MATERIAL SUBMITTAL MS
TO : Saudi Consulting Services Co. (SAUDCONSULT) FROM: BEC Saudi Arabia
Type of Submittal: Samples Specifications Catalogues
Manufacturer / Supplier Details Others (Please Specify:)
1
KIMMCO/ Fawaz Ref. & AC Contracting
L.L.C.
P.O. Box: 2988, RIYADH, 12812, KSA 23 07 00 C
Attached all relevant technical literature marked to identify relevant description, current Test Certificates, samples as appropriate.
Country of Origin:
Availability
Locally Manufactured Overseas
Delivery : Ex-works/Factory [ ]
Lead Time (from P.O. to Arrival on Site) [ ] Days
Estimated Time of Arrival on Site [ ]
Related to LEED V4 construction Prerequisite and/or Credit Yes Refer to attached sheet No Not Applicable
Reviewed & Signed by: Name: Signature Date:
05-11-2022
ACOUSTIC DUCT LINER INSULATION SUBMITTALS
Project Specification Y
Compliance Sheet Y 24
Item
S.NO SPECS NUMBER Description PROPOSED MATERIAL BY MANUFACTURER area of application MANUFACTURER MODEL COUNTRY OF ORIGIN
as Per IFC
KIMMCO GLASS WOOL
ACOUSTIC DUCT LINER (KCL) :
1 23 07 00 (2.1.3) DENSITY: 24 Kg/m3, ACOUSTIC DUCT LINER KIMMCO-ISOVER KCL KUWAIT
THICKNESS : 25 mm, FACING :
BGF
PROJECT SPECIFICATION
KEY:
H
KA
EK
LOT D
M
5 10
PITCH 1/2
D1 %
HEEL RADIUS 1
SPLITTER 3/4D D+3/4D
ISOLATING
D+3/4D ROD STRAIGHT VALVES
D 2
HEEL RADIUS
SPLITTER THROAT RADIUS BUTT HINGE
D ITEM DESCRIPTION
2a
ROD 3/4 D DOOR WINDOW SASH
LOCK
THROAT RADIUS 1 G.S.S. DUCTING OIL TRAP
15 mm (REQUIRED
AT EACH 8m
3/4 D DOOR FRAME
DOUBLE THICKNESS VANES 2 THERMAL INSULATION / LINER ADHESIVE INSULATION OF SUCTION
INTERVAL
LIFT)
3
2a SELF ADHESIVE PIN / HANGER 9
TACK WELD
3 ACOUSTIC LINER
GASKET
SPLITTER 4 8
FIBER GLASS RIGID BOARD 48 kg/m3, 25mm Thick DUCT
DAMPER SUCTION LIQUID
AIR FLOW 7 EXTENSION COLLAR USED LINE LINE
4a FIBER GLASS RIGID BOARD 48 kg/m3, 25mm Thick WHEN DUCT IS INSULATED
1
SPLITTER 2a 4 6 DETAIL "B"
4b FIBER GLASS RIGID BOARD 48 kg/m3, 50mm Thick WINDOW SASH LOCK
ROD 2 4a
5 ALUMINUM FOIL SELF ADHESIVE TAPE AT GRILLE'S
D+3/4D 4b
STRAIGHT HEEL RADIUS ONLY USED WHEN SPACE PLENUM BOX EXTENSION COLLAR LENGTH (SEE DETAIL B )IS DETERMINED
6 INTERNAL INSTALLATION 30-36 TOW LAYERS, 3
SPLITTER LIMITATION DOES NOT EXTERNAL INSTALLATIONS 30-36 TWO LAYERS + 57 ONE LAYER BY INSULATION THICKNESS USED ON DUCT OR CASING INDOOR
DAMPER ALLOW FULL RADIUS ELBOW
UNIT
THROAT RADIUS APPLICATION MATERIAL SPECIFICATION
CURVED FOR
7 CANVAS CLOTH 8 OUNCE A. INDOOR A/C S & R DUCT 1 2 2a 4 5 6 7 8 10
45^ 1. DOOR - 24 U.S.GAGE STEEL OR 22 B & S GAGE ALUMINIUM.
IN COND SPACES 2. FRAME - 24 U.S.GAGESTEEL OR 22 B & S GAGE ALUMINIUM.
