You are on page 1of 16

Corporate name Beneficiary

Inprolec Colbun

Ampliacion SE Candelaria

Calculation notes
Ampliacion SE Candelaria
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364
Power balance 1
Synthetic calculation notes: T2 2
List of selectivity panel T2 10
Log setting of circuit breakers T2 11
Cable Nomenclature T2 12
Panel T2 equipment list 13
Bill of materials 14

List of folios
Ampliacion SE Candelaria
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364
T2 :
Barra 1 : Main panel busbar
Installed power : 10,26 kW (according the downstream result)
: I Allowed : 225 A
CIRCUIT Ib Cos Phi Start type Load
Circuit1 (DC-9, Barra CC - Caseta 1) 109,8 A 2P+PE 126,7 A
Barra CC - Caseta 1 : Distribution
Installed power : 11,85 kW (according the downstream result)
: I Allowed : 125 A
CIRCUIT Ib Cos Phi Start type Load
Div1.1 (CB01, CC-01) 13,4 A 2P+PE 2,4 kW x0,5
Div1.2 (CB02, CC-02) 2,7 A 2P+PE 0,936 kW x0,3
Div1.3 (CB03, CC-03) 12,5 A 2P+PE 4,5 kW x0,3
Div1.4 (CB04, CC-04) 12,5 A 2P+PE 4,5 kW x0,3
Div1.5 (CB05, CC-05) 1,7 A 2P+PE 0,18 kW
Div1.6 (CB06, CC-06) 1,7 A 2P+PE 0,18 kW
Div1.7 (CB07, CC-07) 0,8 A 2P+PE 0,08 kW
Div1.8 (CB08, CC-08) 0,8 A 2P+PE 0,08 kW
Div1.9 (CB09, CC-09) 2,3 A 2P+PE 0,24 kW x0,6
Div1.10 (CB10, CC-10) 8,7 A 2P+PE 0,936 kW x0,3
Div1.11 (CB11, CC-11) 12,5 A 2P+PE 4,5 kW x0,3
Div1.12 (CB12, CC-12) 12,5 A 2P+PE 4,5 kW x0,3
Div1.13 (CB13, CC-13) 13,4 A 2P+PE 2,4 kW x0,6
Div1.14 (CB14, CC-14) 2,7 A 2P+PE 0,936 kW x0,3
Div1.15 (CB15, CC-15) 12,5 A 2P+PE 4,5 kW x0,3
Div1.16 (CB16, CC-16) 12,5 A 2P+PE 4,5 kW x0,3
Div1.17 (CB17, CC-17) 1A 2P+PE 0,1 kW
Div1.18 (CB18, CC-18) 1A 2P+PE 0,1 kW
Div1.19 (CB19, CC-19) 1,7 A 2P+PE 0,18 kW
Div1.20 (CB20, CC-20) 7,5 A 2P+PE 0,8 kW

Power balance
Ampliacion SE Candelaria
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364 1/14
PANEL T2
Earthing system Mid point grounded Upstream
U0 / Un / 108 V I Allowed 225 A
Ik2 max=3,9kA Total V drop 0 % /
S Asynchronous motors power 0 kVA
See at the end of section:

T2.Circuit1

non-compliant circuit non-compliant circuit non-compliant circuit non-compliant circuit


CIRCUIT CircuitG1 Div1.1 Div1.2 Div1.3
Circuit type Main circuit (Rectifier / battery) Load circuit (Various) Load circuit (Various) Load circuit (Various)
Origin PV1 Barra CC - Caseta 1 Barra CC - Caseta 1 Barra CC - Caseta 1
Designation

Start type Ib 2P+PE 200 A 2P+PE 13,4 A 2P+PE 2,7 A 2P+PE 12,5 A
NE loaded Cos Phi
Harmonic
SUPPLY PV1

TOTAL OF POWER Barra 1 CC-01 CC-02 CC-03


Load 2,4 kW 0,936 kW 4,5 kW
k Simul k Util. k Ext. 1 1 1 0,5 1 0,3 1 0,3
I start / I Ib max 95 A 11,1 A 2,6 A 12,5 A
V drop at start Starting Cos
ISOLATING SWITCHES
Type of switch
Switch name

