Professional Documents
Culture Documents
1) Controlled variable, T
Manipulated variable, FB
Disturbance variable, Ti (it is ok if F is counted as DV also)
Control scheme: feedback
2)
If T increases from steady state, we must increase coolant flowrate, since it is
air-to-close valve, we must decrease air pressure, need to decrease
controller output.
In summary, as controlled variable increase, controller output decrease, so it
should be a reverse acting controller.
There is another way to answer this question based on a principle given in the
textbook (section 8.3.2): ”for all components on the loop, the product of their
gain should be positive”, For this example, you will see from part (3) that Gv
has negative gain, Gp has negative gain, Gm has positive gain, so Gc must
have positive gain such that GcGvGpGm has positive gain, hence it is a
reverse acting controller.
3)
1 1
Offset = 0 = (notice that disturbance changes, set point is
1 0.5K c 0.5Kc 1
unchanged)
Q2
Y (s) GcGvGp
Closed loop transfer function
Ysp (s) 1 GcGvGpGm
4(1 5s)
Process transfer function G p ( s)
(25s 1)(4s 1)(2s 1)
Controller transfer function Gc ( s ) K c
and Gv ( s) Gm (s) 1
4(1 5s)
Kc
Y ( s) (25s 1)(4s 1)(2s 1) 4Kc (1 5s)
Ysp (s) 1 K 4(1 5s) (25s 1)(4s 1)(2s 1) 4Kc (1 5s)
(25s 1)(4s 1)(2s 1)
c
Characteristic equation:
(25s 1)(4 s 1)(2 s 1) 4 K c (1 5s ) 0
200 s 3 158s 2 (31 20k ) s 4 K c 1 0
Routh test based stability criterion:
Necessary condition:
31 20k 0
0.25 k 1.55 (1)
4k 1 0
Rough array:
200 31-20 Kc
158 4 Kc +1
b1 b2
c1
158(31 20 K c ) 200(4 K c 1)
b1= b2=0
158
b1 (4 Kc 1) 0
c1=
b1
First column must be positive
let b1>0, c1>0, we get
0.25 K c 1.1864 (2)