FOR SMALL 1/2
8 SAME AS ITEM 6 BUT SECOND COAT 3. EXTENSION COLLAR - SAME GAGE AS DUCT METAL. TWO ELBOWS OIL
BRANCHING %
B. A/C DUCT S & R DUCTS IN 2a 4b 5 6 7 8 10 4. BUTT HINGES - STEEL. (CAN BE DELETED
TRAP
SPLITTER ROD 1 2
10 5. GASKETS - FELT. SUCTION LIFT IS
IF
SHAFTS & NON COND. SPACES
9 ALUMINUM CLADDING 6. FASTENER - SINGLE ACTING HANDLE WITH <2.4m)
WINDOW SASH LOCK.
AIR FLOW AIR FLOW C. ROOF EXPOSED S & R DUCTS 1 2 2a 3 4b 5 6 7 8 9 REFRIGERANT
10 50X50X0.6 mm G.I. ANGLE
PIPING
SCHEMATIC DIAGRAM
TYPICAL DUCTING TAKE - OFFS INSULATION AND LAGGING DETAIL REACH - THRU ACCESS DOOR
RECTANGULAR GALV. STEEL DUCT CONSTRUCTION AND TRANSVERSE JOINT REINFORCEMENT FOR LOW
WIDTH
SIZE
(mm)
KEY PLAN:
OIL THERMAL EXPANSION
TRAP VALVE
OF HANGER SIGHT
(d)IN mm 25X25X1.46 25X25X3 40X40X1.46 40X40X4 40X40X5 40X40X6 50X50X5 50X50X6 70X70X6 GLASS
H
1050 15 50 65 145 220 275 410 540 875 KA
EK
TYPICAL DUCT WALL PENETRATION (APPLICABLE FOR NON. FIRE RATED WALLS) M
1200 - 35 50 130 205 260 395 525 860 FLOOR & WALL DUCT PENETRATION WITH FIRE DAMPER DETAIL REFRIGERANT
PIPING
- - - 85 160 220 355 480 815
1500 SCHEMATIC DIAGRAM
1650 - - - 45 120 180 320 445 780 LOT D
1800 - - - - 85 145 280 410 745
SEALENT
AL.FLASHING
SLOPE
STRAP (WXT(min)mm LOAD, kg
16 18 20 22 24 26 W T
ALTERNATE STRAP 25X0.75 120 GAUGE RIVET 150 HIGH, R.C.C. UPSTAND
STRAP (TYP.) OR
OR ANGLE MIN. THICKNESS
25X0.91 145 1.46 1.18 0.91 0.75 0.60 0.47 WELD
ROD (FROM FFL)
mm H H.3 H 01 GOOD FOR TENDER M.A 09.2020
UPPER 2
25X1.18 190 WT. kg / m H
12.96 10.52 8.08 6.86 5.64 4.42 T
ATTACHMENTS MINIMUM ROOF SLAB 00 GOOD FOR TENDER M.A 08.2020
25X1.46 320 RIGIDITY
UP THRU 10 CLASS
GASKET H
No. REVISION APP'D DATE
40X1.46 500
11-12 A-2.5
17-18
A-3.0
A-3.0
A-2.5
A-2.5
A-1.5
A-1.5
EI + H (mm)XT
H (mm) XT
(mm)
H (mm) XT(a) HXT (b) mm ﺔ ﻟﻠﻌﻘﺎر#ﺷ ـ ـ ــﺮﻛﺔ اﻟﻤﻨﻄﻘﺔ اﻟﺬﻛ
76 mm 10
13
310
570
19-20 B-30 B-2.5 A-1.5 A-1.5 A 0.15 30X26 ga -,25X26 ga 13X24 ga 25 X 3
SMART SQUARE REAL ESTATE
21-22 B-30 B-30 B-2.5 A-1.5 A-1.5
(150 mm)
MAX (TYP)
SCREWS
25mm MIN. 16 910
23-24 C-3.0 C-3.0 C-2.5 B-1.5 B-1.5
B 0.30 30X26 ga -,25X26 ga 20X24 ga 25 X 3
COMPANY
BOLT d TYPICAL DOG HOUSE DETAIL
25-26 C-3.0 C-3.0 C-3.0 C-2.5 B-1.5 B-1.5 C 0.75 30X22 ga -,25X26 ga 25X24 ga 25 X 3
MAXIMUM ALLOWABLE
STRAP HANGER
TRAPEZE HANGER STRAP AND ROD LOADS 27-28 C-3.0 C-3.0 C-3.0 C-1.5 C-1.5 B-1.2 CONSULTANT
DUCT DIMENSIONS (INCHES)
HANGER COUPLING HANGER 61-72 I-1.5 H-1.2 H-1.0 H-1.0 - - H 14 -NOT GIVEN -NOT GIVEN 40 X 4
STRAP STRAP
73-84 J-1.2 J-1.2 I-1.0 - - -
HANGER ROD I 22 40 X 5 PROJECT TITLE
85-96 K-1.2 K-0.75 J-0.75 - - -
WASHER
OVER 96 K-0.75 K-0.75 - - - - J 30
NUT 40 X 6
EXPANSION SHIELDS CONCRETE ANCHORS EXPANSION NAIL POWER ACTUATED WELDED STUDS K 50 X 5
ﺔ#ﻣ ـﺸ ـ ـ ــﺮوع اﻟﻤﻨﻄﻘﺔ اﻟﺬﻛ ـ ـ ــ
STUDS INTO STEEL
UPPER ATTACHMENTS
(a) FOR A GIVEN DUCT THICKNESS, NUMBERS INDICATE
MAX. SPACING (m) BETWEEN DUCT REINFORCEMENT,
LETTERS INDICATE TYPE OF DUCT REINFORCEMENT.