Rating Earth-leakage p
Back up
BREAK DG1 CB01 CB02 CB03
Protection type Other circuit breaker D / Img high D / Img high D / Img high
Protection name DPX³250 25kA 3P 250A DX³ 10000A 2P D 16A DX³ 10000A 1P D 10A DX³ 10000A 2P D 16A

Rating Polarity 250 A 3P


Earth-leakage Delay
Ith Ith NE 225 A 16 A 10 A 16 A
Img Delay 1250 A 0,01 s 224 A 0,02 s 140 A 0,02 s 224 A 0,02 s
Breaking cap Back up 0 kA 0 kA 0 kA 0 kA
Selectivity Total Total Total
CABLE C1.1 C1.2 C1.3
Cable type Multi-core with PE Multi-core with PE Multi-core with PE
CP model

Methods of in k Cor 31A 1 31A 1 31A 1


Conductor InC
Core insulation Copper EPR or XLPE ( Copper EPR or XLPE ( Copper EPR or XLPE (
Sections 3G4 3G4 3G4

Iz Phase S min Phase 48,6 A 0,7 mm² 48,6 A 0,3 mm² 48,6 A 0,7 mm²
Iz neutral S min Neutral
Local V drop Length 2,93 % 20 m 0,59 % 20 m 2,74 % 20 m
Total V drop Total V drop 7,46 % 5,12 % 7,27 %
upstream max current downstre (PV1 / DG1 ) (CB01 / CC-01 ) (CB02 / CC-02 ) (CB03 / CC-03 )
Ik3 max Ik2 max Ik1 max 3,83 kA 2,367 kA 2,367 kA 2,367 kA
Ik2 min Ik1 min If 3,723 kA 1,862 kA 0,339 kA 0,161 kA 0,339 kA 0,161 kA 0,339 kA 0,161 kA
MAX TIME K²S²
Phase Neutral PE 0,054 s 11,726 s 0,054 s 11,726 s 0,054 s 11,726 s
Max lengt 39,5 m 67,7 m 39,5 m
t max Indirect contacts 5s 5s 5s

Synthetic calculation notes: T2


Ampliacion SE Candelaria
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364 2/14
PANEL T2
Earthing system Mid point grounded Upstream
U0 / Un / 108 V I Allowed 225 A
Ik2 max=3,9kA Total V drop 0 % /
S Asynchronous motors power 0 kVA
See at the end of section:

non-compliant circuit non-compliant circuit non-compliant circuit non-compliant circuit


CIRCUIT Div1.4 Div1.5 Div1.6 Div1.7
Circuit type Load circuit (Various) Load circuit (Various) Load circuit (Various) Load circuit (Various)
Origin Barra CC - Caseta 1 Barra CC - Caseta 1 Barra CC - Caseta 1 Barra CC - Caseta 1
Designation

Start type Ib 2P+PE 12,5 A 2P+PE 1,7 A 2P+PE 1,7 A 2P+PE 0,8 A
NE loaded Cos Phi
Harmonic
SUPPLY

TOTAL OF POWER CC-04 CC-05 CC-06 CC-07


Load 4,5 kW 0,18 kW 0,18 kW 0,08 kW
k Simul k Util. k Ext. 1 0,3 1 1 1 1 1 1
I start / I Ib max 12,5 A 1,7 A 1,7 A 0,7 A
V drop at start Starting Cos
ISOLATING SWITCHES
Type of switch
Switch name

Rating Earth-leakage p
Back up
BREAK CB04 CB05 CB06 CB07
Protection type D / Img high D / Img high D / Img high D / Img high
Protection name DX³ 10000A 2P D 16A DX³ 10000A 2P D 10A DX³ 10000A 2P D 10A DX³ 10000A 2P D 10A

Rating Polarity
Earth-leakage Delay
Ith Ith NE 16 A 10 A 10 A 10 A
Img Delay 224 A 0,02 s 140 A 0,02 s 140 A 0,02 s 140 A 0,02 s
Breaking cap Back up 0 kA 0 kA 0 kA 0 kA
Selectivity Total Total Total Total
CABLE C1.4 C1.5 C1.6 C1.7
Cable type Multi-core with PE Multi-core with PE Multi-core with PE Multi-core with PE
CP model

