▪ Excavations must not endanger life or property
▪ Any person undertaking an excavation shall
STORAGE IN PUBLIC PROPERTY ensure that the soil of the adjoining property will
▪ Shall not obstruct utility provisions (fire hydrants, not cave in or settle.
fire alarm box, manholes) ▪ Cut slopes shall be no steeper than 2:1
▪ Shall not interfere with drainage (horizontal:vertical).
▪ Shall not interfere with vehicular and pedestrian
Traffic OCCUPANT LOAD
▪ The maximum number of persons that may be
MORTAR MIXING allowed to occupy a certain room, floor, or area
▪ The mixing of mortar or concrete shall not be ▪ Shall be determined by dividing the floor area
allowed on public streets. assigned to that use by the unit area allowed per
occupant as shown on Table XII.1.
TEMPORARY WALKWAYS ▪ Floor area/unit area per occupant
▪ When the Building Official authorizes a sidewalk
to be closed, a temporary walkway at least 1.20m
wide shall be provided
▪ If the street has no sidewalk, width may be
reduced to 600mm.
▪ If RROW is 5.00m wide or less, no temporary
walkways are allowed

FENCES + CANOPIES
▪ Fences shall entirely enclose a construction site
▪ Minimum height: 2.40 meters above curb

FENCES + CANOPIES
▪ When the horizontal distance between the OFB
and the inner edge or the sidewalk is more than ½
the building height, only a 2.40m high fence is
required.
▪ When the horizontal distance between the OFB
and the inner edge or the sidewalk is equal or less
than ½ the building height, a canopy will be also
be required in addition to the fence.

FENCES + CANOPIES
▪ For canopies: provide a clear unobstructed height
of 2.40m above the walkway
NUMBER OF EXITS open over the top step provided that the landing is
▪ Every building shall have at least one exit not more than 200mm from the floor level and the
▪ Upper floors with occupant load of more than 10 door does not swing over the top step.
shall have at least two exits
▪ A mezzanine floor bigger than 185sqm or having CORRIDORS
more than 18.00m in any dimension shall have at ▪ Minimum width: 1.10m
least two stairways to an adjacent floor ▪ This width shall be unobstructed, except that trim
handrails and doors when fully opened shall not
NUMBER OF EXITS reduce the required with by more than 200mm.
▪ Every floor with occupant load of 500-999 shall ▪ Doors in any position shall not reduce the width by
have at least 3 exits. more than ½.
▪ Every floor with occupant load of 1000 or more
shall have at least 4 exits. DEAD ENDS
▪ Maximum length: 6.00m
WIDTH OF EXITS
▪ Total width of exits = Occupant load/165 STAIRWAY WIDTHS
▪ Note: This is the total width in meters ▪ 1.10m for occupant load more than 50
▪ 0.90m for occupant load of 50 or less
ARRANGEMENT OF EXITS ▪ 0.75m for occupant load of less than 10 (private)
▪ If two exits are required, the two exits must be ▪ Handrails shall not reduce the width of stairways
apart by at least 1/5 of the perimeter of the area by more than 100mm
served.
▪ If three or more are required, they shall be RISER AND TREAD
arranged a reasonable distance apart ▪ Maximum riser: 200mm
▪ Minimum tread: 250mm
DISTANCE TO EXITS ▪ Note: Always keep in mind that the NBC requirement
▪ If without a sprinkler system, 45.00m maximum is a maximum for risers, and a minimum for treads
▪ If with a sprinkler system, 60.00m maximum
▪ Measured from any point in a building, measured STAIRWAY HEADROOM
along the line of travel ▪ Not less than 2.00m measured from the nosing

EXITS DOORS LANDINGS


▪ When serving an occupant load of 50 or more, ▪ Length = stairway width
must swing in the direction of exit travel ▪ If the stairway has a straight run, landing length
▪ Double acting doors shall not be used as exits does not need to exceed 1.20m
when serving a tributary load of more than 100. ▪ Landing width shall not be reduced by more than
Must be provided with a view panel of not less 100mm by any door when fully opened
than 1300 sq. cm. ▪ Max. vertical distance between landings: 3.60m