+ NOMINAL EI EQUALS NUMBER LISTED TIMES 10
TENDER DOCUMENTS
PROJECT ZONE BLDG. STAGE SERIAL NUMBER REVISION
RH1848 00 LD TD MG004 01
SECTION 23 07 00
HVAC INSULATION
October 2021 Smart Square Project
Specifications
TABLE OF CONTENT
SECTION 23 07 00
HVAC INSULATION
PART 1 GENERAL
1.1.1 Supply and install all insulation and lagging on piping, vessels or ducts as indicated
on the drawings or specified to be insulated. Authority regulations and Sustainability
requirements shall also be considered and more stringent specifications to be adopted
1.1.2 Adhesives, sealants, vapour barriers, paints, coating, etc., shall be suitable to HVAC
applications.
1.1.3 All insulation material shall have Zero Ozone Depletion Potential (ODP=0) and less
than Five Global Warming Potential (GWP < 5).
1.1.4 Canvas jacket and all insulating materials shall be non-combustible, or self-
extinguishing non-flame spread grade.
1.1.5 Insulation in exposed areas, i.e. permanently visible, shall be protected with
aluminium cladding as specified herein after.
1.2.1 All items specified in this section are included in each of following divisions, sections
and sub-sections as applicable, as if repeated therein verbatim.
1.3.1 product
1.3.2 samples
1.4.1 Codes and standards applicable to this section shall be primarily British Standards
and United States Codes, unless otherwise specified, the performance/manufacturing
standards of items mentioned in this section shall confirm to the applicable portions
of the latest editions of the following codes, standards and regulations.
Applicable
Reference Code Abbreviation Standard Title of Standard
National Fire Protection NFPA NFPA 90A Standard for Air Conditioning and
Association Ventilating Systems.
1.5.1 ll duct insulation shall be tested in accordance with test methods BS476 pt 6 “Fire
Test on Building Materials and Structures, Method of Test for Fire Propagation for
Products”.
1.5.2 All duct insulation shall be tested in accordance with test methods ISO 5659-Smoke
Density and Toxicity with Additional Gas Analysis. The insulation must comply to
the Standard in terms of smoke density (Dm <200) and combustion gas
concentrations must not exceed those specified in the Standard.
1.6.1 deliver, protect and handle products with care to avoid damage.
1.6.2 tore insulation in original wrapping and protect from weather and construction traffic.
1.6.3 Prolonged storage of duct insulation should be in a cool dry place and away from
direct sunlight. Store material in original packaging. Follow manufacturer’s
recommended storage instructions.
PART 2 PRODUCTS
2.1.1 Codes
2.1.1.1 BS 476 pt 6: Fire Tests on Building Materials and Structures , Method of Test for
Fire Propagation for Products ( British Standards)
2.1.1.2 BS 476 pt 7 : Fire Tests on Building Materials and Structures , Method of Test
for Fire Propagation for Products
2.1.1.3 AS 1530 pt 3: Simultaneous Determination of Ignitibility, Flame Propagation, Heat
Release and Smoke Release ( Building Code of Australia 1979)
2.1.1.4 ASTM E84-05 ( UL 723, NFPA 255) : Surface Burning Characteristics of Building
Materials.
2.1.2.1 Physically crosslinked, closed cell Polyolefin foam with factory applied, 9um
reinforced aluminium foil and factory applied acrylic adhesive backing.