Methods of in k Cor 31A 1 31A 1 31A 1 31A 1


Conductor InC
Core insulation Copper EPR or XLPE ( Copper EPR or XLPE ( Copper EPR or XLPE ( Copper EPR or XLPE (
Sections 3G4 3G4 3G4 3G4

Iz Phase S min Phase 48,6 A 0,7 mm² 48,6 A 0,3 mm² 48,6 A 0,3 mm² 48,6 A 0,3 mm²
Iz neutral S min Neutral
Local V drop Length 2,74 % 20 m 0,15 % 8m 0,15 % 8m 0,07 % 8m
Total V drop Total V drop 7,27 % 4,68 % 4,68 % 4,6 %
upstream max current downstre (CB04 / CC-04 ) (CB05 / CC-05 ) (CB06 / CC-06 ) (CB07 / CC-07 )
Ik3 max Ik2 max Ik1 max 2,367 kA 2,367 kA 2,367 kA 2,367 kA
Ik2 min Ik1 min If 0,339 kA 0,161 kA 0,627 kA 0,286 kA 0,627 kA 0,286 kA 0,627 kA 0,286 kA
MAX TIME K²S²
Phase Neutral PE 0,054 s 11,726 s 0,054 s 3,724 s 0,054 s 3,724 s 0,054 s 3,724 s
Max lengt 39,5 m 67,7 m 67,7 m 67,7 m
t max Indirect contacts 5s 5s 5s 5s

Synthetic calculation notes: T2


Ampliacion SE Candelaria
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364 3/14
PANEL T2
Earthing system Mid point grounded Upstream
U0 / Un / 108 V I Allowed 225 A
Ik2 max=3,9kA Total V drop 0 % /
S Asynchronous motors power 0 kVA
See at the end of section:

non-compliant circuit non-compliant circuit non-compliant circuit non-compliant circuit


CIRCUIT Div1.8 Div1.9 Div1.10 Div1.11
Circuit type Load circuit (Various) Load circuit (Various) Load circuit (Various) Load circuit (Various)
Origin Barra CC - Caseta 1 Barra CC - Caseta 1 Barra CC - Caseta 1 Barra CC - Caseta 1
Designation

Start type Ib 2P+PE 0,8 A 2P+PE 2,3 A 2P+PE 8,7 A 2P+PE 12,5 A
NE loaded Cos Phi
Harmonic
SUPPLY

TOTAL OF POWER CC-08 CC-09 CC-10 CC-11


Load 0,08 kW 0,24 kW 0,936 kW 4,5 kW
k Simul k Util. k Ext. 1 1 1 0,6 1 0,3 1 0,3
I start / I Ib max 0,7 A 1,3 A 2,6 A 12,5 A
V drop at start Starting Cos
ISOLATING SWITCHES
Type of switch
Switch name

Rating Earth-leakage p
Back up
BREAK CB08 CB09 CB10 CB11
Protection type D / Img high D / Img high D / Img high D / Img high
Protection name DX³ 10000A 2P D 10A DX³ 10000A 2P D 10A DX³ 10000A 2P D 10A DX³ 10000A 2P D 16A

Rating Polarity
Earth-leakage Delay
Ith Ith NE 10 A 10 A 10 A 16 A
Img Delay 140 A 0,02 s 140 A 0,02 s 140 A 0,02 s 224 A 0,02 s
Breaking cap Back up 0 kA 0 kA 0 kA 0 kA
Selectivity Total Total Total Total
CABLE C1.8 C1.9 C1.10 C1.11
Cable type Multi-core with PE Multi-core with PE Multi-core with PE Multi-core with PE
CP model

Methods of in k Cor 31A 1 31A 1 31A 1 31A 1


Conductor InC
Core insulation Copper EPR or XLPE ( Copper EPR or XLPE ( Copper EPR or XLPE ( Copper EPR or XLPE (
Sections 3G4 3G16 3G10 3G16

