Design of Fastenings for Dynamic

Actions (Seismic Loads)

Seminar Teheran

November , 2006

www.hilti.com Seismic design for anchors 1


Jenö Varga

1976 - 1981: Civil Engineering Diploma, Technical University of Budapest, Hungary

1981 - 1982: Structural Designer, “Olajterv” – Budapest, Hungary

1882 - 1983: Engineer, Hungarian Army, Hungary

1983 - 1991: Research Officer, Technical University of Budapest, Hungary


1984 - 1987: Post-graduate Research, The University of Adelaide, Australia

1991 - 1993: Senior Lecturer, The University of Witsvatersrand, Johannesburg, South Africa
1991 – 1993 Post-Doctoral Research

1993 - 1998: Research Officer, IWB, The University of Stuttgart, Germany


approval and development tests of various pre-cast and post-installed
fasteners, contribution into CEB Fastening Design
1995 – 1997: Teacher Diploma, The University of Budapest

1998 - 2000: Teacher, International School of Stuttgart, Germany


Mathematics, Physics, Computing – IB course Higher lever

2000 - : Engineer, Hilti AG, Fastening Technologies


(application support for non-code cases – fastenings, training Hilti staff,
calculation control, Profis Anchor - project manager, HAT-175 developer)

www.hilti.com Seismic design for anchors 2


Basics
Differences to static design, classification, characteristics:
induced accelerations activate forces of inertia and damping

Classification Fatigue Seismic Shock

Number of
104 < n < 108 101 < n < 104 1 < n < 20
load cycles

Rate of strain 10-6 <  < 10-3 10-5 <  < 10-2 10-3 <  < 10-1
•Traffic loads •Earthquakes •Explosions
Examples
•Machines, cranes •Artificial •Abrupt Structure
•Ventilators earthquakes failure
•Wind, Waves •Crash Barriers

Ratio FR,dyn/FR,stat 30 (!) - 100% 80 - 130% 100 - 200%

www.hilti.com Seismic design for anchors 3


Examples Earthquake
Typical Fastening Problems (structural and non structural)

Toppled and damaged Falling wall panels


furniture,City Hall Kobe, 1995 Public Building, Kobe, 1995

Suspended Ceilings
San Francisco Airport
Loma Prieta earthquake
1989

Damages in a Switchyard Destroyed column fixing


Managua, 1972 San Francisco, 1989
www.hilti.com Seismic design for anchors 4
Earthquake Relevance

www.hilti.com Seismic design for anchors 5


Video from Hyogo-Ken Nanbu Earthquake
Kobe, Japan
January 17, 1995 5:46 am

moment magnitude: 7.2 (JMA)


loss of life: 5,200
injured: > 26,000 Kobe2.mpg

homeless: > 300,000


estimated total loss: $100 billion

www.hilti.com Seismic design for anchors 6


Examples Shock
Typical Fastening Problems (structural)
Emergency Installations
(e.g. emergency stop
fixings in elevators)

Crash barrier fixing on concrete


(e.g. on bridges, etc.)

Explosions
(e.g. installations in civil shelters)
www.hilti.com Seismic design for anchors 7
Examples Fatigue

Machine fixing
(e.g. pumps, ventilators,
punching machines, etc.)
Robot fixing
(e.g. in automobile
industry, etc.) Fixing of cranes,
hydro-jacks, etc.)

www.hilti.com Seismic design for anchors 8


Suitability of Different Anchor Types

controlled
Displacement

Bonded

Bonded Expansion

Concrete screw

bolt
Torque controlled

sleeve
Torque controlled

Undercut
Anchor Type

Base Material

Un-cracked concrete + ++ ++ ++ ++ ++ ++

Cracked concrete - + ++ ++ ++ ++ ++
Small cracks w<0,5mm

Cracked concrete - - + + + ++ ++
Medium cracks
0.5mm<w<1.0mm
Cracked concrete - - - - - + ++
Large cracks w>1,0mm