2.1.2.2 Density: 25 Kg / m3 (foam core only)
2.1.2.3 Thermal Conductivity (ASTM C518) : Maximum 0.032 W/mK at mean temperature
23oC
2.1.2.4 Moisture absorption : Non hygroscopic
2.1.2.5 Water Vapour permeability (ASTM E96) : Better than 8.19 X 10-15 Kg/Pa.s.m
2.1.2.6 Minimum Service Temperature : - 80o C
2.1.2.7 Maximum Mean Duct Service Temperature : 90o C
2.1.2.8 Maximum Service Temperature : 1000 C
2.1.2.9 Fire Rating:
•
Class 0 to BS476
•
Complies with ASTM E84 ( 25/50)
•
UL 723 certificate from the UL , Company name must be listed in the UL database
available online.
• FM 4924 Approval for the sheets
• Smoke Density and Toxicity
a) Meets ISO 5659 ( 1994) - Smoke Density and Toxicity
b) Dm <200
c) Combustion gases CO, HCL,HF, NOx, HBr, HCN and SO2 to be within the maximum
allowable concentrations of the Standard.
2.1.3 Duct Insulation (Outdoor)
2.1.3.1 Physically crosslinked, closed cell Polyolefin foam with factory applied, heavy duty
multilayer composite with a specially developed UV and weather durable coating
2.1.3.2 Density: 25 Kg / m3 (foam core only)
2.1.3.3 Thermal Conductivity (ASTM C518): Maximum 0.032 W/mK at mean temperature
23oC
2.1.3.4 Puncture Resistance >400 N (ASTM D4833)
2.1.3.5 Tear Testing (ASTM D751) > 60 N Machine Direction , > 50 N Cross Direction
2.1.4 Fittings
2.1.4.1 The same material is to be used for insulating the flanges (150mm width). Refers to
manufacturer’s installation instructions for flanges
2.1.4.2 All joints to be sealed with 75mm wide foil tape.
2.1.4.3 No clad tape to be used for the outdoor duct insulation with 75mm wide foil tape no
clad type.
2.1.4.4 Same material or approved foam gasket to be used on all hangers supporting the
ducts.
2.1.4.5 Refer to manufacturer’s installation instructions.
Khatib & Alami HVAC Insulation
23 07 00 - 5
October 2021 Smart Square Project
Specifications
2.1.5 Adhesive
2.1.5.1 Factory applied acrylic adhesive G60 supplied with the insulation ( factory applied)
2.2.1 This type of insulation shall apply to refrigerant pipes and A/C condensate drain
pipes. Thickness ½ inch.
2.2.2 Insulation shall be flexible foamed closed cell elastomeric tubular form type.
Insulation may be slipped over pipe or tubing before pipe connections are made, or
may be slit longitudinally and snapped onto the pipe and then sealed with vapour
barrier adhesive.
2.2.3 Insulation shall have a thermal conductivity not greater than 0.27 Btu/hr °F. ft2. per
inch thickness at a mean temperature of 75 ° F.
2.2.4 The surface finish shall be an 8-ounce canvas cloth embedded between 2 coats of
vapour barrier. Aluminium cladding shall be provided as specified.
Insulation shall be 75mm thick hydrous calcium silicate sheet, rigid board form, 11
lbs/ft3 (175 Kg/m3) density, 0.38 Btu.in/ft2.hr.°F(0.055 W/m.° K) K-factor at mean
temperature of 100 °F (38 °C) applicable maximum temperature is 1200 °F (650
°C)) secured with metal mechanical surfaces fasteners on 460 mm centers both ways
and metal bands on 460mm centers, surfaces with a coat of hard surface insulating
cement, 13mm thick, and exposed portions finished with 8 ounce glass cloth jacket
neatly pasted on.
2.4 Equipment Insulation
2.4.1 This type of insulation shall apply to pumps, heat exchangers and water expansion
tanks.
2.4.2 Insulation shall be semi-rigid fibrous glass with organic binder up in board form with
a minimum density of 3 lbs/ft3 (50 kg/m3) and a maximum K-factor of 0.42 Btu-
in/ft2.hr.°F (0.06 W/m.° K) at a mean temperature of 200 °F (94 °C). Insulation shall
be applied over pins welded to the vessel on 300 mm centers. All joints shall be
staggered and tightly butted. The insulation shall be covered with gauge 18
2.4.3 This type of insulation shall apply to water chillers and water expansion tanks.
2.4.4 Insulation shall be flexible elastomeric flat sheets furnished with a smooth skin on the
outer side with a maximum K-factor of 0.27 Btu-in/ft2.hr.°F (0.039 W/m.° K) at a
mean temperature of 75°F (24°C). Insulation shall comply with flame spread rate by
ASTM E84 test methods.