Iz Phase S min Phase 48,6 A 0,3 mm² 115,3 A 0,3 mm² 86,1 A 0,3 mm² 115,3 A 0,7 mm²
Iz neutral S min Neutral
Local V drop Length 0,07 % 8m 0,52 % 85 m 3,23 % 85 m 2,91 % 85 m
Total V drop Total V drop 4,6 % 5,05 % 7,76 % 7,45 %
upstream max current downstre (CB08 / CC-08 ) (CB09 / CC-09 ) (CB10 / CC-10 ) (CB11 / CC-11 )
Ik3 max Ik2 max Ik1 max 2,367 kA 2,367 kA 2,367 kA 2,367 kA
Ik2 min Ik1 min If 0,627 kA 0,286 kA 0,324 kA 0,154 kA 0,221 kA 0,107 kA 0,324 kA 0,154 kA
MAX TIME K²S²
Phase Neutral PE 0,054 s 3,724 s 0,87 s 205,068 s 0,34 s 166,936 s 0,87 s 205,068 s
Max lengt 67,7 m 270,8 m 169,25 m 158,01 m
t max Indirect contacts 5s 5s 5s 5s

Synthetic calculation notes: T2


Ampliacion SE Candelaria
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364 4/14
PANEL T2
Earthing system Mid point grounded Upstream
U0 / Un / 108 V I Allowed 225 A
Ik2 max=3,9kA Total V drop 0 % /
S Asynchronous motors power 0 kVA
See at the end of section:

non-compliant circuit non-compliant circuit non-compliant circuit non-compliant circuit


CIRCUIT Div1.12 Div1.13 Div1.14 Div1.15
Circuit type Load circuit (Various) Load circuit (Various) Load circuit (Various) Load circuit (Various)
Origin Barra CC - Caseta 1 Barra CC - Caseta 1 Barra CC - Caseta 1 Barra CC - Caseta 1
Designation

Start type Ib 2P+PE 12,5 A 2P+PE 13,4 A 2P+PE 2,7 A 2P+PE 12,5 A
NE loaded Cos Phi
Harmonic
SUPPLY

TOTAL OF POWER CC-12 CC-13 CC-14 CC-15


Load 4,5 kW 2,4 kW 0,936 kW 4,5 kW
k Simul k Util. k Ext. 1 0,3 1 0,6 1 0,3 1 0,3
I start / I Ib max 12,5 A 13,3 A 2,6 A 12,5 A
V drop at start Starting Cos
ISOLATING SWITCHES
Type of switch
Switch name

Rating Earth-leakage p
Back up
BREAK CB12 CB13 CB14 CB15
Protection type D / Img high D / Img high D / Img high D / Img high
Protection name DX³ 10000A 2P D 16A DX³ 10000A 2P D 16A DX³ 10000A 2P D 16A DX³ 10000A 2P D 16A

Rating Polarity
Earth-leakage Delay
Ith Ith NE 16 A 16 A 16 A 16 A
Img Delay 224 A 0,02 s 224 A 0,02 s 224 A 0,02 s 224 A 0,02 s
Breaking cap Back up 0 kA 0 kA 0 kA 0 kA
Selectivity Total Total Total Total
CABLE C1.12 C1.13 C1.14 C1.15
Cable type Multi-core with PE Multi-core with PE Multi-core with PE Multi-core with PE
CP model

Methods of in k Cor 31A 1 31A 1 31A 1 31A 1


Conductor InC
Core insulation Copper EPR or XLPE ( Copper EPR or XLPE ( Copper EPR or XLPE ( Copper EPR or XLPE (
Sections 3G16 3G25 3G16 3G16

Iz Phase S min Phase 115,3 A 0,7 mm² 148,8 A 0,7 mm² 115,3 A 0,7 mm² 115,3 A 0,7 mm²
Iz neutral S min Neutral
Local V drop Length 2,91 % 85 m 2,34 % 100 m 0,73 % 100 m 3,43 % 100 m
Total V drop Total V drop 7,45 % 6,87 % 5,26 % 7,96 %
upstream max current downstre (CB12 / CC-12 ) (CB13 / CC-13 ) (CB14 / CC-14 ) (CB15 / CC-15 )
Ik3 max Ik2 max Ik1 max 2,367 kA 2,367 kA 2,367 kA 2,367 kA
Ik2 min Ik1 min If 0,324 kA 0,154 kA 0,4 kA 0,189 kA 0,285 kA 0,136 kA 0,285 kA 0,136 kA
MAX TIME K²S²
Phase Neutral PE 0,87 s 205,068 s 2,125 s 334,462 s 0,87 s 262,069 s 0,87 s 262,069 s
Max lengt 158,01 m 246,89 m 158,01 m 158,01 m
t max Indirect contacts 5s 5s 5s 5s

