Professional Documents
Culture Documents
Calculated
Load capacity Instalation Utilization Required Diversity Calculatedcur Coefficient
Power load Quantity power(Ptt) Cos phi Phase Itt*Kcb Switchgear
(Pt) Power (Pd) [W] factor (Ku) Power(Pyc) [kW] factor (Ks) rent (Itt) [A] Kcb
[kW]
I Cabinets DB -QL1 102.76 0.63 64.74 0.85 3P 115.86 1.25 144.82 MCCB-4P 150A
1. Cabinets
+ Cabinets DB 1-1 11.20 [KW/Lộ] 1.0 [Lộ] 11.2 1.0 11.20 1 11.20 0.85 1P 59.87 1.25 74.84 MCB-2P 80A
+ Cabinets DB 1-2 11.20 [KW/Lộ] 1 [Lộ] 11.2 1.0 11.20 1 11.20 0.85 1P 59.87 1.25 74.84 MCB-2P 80A
+ Cabinets DB 1-3 11.20 [KW/Lộ] 1 [Lộ] 11.2 1.0 11.20 1 11.20 0.85 1P 59.87 1.25 74.84 MCB-2P 80A
+ Cabinets DB 1-4 11.20 [KW/Lộ] 1 [Lộ] 11.2 1.0 11.20 1 11.20 0.85 1P 59.87 1.25 74.84 MCB-2P 80A
+ Cabinets DB 1-5 7.12 [KW/Lộ] 1 [Lộ] 7.1 1.0 7.12 1 7.12 0.85 1P 38.09 1.25 47.61 MCB-2P 50A
+ Cabinets DB 1-6 7.12 [KW/Lộ] 1 [Lộ] 7.1 1.0 7.12 1 7.12 0.85 1P 38.09 1.25 47.61 MCB-2P 50A
+ Cabinets DB 1-7 7.12 [KW/Lộ] 1 [Lộ] 7.1 1.0 7.12 1 7.12 0.85 1P 38.09 1.25 47.61 MCB-2P 50A
+ Cabinets DB 1-8 7.12 [KW/Lộ] 1 [Lộ] 7.1 1.0 7.12 1 7.12 0.85 1P 38.09 1.25 47.61 MCB-2P 50A
+ Cabinets DB 2-5 6.80 [KW/Lộ] 1 [Lộ] 6.8 1.0 6.80 1 6.80 0.85 1P 36.35 1.25 45.44 MCB-2P 50A
+ Cabinets DB 2-6 6.80 [KW/Lộ] 1 [Lộ] 6.8 1.0 6.80 1 6.80 0.85 1P 36.35 1.25 45.44 MCB-2P 50A
+ Cabinets DB 2-7 6.80 [KW/Lộ] 1 [Lộ] 6.8 1.0 6.80 1 6.80 0.85 1P 36.35 1.25 45.44 MCB-2P 50A
+ Cabinets DB 2-8 6.80 [KW/Lộ] 1 [Lộ] 6.8 1.0 6.80 1 6.80 0.85 1P 36.35 1.25 45.44 MCB-2P 50A
2. Lighting
+ Incident lighting 0.30 [KW/Lộ] 1.0 [Lộ] 0.3 1.0 0.30 1 0.30 0.85 1P 1.60 1.25 2.01 MCB-1P 16A
3. Spare
+ Spare 1 [KW/Lộ] 1 [Lộ] 1.0 1.0 1.00 1 1.00 0.85 1P 5.35 1.25 6.68 MCB-1P 16A
+ Spare 1 [KW/Lộ] 1 [Lộ] 1.0 1.0 1.00 1 1.00 0.85 1P 5.35 1.25 6.68 MCB-1P 16A