2.4.5 Insulation shall be applied over a heavy coating of special adhesive as recommended
by insulation manufacturer.
2.4.7 Insulation shall be removable and replaceable covers consisting of No. 18 gauge
aluminium sheet metal jacket lined with rigid fibrous glass with a resin binder of a
minimum density of 6 lbs/ft3 (96 Kg/m3) and a maximum K-factor of 0.25
Btu.in/ft2.hr.°F (0.036 W/m. °K). All voids between insulation and pump housing
shall be filled with blanket type fibreglass insulation of 6 lbs/ft3 (96 Kg/m3) density.
2.5.1 The vapour barrier coating shall be tough flexible fire resistive elastomeric finish for
protection of thermal insulation and ultra violet. It shall meet the requirements of
NFPA 90A and 90B and shall be UL classified.
2.5.2 The vapour barrier shall have water vapour permeability not more than 0.02 perms at
0.75 mm dry film thickness when tested to ASTM E96 Method.
2.5.3 When tested for surface burning characteristics (ASTM E84) it shall have a flame
spread rating not exceeding 10 and smoke developed not higher than 15.
2.5.4 The vapour barrier shall be suitable for application by brush or spray. It shall be
applied in 2 coats with heavy duty fire retardant canvas cloth (8 ounce) embedded
between the coats. Canvas overlap at joints shall be at least 50 mm. The wet film
thickness of each coat shall be at least 1.25 mm.
2.5.5 Vapour barrier coating shall be applied above thermal insulation of G.I. Ducts,
chilled water, water supply (hot and cold), refrigeration and condensate drain pipes.
2.6.2 Aluminium cladding shall be applied on top of insulation above the canvas jacket and
vapour barrier coating. It shall be held in place by means of self tapping screws and
by using 38 mm wide aluminium straps at 300 mm centers with aluminium or
stainless steel angle rib clips, all joints shall be sealed with grey coloured suitable
sealant. Rivets and screws shall not be used for cladding unless approved by the
Engineer for use on elbows and fittings. Cladding shall be overlapping at joints,
horizontal seams shall be at the bottom. Cladding on ducts shall be formed in such a
way to allow for rain/dew drain off.
2.6.3 Fabricated 20 gauge aluminium covers shall be used for valves and fittings. The
covers shall be in two sections hinged together and held in place by suitable stainless
steel/aluminium clasps.
2.6.4 Aluminium cladding shall be applied to all insulated pipes (chilled water, condensate
drains, etc.,) and ducts (Galvanised and Pre-insulated) running exposed on roof,
outside building, inside parking floors and in plant rooms.
PART 3 EXECUTION
3.1.1 All insulation shall have a smooth, homogenous and lineable finished surface. All
rigid sections shall be concentric and be accurately matched for thickness.
3.1.2 All surface to be insulated shall be dry and clean, free from loose scale, dirt, oil or
water, when insulation is applied. Clean with suitable solvents such as methylated
spirits or alcohol based solvents. ( refer to manufacturer’s instructions)
3.1.3 Insulation shall be applied in such a manner that air circulation within the insulation
or between the insulation and the pipe shall be avoided.
3.1.4 No surface imperfections in the insulation such as damaged edges, or ends, cracks
and small voids or holes shall be accepted.
3.1.5 Insulation materials shall be stored and protected from weather moisture,
3.1.6 Surface finishes and lagging adhesives shall not be diluted and shall be applied in
accordance with the manufacturer's instructions.
3.1.7 Apply insulation to permit expansion or contraction of metal without causing damage
to insulation or surface finish.
3.2.3 All joints should be butted firmly against each other. No adhesive is required for the
joints (self adhesive system)
3.2.6 Any minor surface cuts should be covered with aluminium foil.
3.2.7 All pipe covering 2 ½" (65 mm) or less in thickness shall be applied in single layer
with joints tightly butted together.
3.2.8 All pipe covering 3" (80 mm) and larger in thickness shall be double layer with
lateral and longitudinal joints of the second layer staggered with those of the first
layer. No canvas is to be used between the layers.
3.2.9 All pipe covering shall fit snugly on the pipe to which it is applied. Inside
circumference of pipe covering when applied shall not vary from the outside
circumference of the pipe by more than 3mm. undersize.