Synthetic calculation notes: T2


Ampliacion SE Candelaria
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364 5/14
PANEL T2
Earthing system Mid point grounded Upstream
U0 / Un / 108 V I Allowed 225 A
Ik2 max=3,9kA Total V drop 0 % /
S Asynchronous motors power 0 kVA
See at the end of section:

non-compliant circuit non-compliant circuit non-compliant circuit non-compliant circuit


CIRCUIT Div1.16 Div1.17 Div1.18 Div1.19
Circuit type Load circuit (Various) Load circuit (Various) Load circuit (Various) Load circuit (Various)
Origin Barra CC - Caseta 1 Barra CC - Caseta 1 Barra CC - Caseta 1 Barra CC - Caseta 1
Designation

Start type Ib 2P+PE 12,5 A 2P+PE 1A 2P+PE 1A 2P+PE 1,7 A


NE loaded Cos Phi
Harmonic
SUPPLY

TOTAL OF POWER CC-16 CC-17 CC-18 CC-19


Load 4,5 kW 0,1 kW 0,1 kW 0,18 kW
k Simul k Util. k Ext. 1 0,3 1 1 1 1 1 1
I start / I Ib max 12,5 A 0,9 A 0,9 A 1,7 A
V drop at start Starting Cos
ISOLATING SWITCHES
Type of switch
Switch name

Rating Earth-leakage p
Back up
BREAK CB16 CB17 CB18 CB19
Protection type D / Img high D / Img high D / Img high D / Img high
Protection name DX³ 10000A 2P D 25A DX³ 10000A 2P D 10A DX³ 10000A 2P D 10A DX³ 10000A 2P D 10A

Rating Polarity
Earth-leakage Delay
Ith Ith NE 25 A 10 A 10 A 10 A
Img Delay 350 A 0,02 s 140 A 0,02 s 140 A 0,02 s 140 A 0,02 s
Breaking cap Back up 0 kA 0 kA 0 kA 0 kA
Selectivity Total Total Total Total
CABLE C1.16 C1.17 C1.18 C1.19
Cable type Multi-core with PE Multi-core with PE Multi-core with PE Multi-core with PE
CP model

Methods of in k Cor 31A 1 31A 1 31A 1 31A 1


Conductor InC
Core insulation Copper EPR or XLPE ( Copper EPR or XLPE ( Copper EPR or XLPE ( Copper EPR or XLPE (
Sections 3G16 3G4 3G4 3G4

Iz Phase S min Phase 115,3 A 1,4 mm² 48,6 A 0,3 mm² 48,6 A 0,3 mm² 48,6 A 0,3 mm²
Iz neutral S min Neutral
Local V drop Length 3,43 % 100 m 0,16 % 16 m 0,14 % 14 m 0,26 % 14 m
Total V drop Total V drop 7,96 % 4,7 % 4,67 % 4,79 %
upstream max current downstre (CB16 / CC-16 ) (CB17 / CC-17 ) (CB18 / CC-18 ) (CB19 / CC-19 )
Ik3 max Ik2 max Ik1 max 2,367 kA 2,367 kA 2,367 kA 2,367 kA
Ik2 min Ik1 min If 0,285 kA 0,136 kA 0,4 kA 0,189 kA 0,44 kA 0,206 kA 0,44 kA 0,206 kA
MAX TIME K²S²
Phase Neutral PE 0,87 s 262,069 s 0,054 s 8,562 s 0,054 s 7,166 s 0,054 s 7,166 s
Max lengt 90,33 m 67,7 m 67,7 m 67,7 m
t max Indirect contacts 5s 5s 5s 5s

