Professional Documents
Culture Documents
MINIMUM EASEMENTS
RROW
GRADE OF SIDEWALKS
▪ As much as possible, sidewalks shall be level and of
uniform grade throughout the length of the street
▪ When the street slope does not exceed 1/12, the
sidewalk shall follow the street slope
▪ When the street slope is 1/10, the sidewalk shall be
maintained level for every 20-40 meters of run, each
level joined by a ramp of a slope not exceeding 1/6.
PLANTING STRIPS
▪ Sidewalks 2.00m or more in width shall include on
RULE 10
its outer side a planting strip of not less than Building Projections Over Public
800mm wide up to a maximum of 1/3 of the
sidewalk width Streets
▪ The planting strip is meant to separate the curb
from the sidewalk, and must always be placed
ARE PROJECTIONS BEYOND THE
near the curbline.
PROPERTY LINE ALLOWED?
▪ No. Unless otherwise allowed by the Code.
RULE 9 SANITATION
BASIC SANITATION PROVISIONS BALCONIES
▪ All buildings shall be provided with the ff: ▪ Clearance between sidewalk grade and lowest
▪ Adequate and potable water supply portion of balcony = 3.00m minimum
▪ Adequate plumbing installation
▪ Suitable wastewater treatment/disposal system ARCADES
▪ Storm water drainage ▪ Arcades may be constructed on sidewalks of
streets whenever allowed or required by existing
WATER SOURCE building and zoning regulations.
▪ Potable water shall be sourced from the existing ▪ Arcades shall be at least 3.00m above the
municipal waterworks system whenever possible sidewalk grade.
WATER QUALITY
▪ Shall conform to the criteria in the National
Standards for Drinking Water
PROTECTION OF PEDESTRIANS
▪ No person shall use or occupy a street or sidewalk
RULE 12
for the performance of work except in accordance General Design Requirements
with this rule
▪ No work shall be performed adjacent to a public
way unless pedestrians are protected as specified EXCAVATIONS
in this rule ▪ Excavations must not endanger life or property
▪ Any person undertaking an excavation shall
STORAGE IN PUBLIC PROPERTY ensure that the soil of the adjoining property will
▪ Shall not obstruct utility provisions (fire hydrants, not cave in or settle.
fire alarm box, manholes) ▪ Cut slopes shall be no steeper than 2:1
▪ Shall not interfere with drainage (horizontal:vertical).
▪ Shall not interfere with vehicular and pedestrian
Traffic OCCUPANT LOAD
▪ The maximum number of persons that may be
MORTAR MIXING allowed to occupy a certain room, floor, or area
▪ The mixing of mortar or concrete shall not be ▪ Shall be determined by dividing the floor area
allowed on public streets. assigned to that use by the unit area allowed per
occupant as shown on Table XII.1.
TEMPORARY WALKWAYS ▪ Floor area/unit area per occupant
▪ When the Building Official authorizes a sidewalk
to be closed, a temporary walkway at least 1.20m
wide shall be provided
▪ If the street has no sidewalk, width may be
reduced to 600mm.
▪ If RROW is 5.00m wide or less, no temporary
walkways are allowed
FENCES + CANOPIES
▪ Fences shall entirely enclose a construction site
▪ Minimum height: 2.40 meters above curb
FENCES + CANOPIES
▪ When the horizontal distance between the OFB
and the inner edge or the sidewalk is more than ½
the building height, only a 2.40m high fence is
required.
▪ When the horizontal distance between the OFB
and the inner edge or the sidewalk is equal or less
than ½ the building height, a canopy will be also
be required in addition to the fence.
FENCES + CANOPIES
▪ For canopies: provide a clear unobstructed height
of 2.40m above the walkway
NUMBER OF EXITS open over the top step provided that the landing is
▪ Every building shall have at least one exit not more than 200mm from the floor level and the
▪ Upper floors with occupant load of more than 10 door does not swing over the top step.
shall have at least two exits
▪ A mezzanine floor bigger than 185sqm or having CORRIDORS
more than 18.00m in any dimension shall have at ▪ Minimum width: 1.10m
least two stairways to an adjacent floor ▪ This width shall be unobstructed, except that trim
handrails and doors when fully opened shall not
NUMBER OF EXITS reduce the required with by more than 200mm.
▪ Every floor with occupant load of 500-999 shall ▪ Doors in any position shall not reduce the width by
have at least 3 exits. more than ½.
▪ Every floor with occupant load of 1000 or more
shall have at least 4 exits. DEAD ENDS
▪ Maximum length: 6.00m
WIDTH OF EXITS
▪ Total width of exits = Occupant load/165 STAIRWAY WIDTHS
▪ Note: This is the total width in meters ▪ 1.10m for occupant load more than 50
▪ 0.90m for occupant load of 50 or less
ARRANGEMENT OF EXITS ▪ 0.75m for occupant load of less than 10 (private)
▪ If two exits are required, the two exits must be ▪ Handrails shall not reduce the width of stairways
apart by at least 1/5 of the perimeter of the area by more than 100mm
served.
▪ If three or more are required, they shall be RISER AND TREAD
arranged a reasonable distance apart ▪ Maximum riser: 200mm
▪ Minimum tread: 250mm
DISTANCE TO EXITS ▪ Note: Always keep in mind that the NBC requirement
▪ If without a sprinkler system, 45.00m maximum is a maximum for risers, and a minimum for treads
▪ If with a sprinkler system, 60.00m maximum
▪ Measured from any point in a building, measured STAIRWAY HEADROOM
along the line of travel ▪ Not less than 2.00m measured from the nosing
GENERAL REQUIREMENTS
▪ Glass in large areas along shopping malls,
commercial buildings, institutional buildings, etc.
RULE 19
Use of Computers
GENERAL REQUIREMENTS
▪ The use of computers for all or any part of
building design is permitted provided that all
programs to be used are documented
PROGRAM DOCUMENTATION
▪ File with the OBO a reference to a publication