3.2.10 Pipe insulation shall have factory applied jackets and secured with plastic bands at
each joint at center of each section and where sections abut upon fittings, except
where otherwise specified.
3.2.11 Insulation shall only be applied to piping after all testing has been accomplished and
after all the coats of paint have been applied.
3.2.12 Pipe covering shall be terminated at a sufficient distance from all flanges to permit
easy removal of bolts.
3.2.14 All insulated piping not supported on roller hangers and subject to movement, shall
be provided with protection shields at all hanger locations. Shields shall be of 3mm.
galvanized iron extending on each side of the hanger for a distance equal to the
diameter of the insulation and shall extend up the sides of the insulation to the center
of the pipe and shall be provided with cork pad support.
3.2.15 Special care shall be exercised in insulating chilled water lines to prevent sweat leaks
at piping hanger locations.
3.2.16 Where standard insulation shapes are not available, cut, score or meter segmental or
flat block to fit contour of pipe, stagger joints of adjoining segments. Fit insulation
carefully and secure with wire. Smooth with insulating cement.
3.2.17 Adhesives, sealants, vapour barriers, paints, etc., shall meet LEED NC V3
requirements for Volatile Organic Compounds, (VOCs) content limits.
3.3 Finishes
3.3.1.1 All pipes running in concealed spaces shall have canvas cover, securely fixed,
overlaps firmly pasted down, secured with aluminium bands at intervals and painted
with two coats of fire retardant emulsion paint.
3.3.1.2 All non-cladded pipes running inside building but exposed to view shall have same
treatment as for those in concealed spaces but with one coat of gloss paint, to an
approved colour, in addition.
3.3.1.3 Insulation in exposed areas, i.e. permanently visible, shall be protected with
aluminium cladding as specified.
3.4 Installation of Equipment and Duct Insulation
3.4.1 Curved or cylindrical equipment shall be insulated with blocks or curved segments in
one layer for thicknesses of 65 mm or less and two layers for thicknesses of 76 mm or
more. The insulation shall be applied with joints staggered and tightly butted together
and held in place with bands. Square cornered equipment such as boilers, ducts
casings etc. shall be insulated with block insulation protected at corners by
metal shields and held in place by bands, carried around the unit over the insulation
and fastened tight.
Khatib & Alami HVAC Insulation
23 07 00 - 10
October 2021 Smart Square Project
Specifications
3.4.2 Metal anchoring clips shall be welded to the equipment surface so that the band will
pass over them and may be wired to them after insulation is in place.
3.4.3 Insulation in exposed areas, i.e. permanently visible, shall be protected with
aluminium cladding as specified.
3.4.4 Any part of equipment that is normally removable for service such as heads of heat
exchangers, shall be insulated separately from the equipment.
3.4.6 Insulated ducts penetrating walls or floors shall be insulated completely thru
penetration. Provide waterproof calcium silicate insert, same thickness and jacketing
as insulation with wall flange for fire wall or floor penetrations, or as detailed on the
Drawings.
3.4.7 Duct insulation or lining or any type of covering together with the applied adhesives
shall have a flame spread rating not over 25 without evidence of continued
progressive combustion and a smoke developed rating no higher than 50, wherever
the duct crosses a fire wall or penetrates a roof slab.
3.4.8 Duct linings shall be interrupted at fire dampers and fire doors so as not to interfere
with the operation of services.
3.4.9 All duct materials and coverings (insulation, pre-insulated panels, linings, etc.) shall
meet the requirements of NFPA 90A and 90B Standards or equivalent European
Standards.
3.4.10 Adhesives, sealants, vapour barriers, paints, etc., shall meet the requirements of
NFPA 90A and 90B and shall be UL Classified.