TYPE OF LOCKS HANDRAILS


▪ Exit doors shall be openable from the inside ▪ Stairways shall have handrails on each side
without the use of a key or any special knowledge ▪ If a stairway is more than 3.00m in width, at least
or effort one intermediate handrail shall be provided
▪ Height of handrails: 800-900mm above the nosing
SIZE OF DOORS of treads
▪ Minimum width of doorway: 0.90mm
▪ Minimum height of doorway: 2.00m HANDRAILS
▪ Shall be capable of opening at least 90 degrees ▪ Exceptions:
▪ In Group A or B occupancies, stairways 1.10m or less
BASEMENT STAIRWAYS in width serving one individual dwelling may have one
▪ If a basement stairway and a stairway to an upper handrail only
storey terminate at the same exit enclosure, a ▪ Stairways having less than four risers need not have
barrier shall be provided to prevent persons from Handrails
continuing into the basements
▪ Also provide directional exit signs WINDING STAIRWAYS
▪ Maximum door leaf width: 1.20m ▪ Allowed as exits as long as the required tread
(250mm) is provided at a point 300mm away
PROHIBITED DOORS from the narrow end
▪ The following shall not be used as exit doors: ▪ However, the tread must not be narrower than
▪ Revolving doors 150mm at any point
▪ Sliding doors
▪ Overhead doors CIRCULAR STAIRWAYS
▪ May be used as exits provided that the minimum
FLOOR LEVEL CHANGE AT DOORS width of run is not less than 250mm
▪ There shall be a floor or a landing on each side of an
exit door AISLES
▪ The floor/landing shall not be more than 50mm lower ▪ Aisles leading to an exit shall be provided for all
than the door threshold portions with installed seats, tables, etc.
▪ Exception: For Group A or B occupancies, a door may ▪ Shall be at least 0.80m wide if serving only one
side, or 1.00m if serving both sides ▪ All mechanical systems and installations shall
▪ This minimum width shall be measured at the conform to the provisions of the Philippine
point farthest from the exit, and shall be increased Mechanical Code pursuant to RA 8495 (Mech.
by 30mm for every meter in length towards the Engg. Law)
exit
CLEARANCE OF SERVICE DROPS
AISLE TRAVEL DISTANCE ▪ 2.50m from highest point of roofs
▪ The line of travel to an exit door by an aisle shall ▪ 3.00m from the ground
not be more than 45.00m ▪ 1.00m (horizontal) from windows/porches
▪ Maximum 7 seats between wall and aisle ▪ 5.50m from the crown of the street or sidewalk
▪ Maximum 14 seats between two aisles ▪ No service drop conductors or any other wiring
▪ Maximum slope: 1 in 8 shall pass over swimming pools