++ very suitable + suitable – not suitable


www.hilti.com Seismic design for anchors 9
General Rules for Seismic Safe Design

Design Constructive
• EQ-proof position and
fastening measures

• EQ-proof design of the fixing


• Additional Fixings as
constructive measure
• Limitation or allowance of
displacements
Examples • design of anchors • screws, clamping etc. to
• design of cross- limit displacements
sections, etc. • struts to take horizontal
loads
• free space to allow
differential displacements

www.hilti.com Seismic design for anchors 10


Design for Earthquakes
Main difficulties for a proper earthquake design

1. Predictability of Seismic activities and loads Ground acceleration

time

Floor acceleration
time

Equipment acceleration

time

2. Cracks 3. Ductility

www.hilti.com Seismic design for anchors 11


Design for Earthquakes

Example: Uniform Building Code (USA)

•estimation of horizontal load (static)

Fp  Z  I  C p  W p
FP static horizontal load
Z factor for seismic zone (from code)
I factor for acceleration
CP factor for stiffness of structure
WP mass of element / equipment

•resistance: safety factor 4


“fasteners shall be designed for four times the forces determined“

www.hilti.com Seismic design for anchors 12


3 main design possibilities
Stiff fixture: ”equivalent force process” stiff fixing
Based on the building floor
acceleration and the mass of the
fixture.

Elastic fixture: “response spectra process” low


elastic fixing
natural frequency, the load on the fas-
tening is governed by the fixture's
response to dynamic incitation.
Acceleration of the fixture is relevant
when using this process.
ductile fixing
Ductile fixture: “plastic design” fastening design
is based on the maximum load that can
be applied to the anchor when plastic
deformation takes place.

www.hilti.com Seismic design for anchors 13


Case Study Seismic Design

Example: Equivalent Force Process


afloor = 0.75 g ≈ 7.5 m/s2 (e.g. from codes)
F=m . afloor
F=500 . 7.5 = 3,750 N = 3.75 kN
Vd=F / 4
Vd=3.75 / 4 = 0.94 kN
Nd= F . hCG / (2 . b)
Nd= 3.75 . 100 / (2 . 60) = 3.13 kN
2 2
Sd  Vd  Nd

Sd  0.942 3.132 3.27kN

www.hilti.com Seismic design for anchors 14


Case Study Seismic Design

Example: Response Spectra Process

Ventilation unit mounted on springs (for


insulation reasons): f0<15Hz
afloor = 0.75 g ≈ 7.5 m/s2
Increasing factor due to low natural
frequency: factor Aequip = 2.0 (out of literature
or manufact. informations)
-> aequip = Aequip*afloor ≈ 15 m/s2
F = m*aequip
F = 600*15 = 9,000N = 9.0kN
Vd = F/4
Vd = 9.0/4 = 2.25 kN
Nd = F*hCG / (2*b)
Nd = 9 . 80 / (2*175) = 2.06 kN
Fadm,eq = Rd,crack > Sd

www.hilti.com Seismic design for anchors 15


Case Study Seismic Design

Example: Design with Plastic Moment

Installation channels used as columns


for ventilation fixing:
W=3’000mm3,fy=235N/mm2
Mplast = fy . W
Mplast = 235*3’000 = 705’000 Nmm
Mplast is generated Fplast, acting at a height, hp:
Fplast = Mplast/hp
Fplast = 705’000 / 500 = 1,410 N = 1.41 kN

www.hilti.com Seismic design for anchors 16


Seismic Design with Hilti PROFIS Anchor program

www.hilti.com Seismic design for anchors 17


Special Applications: Nuclear Power Plants - Impact

DIBt Guideline for the use of anchors in Nuclear Power Plants (NPP)
Impact categories:

A) probability of 1 occurrence during service life


(design earthquake, plane crash, explosions...)

B) probability of 10 occurrences during service life

C) service loads (static) and incidents with a


probability of 10 occurrences during
service life

For safety relevant fixings in NPP, DIBt asks for additional tests beside the
statical DIBt or ETA-approval.