Synthetic calculation notes: T2


Ampliacion SE Candelaria
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364 6/14
PANEL T2
Earthing system Mid point grounded Upstream
U0 / Un / 108 V I Allowed 225 A
Ik2 max=3,9kA Total V drop 0 % /
S Asynchronous motors power 0 kVA
See at the end of section:

non-compliant circuit
CIRCUIT Div1.20
Circuit type Load circuit (Various)
Origin Barra CC - Caseta 1
Designation

Start type Ib 2P+PE 7,5 A


NE loaded Cos Phi
Harmonic
SUPPLY

TOTAL OF POWER CC-20


Load 0,8 kW
k Simul k Util. k Ext. 1 1
I start / I Ib max 7,4 A
V drop at start Starting Cos
ISOLATING SWITCHES
Type of switch
Switch name

Rating Earth-leakage p
Back up
BREAK CB20
Protection type D / Img high
Protection name DX³ 10000A 2P D 10A

Rating Polarity
Earth-leakage Delay
Ith Ith NE 10 A
Img Delay 140 A 0,02 s
Breaking cap Back up 0 kA
Selectivity Total
CABLE C1.20
Cable type Multi-core with PE
CP model

Methods of in k Cor 31A 1


Conductor InC
Core insulation Copper EPR or XLPE (
Sections 3G4

Iz Phase S min Phase 48,6 A 0,3 mm²


Iz neutral S min Neutral
Local V drop Length 1,22 % 15 m
Total V drop Total V drop 5,75 %
upstream max current downstre (CB20 / CC-20 )
Ik3 max Ik2 max Ik1 max 2,367 kA
Ik2 min Ik1 min If 0,419 kA 0,197 kA
MAX TIME K²S²
Phase Neutral PE 0,054 s 7,849 s
Max lengt 67,7 m
t max Indirect contacts 5s

Synthetic calculation notes: T2


Ampliacion SE Candelaria
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364 7/14
Circuit1
Ib : 109,8 A : 2P+PE
Power : 11,85 kW : :

DC-9 Protection
In : 160 A 3P
LEGRAND MCCB DPX³160 25kA 3P 160A thermal-magnetic :

I th : 160 A : k Temperature : 1 Shorts circuits


I sd : 1600 A Delay : 0,01 s : :
: Magnetic tolerance : 20 % Ik2 max : 3,83 kA
: : :
Icu : 0 kA :
:
:
: :
Frequency not supported. Reference not in the filter.
Breaking capacity insufficient.

Alim B1 C1 Cable
113 m Multi-core with PE (Copper , EPR or XLPE (90°) ) Local V drop : 4,53 %
PE conductor Incorporated to phase cable or grouped
: 2x120+1G70 Shorts circuits
Method of installation : 31A Current carrying capacities downstream Ik2 min : 1,442 kA
Correction factor : 1 Iz PH : 409,9 A Ph mini section : 28 mm² :
Ambient temperature : 30 °C : : If : 0,591 kA
Additional derating : 1
K²S² I²t I²t limited t fonc. t max

Nb additionnal grouped circuits : 0 L : 274,234 E6 A²s 0,147 E6 A²s 0,01 s 18,697 s


Nb of perforated trays or ladders : 1 Ne :
: PE : 93,316 E6 A²s 0,003 E6 A²s 0,01 s 266,715 s
: Max length protected : 68,57 m Indirect contact max time : 5 s
Protection against short circuits improperly adjusted.

CB0B1 Protection
In : 125 A 3P
LEGRAND MCCB DPX³160 16kA 3P 125A thermal-magnetic :

I th : 125 A : k Temperature : 1 Shorts circuits


I sd : 1250 A Delay : 0,01 s : :
: Magnetic tolerance : 20 % Ik2 max : 2,367 kA
: : :
Icu : 0 kA Back up : 40 kA
:
:
: :
Frequency not supported. Polarity inappropriate.
Reference not in the filter.