AISLE TRAVEL DISTANCE ELEVATORS


▪ The number of seats between aisles may be ▪ Hoistway pit: minimum 600mm from underside of
increased to 30 if: car to bottom of pit
▪ Exit doors are provided along each aisle at the rate of ▪ Maximum four elevators in a single hoistway
1 ▪ Residential buildings 5 storeys or higher shall
pair of exit doors for every 5 rows of seats have at least one passenger elevator on 24-hour
▪ The back-to-back distance between seats is 1.00m constant operation
minimum
▪ Minimum clear width of exit doors is 1.70m ESCALATORS
▪ Maximum inclination: 30° from horizontal
FIRE EXTINGUISHING SYSTEMS ▪ Width between ballustrades: 560mm-1200mm.
▪ Automatic fire extinguishing systems are required Shall not exceed the width of the step by more
for the following: than 330mm
▪ Habitable storeys with an area of 200 sqm or more ▪ Speed: 38 meters per minute maximum (common
with an occupant load of more than 20 rule is 90-120 fpm/27.5-36.5mpm)
▪ Dressing rooms, rehearsal rooms, workshops or
factories with occupant load of more than 10 AIR CONDITIONING
▪ Assembly halls under Group H and I with occupant ▪ Comfortable cooling standards:
load of more than 500 ▪ Temperature: 20°-24° Celsius
▪ Humidity: 50% - 60%
DRY STANDPIPES ▪ Air movement: 4.60-7.60 meters per minute
▪ All buildings 4 or more storeys in height shall be
equipped with one or more dry standpipes WATER PUMPING
▪ Standpipes shall be located within enclosed ▪ Installation of pumping equipment directly from
stairway landings the public water supply system is prohibited
▪ Siamese connections shall be located on the
street-front of a building 300mm-1200mm above
grade
RULE 14
Photo Films + X-ray Films
WET STANDPIPES
▪ The following shall have wet standpipes: FILM STORAGE ROOMS
▪ Group H or I occupancy of any height ▪ Provide automatic fire extinguishing systems for
▪ Group C occupancy 2 or more storeys in height the following:
▪ Groups B, D, E F and G 3 or more storeys in height ▪ When unexposed films in shipping containers exceed
▪ Group G and E occupancy over 1800 sqm in area 14.00 cubic meters
▪ Exemption: ▪ When shelving used for storing film exceeds 1.40
▪ Group H buildings without stage whose seating cubic meters in capacity
capacity is less than 500
FILM STORAGE ROOMS
LOCATIONS OF WET STANDPIPES ▪ No films shall be stored within 600mm of steam
▪ All portions of the building are within 6.00m of a pipes, chimneys, or other sources of heat
nozzle attached to a hose 23.00m in length
(standpipes 58.00m apart)
▪ For assembly occupancies: RULE 15
▪ 1 outlet on each side of the stage
▪ 1 at the rear of the auditorium
Prefabricated Construction
▪ 1 at the rear of the balcony
PREFABRICATED ASSEMBLY
▪ A structural unit, the integral parts of which have
RULE 13 Electrical + Mechanical been built-up or assembled prior to incorporation
in the building
REFERRAL CODES ▪ To determine structural adequacy, they shall pass
▪ All electrical systems and installations shall special tests conducted by accredited material
conform to the provisions of the Philippine testing laboratories
Electrical Code pursuant to RA 7920 (Electrical
Engg. Law)
RULE 16 Plastics
accessible to him where a detailed description of
APPROVED PLASTICS the program including a description of the
▪ Those which have a flame-spread rating of 225 or algorithms are found
less ▪ The software name, version number and the
▪ Those with a smoke density not greater than that developer and its address shall be provided as
obtained from the burning of untreated wood part of documentation
▪ Those whose products of combustion are no
more toxic than those of untreated wood
RULE 20
PLASTIC DOORS Signs
▪ Plastic doors are allowed except for entrance
doors and exit doors, which should be of materials SIGNS
other than plastics ▪ No sign shall be erected in such a manner as to
confuse or obstruct the view or interpretation of
RULE 17 any official traffic sign/device
▪ Signs in any foreign language shall have a
Sheet Metal Spray booths translation in English or the local dialect

SPRAY PAINT BOOTHS ROOF SIGNS


▪ Paint spray booths shall be constructed of not ▪ No signs shall be installed on rooftops of
less than No. 18 US Gauge in thickness buildings of wooden structures or of buildings
▪ The area of a spray paint booth shall not exceed with wooden roof framing
150sqm ▪ Provide grounding of metallic parts of roof signs
▪ The floor of the booth, if combustible, shall be exposed to lightning
covered with non-combustible material
▪ Shall permit the free passage of exhaust air GROUND SIGNS
▪ Shall be located within the property line and under
no circumstances shall they occupy the RROW
RULE 18
Glass + Glazing PROJECTING SIGNS
▪ On non-arcaded RROW:
▪ Signs shall not project more than 1.20m
GENERAL REQUIREMENTS ▪ On arcaded RROW:
▪ Applies to all exterior glass/glazing except Groups ▪ Signs shall not project more than 0.60m
A, B, and J not taller than three storeys ▪ Buildings abutting RROW without sidewalks:
▪ Each glass panel shall bear the manufacturer’s ▪ Signs shall not project more than 0.30m
label designating the type and thickness of glass
PROJECTING SIGNS
GENERAL REQUIREMENTS ▪ Minimum vertical clearance
▪ Glass panels with special performance ▪ Non-arcaded RROW: 3.00m from road surface to
characteristics shall bear the manufacturer’s label lowest part of signs
indicating said characteristics ▪ Arcaded RROW: 5.00m from road surface to lowest
▪ Measures shall be taken to keep persons from part of signs
walking into fixed glass panels where the floor on
both sides of the glass are the same level
(guardrails, etching, flower bins)

GENERAL REQUIREMENTS
▪ Glass in large areas along shopping malls,
commercial buildings, institutional buildings, etc.

RULE 19
Use of Computers
GENERAL REQUIREMENTS
▪ The use of computers for all or any part of
building design is permitted provided that all
programs to be used are documented

PROGRAM DOCUMENTATION
▪ File with the OBO a reference to a publication

You might also like