DIBt: Deutsches Institut für Bautechnik (German Institute for construction technology)

www.hilti.com Seismic design for anchors 18


Special Applications: Nuclear Power Plants - Design
DIBt Guideline for the use of anchors in Nuclear Power Plants (NPP)

Design according to concrete-capacity-method, with special load and


material safety factors
Load safety factors:
G=Q= 1.0 for category A
1.2 for category B
1.4 for category C

Material safety factors:


concrete Mc=Mp= 1.7 for category A
1.9 for category B
2.1 for category C
steel: according to ETAG, Annex C
(Ms=1.4 for tensile loads and Ms=1.25 for shear loads)

www.hilti.com Seismic design for anchors 19


Special Applications: Nuclear Power Plants - Tests
DIBt Guideline for the use of anchors in Nuclear Power Plants (NPP)
• all anchors are set in closed hairline cracks
crack width at test load criteria
N - displacement at 0.5 Fu,m
1 1.5 mm - variation of Fu,m
t - value of Fu,m
N - no failure
2 1.5 mm - develop. of displacement
t in time

w 1.5mm - no failure
N
3 1.0mm - develop. of displacement
t t in time

N - variation of displ. at Fu,m


4 1.0 mm - variation of Fu,m
t
- no failure
V
5 1.0 mm t - final ultimate shear load

www.hilti.com Seismic design for anchors 20


Earthquakes: Testing of Anchors
Many different test procedures according to national regulations

Excerpt from ICC ES Acceptance Criteria (seismic method 6.2.7.2):

• Tension: pulsating sinusoidal seismic cycle


• shear: alternating sinusoidal seismic cycle
• frequency 0.1 to 0.2 Hertz
• at least 5 anchors
• shallowest and deepest embedment depth

www.hilti.com Seismic design for anchors 21


Earthquakes: Testing of Anchors - Tension
• Maximum load Ns: 1.5tension value for which recognition is
desired
• The minimum load value shall not be smaller than 5% of Fu
• Uncracked concrete

Ns Ns: maximum tension test load


load
Ni
Ni: a load midway between
Nm Ns and Nm
10 30 100
Nm: 1/4 of the average ultimate
cycles
tension load Tref

www.hilti.com Seismic design for anchors 22


Earthquakes: Testing of Anchors - Shear
• Maximum load Vs: 1.5shear value for which recognition is desired
• The value for which recognition is desired shall not be larger than
133.33 percent of the allowable static loads under the same
conditions
• Uncracked concrete
Vs
load Vi
Vm Vs: maximum shear test load

10 30 100 Vi: a load midway between


Vs and Vm
cycles
Vm: 1/4 of the average ultimate
- -Vm tension load Tref
Vi
-Vs

www.hilti.com Seismic design for anchors 23


General Improvement of Fixings to Steel Beams

Standard Fixings
not suitable for EQ limited suitable for EQ

www.hilti.com Seismic design for anchors 24


General Improvement of Fixings to Steel Beams

Improvement with
Hilti MF-CS

www.hilti.com Seismic design for anchors 25


General Improvement of Fixings to Steel Beams

Securing of
channels with
End- Stoppers

www.hilti.com Seismic design for anchors 26


General Improvement of Fixings to Steel Beams

Securing of
channels with
End- Stoppers

Securing of
channels with
DX

www.hilti.com Seismic design for anchors 27


Installations: Pipes

The distance between the


supports, the size and mass
of the pipe and the
horizontal acceleration are
decisive whether or not
struts are necessary.

www.hilti.com Seismic design for anchors 28


Installations: EQ Proof Channels
multiple fixing Load Direction
lateral longitudin
Type al

direct
no additional measures for EQ
necessary
ceiling

hanger
stiff U-Joch constructions or
struts necessary

console

no additional additional
wall

struts struts
necessary

www.hilti.com Seismic design for anchors 29