END OF SECTION
S.NO SPECS NUMBER ITEM DESCRIPTION PROPOSED MATERIAL BY MANUFACTURER area of application MANUFACTURER MODEL COUNTRY OF ORIGIN
PART 1 GENERAL
1.5
Quality Assurance
PART 2 PRODUCTS
2.1.3
Duct Insulation (Outdoor)
Comply with Drawing title HVAC Miscellaneous Details (2/2) (Insulation and Lagging Detail)
QC-F-Q-012 - Rev. 1
Page 1 of 3
KIMMCO-ISOVER Glass Mineral Wool Acoustic Clean
Liner Blanket (KCL)
24
Density ρ (kg/m3)
(Tolerance: ± 15%)
20.0
Length L (m)
(Tolerance: -0.5%; excess permitted)
ASTM C167
1.2
Width W (m)
(Tolerance: -6mm; + 12mm)
25.0
Thickness T (mm)
(Tolerance: -3mm; excess permitted)
QC-F-Q-012 - Rev. 1
Page 2 of 3
KIMMCO-ISOVER Glass Mineral Wool Acoustic Clean
Liner Blanket (KCL)
Maximum Service
Temperature
Min. - °c -50
Max. (Fiber) +232
ASTM C411
Max. (Facing) +100
No evidence of flaming, glowing,
Temperature Resistance at smoldering, visible smoke or
- -
121 ⁰C delamination, cracking, deformation
or reduction in thickness
Linear Shrinkage - (%) Less than 1 ASTM C356
Color - - Yellow -
Disclaimer: All information and data mentioned in this technical data sheet are based on tests performed in the
laboratory. No thing here into be construed as a warranty or representation and were commend, However, that all
potential users of the product make their own actual tests prior to using it on industrial scale.
-Product Manufactured and supplied by Kuwait Insulating Material Manufacturing Company (KIMMCO)
www.kimmco-isover.com
QC-F-Q-012 - Rev. 1
Page 3 of 3
Company Profile
Company Profile
T
Trustable Insulation
For a Healthy Wellbeing
WE BELIEVE IN
SUSTAINABILITY
FOR THE FUTURE
OF OUR PLANET
We take our environmental responsibility seriously;
developing insulation solutions to protect both the
built environment and the natural environment.
In fact, all KIMMCO-Isover’s manufacturing plants
are certified to the ISO 14001:2015 Environmental
Management System and hold Quality Management
Standard ISO 9001:2015 for manufacturing and ISO
45001:2018 for Occupational health and safety.
Our production capabilities can always fulfill your demand & standards 04
1
WE’RE
THE LEADERS OF
MINERAL WOOL
INSULATION IN GCC
2
OUR PRODUCTION
CAPABILITIES CAN
ALWAYS FULFILL
YOUR DEMAND &
STANDARDS
Over 43 years of expertise in manufacturing and Highly sustainable Stone wool manufacturing
supplying glass wool product to markets in GCC, technology which reduces production wastage to
Asia, Africa and other regions almost Zero
Glass wool is an environment friendly product, KIMMCO-Isover Stone Wool products are made
mainly made from abundantly available sand of volcanic rock – a natural material present in
and recycled glass. KIMMCO-Isover Glass large quantities throughout the Earth. These raw
wool is manufactured in Kuwait using modern materials, natural basalt and dolomite are sensibly
manufacturing technology from ISOVER, Saint- sourced locally in Saudi Arabia. The plant located in
Gobain Yanbu, Saudi Arabia has the latest technology from
Saint-Gobain to produce Stone Wool with a very
Reliable Glass wool products in rolls, slabs and pre-
low environmental impact (zero waste to landfill).
formed pipes with wide range of density, thickness
and facings to provide best thermal, acoustic and Wide range of Stone wool products in slabs, rolls
fire safety solutions in construction and industry and pipe sections forms are produced in different
segment. density and thickness to provide best solution for
safety, efficiency, and thermal & acoustical comfort
in building and industry application.
5
MODERN BUILDINGS
ARE MORE
DEMANDING FOR
PROPER INSULATION
6
PROVIDE
BUILDING WITH
MORE COMFORT
& SAFETY
9
PROVIDE
BUILDING WITH
MORE COMFORT
& SAFETY
Roof Floor
Roof is one of the critical building The floors which separate two different
structure through which nearly 40% levels needs insulation to reduce the
of the heat is gained or lost and this noise impact reaching the floor below.
results in increased energy wastage.
Noise generated by the people walking
It is also important to consider safety
in the floor above or the noise from
of the building while considering
vibrating machines and equipment can
insulation for building.
be isolated using suitable insulation to
create acoustic comfort.
10
ALL INDUSTRIES
ARE LOOKING
FOR EFFICIENCY
Boilers, heaters and vessels
Boilers, heaters, vessels and industrial ovens place
very high demands on insulation systems operating
at high temperatures. While personnel protection
is usually considered in thermal specifications,
economic and sustainable design to improve
efficiency, reducing energy consumption and CO2
emissions often still needs to be adapted. KIMMCO-
Isover supplies flexible, light and efficient range
products that are usable up to 750 °C optimizing
heat loss with less thickness needs when having
space constraints.