Synthetic calculation notes: T2 - circuits


Ampliacion SE Candelaria reported in the end section
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364 8/14
Barra CC - Caseta 1 Distribution
Installed power : 11,85 kW : I:Allowed : 125 A
Consumption Output consumption : 126,7 A k Simul : 1 Total V drop (B type) : 4,53 %
Total power : 13,7 kW : :
k Ext. : 1
: :
Shorts circuits
: :
: Corrected consumption : 126,7 A :
Ik2 max : 2,367 kA
:
:
Ik2 min : 1,442 kA
:
If : 0,591 kA

Synthetic calculation notes: T2 - circuits


Ampliacion SE Candelaria reported in the end section
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364 9/14
Identification Selectivity Additional conditions
DG1 / DC-9 Total

DC-9 / CB0B1 Partial, limit to 0 kA (Would be total without


coordination)

CB0B1 / CB01 Total

CB0B1 / CB02 Total

CB0B1 / CB03 Total

CB0B1 / CB04 Total

CB0B1 / CB05 Total

CB0B1 / CB06 Total

CB0B1 / CB07 Total

CB0B1 / CB08 Total

CB0B1 / CB09 Total

CB0B1 / CB10 Total

CB0B1 / CB11 Total

CB0B1 / CB12 Total

CB0B1 / CB13 Total

CB0B1 / CB14 Total

CB0B1 / CB15 Total

CB0B1 / CB16 Total

CB0B1 / CB17 Total

CB0B1 / CB18 Total

CB0B1 / CB19 Total

CB0B1 / CB20 Total

List of selectivity panel T2


Ampliacion SE Candelaria
Printed on 26-04-2021 Ref. :
Rev. : 1 Creation of the study 26-04-21. Legrand XLPro³Calcul Export 3.6.06 -b2 IEC 60364 10/14
Identificati Circuit name Designation Settings
CB0B1 MCCB DPX³160 16kA 3P 125A thermal-magnetic I th=125A (1xIn)
CB01 MCB DX³ 10000A 2P D 16A
CB02 MCB DX³ 10000A 1P D 10A
CB03 MCB DX³ 10000A 2P D 16A
CB04 MCB DX³ 10000A 2P D 16A
CB05 MCB DX³ 10000A 2P D 10A
CB06 MCB DX³ 10000A 2P D 10A
CB07 MCB DX³ 10000A 2P D 10A
CB08 MCB DX³ 10000A 2P D 10A
CB09 MCB DX³ 10000A 2P D 10A
CB10 MCB DX³ 10000A 2P D 10A
CB11 MCB DX³ 10000A 2P D 16A
CB12 MCB DX³ 10000A 2P D 16A
CB13 MCB DX³ 10000A 2P D 16A
CB14 MCB DX³ 10000A 2P D 16A
CB15 MCB DX³ 10000A 2P D 16A
CB16 MCB DX³ 10000A 2P D 25A
CB17 MCB DX³ 10000A 2P D 10A
CB18 MCB DX³ 10000A 2P D 10A
CB19 MCB DX³ 10000A 2P D 10A
CB20 MCB DX³ 10000A 2P D 10A
DC-9 MCCB DPX³160 25kA 3P 160A thermal-magnetic I th=160A (1xIn)
DG1 MCCB DPX³250 25kA 3P 250A thermal-magnetic I th=225A (0,9xIn) I sd=1250A (5xIn)

Ampliacion SE Candelaria
Log setting of circuit breakers T2
Printed on 26-04-2021 Ref. : Legrand XLPro³Calcul Export 3.6.06 -b2
Rev. : 1 Creation of the study 26-04-21. IEC 60364 11/14
Identificati Beginning Circuit name Nature Sections L (m) Ending
Alim B1 C1 DC-9 Copper EPR or XLPE (90°) 2x120+1G70 113 CB0B1
C1.1 CB01 Copper EPR or XLPE (90°) 3G4 20 CC-01
C1.2 CB02 Copper EPR or XLPE (90°) 3G4 20 CC-02
C1.3 CB03 Copper EPR or XLPE (90°) 3G4 20 CC-03
C1.4 CB04 Copper EPR or XLPE (90°) 3G4 20 CC-04
C1.5 CB05 Copper EPR or XLPE (90°) 3G4 8 CC-05
C1.6 CB06 Copper EPR or XLPE (90°) 3G4 8 CC-06
C1.7 CB07 Copper EPR or XLPE (90°) 3G4 8 CC-07
C1.8 CB08 Copper EPR or XLPE (90°) 3G4 8 CC-08
C1.9 CB09 Copper EPR or XLPE (90°) 3G16 85 CC-09
C1.10 CB10 Copper EPR or XLPE (90°) 3G10 85 CC-10
C1.11 CB11 Copper EPR or XLPE (90°) 3G16 85 CC-11
C1.12 CB12 Copper EPR or XLPE (90°) 3G16 85 CC-12
C1.13 CB13 Copper EPR or XLPE (90°) 3G25 100 CC-13
C1.14 CB14 Copper EPR or XLPE (90°) 3G16 100 CC-14
C1.15 CB15 Copper EPR or XLPE (90°) 3G16 100 CC-15
C1.16 CB16 Copper EPR or XLPE (90°) 3G16 100 CC-16
C1.17 CB17 Copper EPR or XLPE (90°) 3G4 16 CC-17
C1.18 CB18 Copper EPR or XLPE (90°) 3G4 14 CC-18
C1.19 CB19 Copper EPR or XLPE (90°) 3G4 14 CC-19
C1.20 CB20 Copper EPR or XLPE (90°) 3G4 15 CC-20

Ampliacion SE Candelaria
Cable Nomenclature T2
Printed on 26-04-2021 Ref. : Legrand XLPro³Calcul Export 3.6.06 -b2
Rev. : 1 Creation of the study 26-04-21. IEC 60364 12/14
Reference Quantity Manufacturer Designation Identification(s)
409430 1 LEGRAND MCB DX³ 10000A 1P D 10A CB02
409449 10 LEGRAND MCB DX³ 10000A 2P D 10A CB05 CB06 CB07 CB08 CB09 CB10 CB17 CB18 CB19
CB20
409451 8 LEGRAND MCB DX³ 10000A 2P D 16A CB01 CB03 CB04 CB11 CB12 CB13 CB14 CB15
409453 1 LEGRAND MCB DX³ 10000A 2P D 25A CB16
420006 1 LEGRAND MCCB DPX³160 16kA 3P 125A thermal-magnetic CB0B1
420047 1 LEGRAND MCCB DPX³160 25kA 3P 160A thermal-magnetic DC-9
420209 1 LEGRAND MCCB DPX³250 25kA 3P 250A thermal-magnetic DG1

113 m Cable Copper EPR or XLPE (90°) 2x120+1G70 Alim B1 C1


85 m Cable Copper EPR or XLPE (90°) 3G10 C1.10
555 m Cable Copper EPR or XLPE (90°) 3G16 C1.9 C1.11 C1.12 C1.14 C1.15 C1.16
100 m Cable Copper EPR or XLPE (90°) 3G25 C1.13
171 m Cable Copper EPR or XLPE (90°) 3G4 C1.1 C1.2 C1.3 C1.4 C1.5 C1.6 C1.7 C1.8 C1.17 C1.18
C1.19 C1.20

Ampliacion SE Candelaria
Panel T2
Printed on 26-04-2021 Ref. : equipment list Legrand XLPro³Calcul Export 3.6.06 -b2
Rev. : 1 Creation of the study 26-04-21. IEC 60364 13/14
Reference Quantity Manufacturer Designation
409430 1 LEGRAND MCB DX³ 10000A 1P D 10A
409449 10 LEGRAND MCB DX³ 10000A 2P D 10A
409451 8 LEGRAND MCB DX³ 10000A 2P D 16A
409453 1 LEGRAND MCB DX³ 10000A 2P D 25A
420006 1 LEGRAND MCCB DPX³160 16kA 3P 125A thermal-magnetic
420047 1 LEGRAND MCCB DPX³160 25kA 3P 160A thermal-magnetic
420209 1 LEGRAND MCCB DPX³250 25kA 3P 250A thermal-magnetic

113 m Cable Copper EPR or XLPE (90°) 2x120+1G70


85 m Cable Copper EPR or XLPE (90°) 3G10
555 m Cable Copper EPR or XLPE (90°) 3G16
100 m Cable Copper EPR or XLPE (90°) 3G25
171 m Cable Copper EPR or XLPE (90°) 3G4

Ampliacion SE Candelaria
Bill of materials
Printed on 26-04-2021 Ref. : Legrand XLPro³Calcul Export 3.6.06 -b2
Rev. : 1 Creation of the study 26-04-21. IEC 60364 14/14