13
FIRE SAFETY AND ACOUSTIC
IN INDUSTRIAL APPLICATION
The risk of fire in industrial
environments is much higher than
KIMMCO-Isover mineral wool solutions
are characterized by high longitudinal
CORROSION
in buildings and other applications,
particularly when working with
air-flow resistance (up to >100 kPa·s/
m2) and uniform porosity (93-99%),
PROTECTION
welding and grinding equipment resulting in high sound attenuation
in high temperature environments levels. Highly alloyed austenitic steels (alloys
containing flammable and /or of chrome, nickel and molybdenum) are
Their outstanding performance is a predisposed to tensile stress corrosion (stress
explosive media.
direct result of their elastic properties corrosion cracking), caused mainly by water
KIMMCO-Isover Industrial Insulation and low modulus of elasticity, which soluble ions, such as chlorides. As temperature
Solutions offer gives KIMMCO-Isover mineral wool increases, so does the risk of stress corrosion
solutions a low dynamic toughness, cracking. KIMMCO-Isover industrial products are
Best-in-class fire safety properties,
and makes them superior to other therefore low in chlorides.
Classified in Euroclass Group A
insulants, such as plastic foams.C18
• Will not ignite
• Will not generate smoke or toxic Moisture and water repellence
gases
Low chloride insulation products are the basis
• Will not generate harmful gases for preventing corrosion under insulation (CUI),
Acoustic insulation in this field especially where higher temperature surfaces
therefore has two main objectives: are involved. In addition, KIMMCO-Isover
industrial insulation products for external use
• To protect the hearing of are hydrophobic and non-hygroscopic, thus
personnel working close by. limiting potential water absorption. The open
• Particularly in urban areas, to cell structure allows products to dry out quickly,
reduce ambient sound in the should they become wet, without loss of their
local environment. mechanical or insulating properties.
14
CLIMATIZE
INDOOR SPACES
CAN BE MORE
EFFICIENT AND
COMFORTABLE
Importance of HVAC
thermal Insulation Effective acoustic
Effective thermal insulation ensures that protection
the medium (air or liquid) stays at the
Enjoy your living or working space
right temperature, reducing energy loss
without disturbing noise from HVAC or
throughout the system and preventing
pipe systems with wide range of internal
the risk of condensation.
duct liners for acoustic treatment and
Our solutions achieve significant preformed mineral wool pipe sections.
operating and maintenance cost savings, The products are developed to meet
while also guaranteeing an appropriate the needs of installers and building
level of thermal and acoustical comfort. users, KIMMCO-Isover HVAC insulation
materials actively reduce noise levels, as
KIMMCO-Isover provides the right
well as providing high levels of thermal
solutions, for all HVAC equipment and
and fire protection.
building types:
• Thermal insulation
• Condensation control Effective Fire Protection
• Effective acoustic performance for your HVAC System
• Cost effective solution Fire resistant ducts with KIMMCO-Isover
• Effective Fire Protection are the best way to ensure fire safety in
HVAC installations as the ducts could
• Improved logistics keep their integrity for a given time
period and to not promote flame spread
during a fire.
It is vital to develop safe, durable and
reliable fire protection solutions for
ventilation systems as a fire can easily
spread from the point of origin via
ductwork especially in ventilation and
smoke extraction.
Fire protection of metal duct is the
best way to ensure fire safety of both
ventilation and smoke extraction ducts in
building. KIMMCO-Isover offers solutions
with Stone mineral wool that provides
fire resistance to metal ductwork
while meeting thermal and acoustic
requirements.
17
Indoor Air Quality
The first step in controlling indoor air
pollution is to remove emissions of
pollutants at source. This can be achieved
by paying attention to the ingredients
of materials brought into any living or
working space and, where possible,
choosing healthier alternatives.
KIMMCO-Isover offer range products
and solutions which enhances the Indoor
Air Quality. These products are tested
and certified by international agency like
UL Greenguard. In addition the HVAC
products are tested for non-fungal and
bacterial growth as per international
standards and testing procedures
HVAC insulation solution for all types of duct Plus provide highly efficient thermal insulation,
works prevention of condensation and acoustic
treatment.
External insulation for HVAC Ducts for thermal
efficiency and to reduce risk of condensation Exhaust duct Insulation maintains first safety in
kitchens vents and exhaust ducts
Provides thermal insulation and prevent
condensation on the outside of the metal duct. KIMMCO-Isover Stone wool solutions for
Wide range of products are available with providing fire resistance in kitchen exhaust and
different facings - KDI, KDIP, EDI, EDIP and Self- fire safety applications.
seal for indoor and external metal ducts
18
INNOVATIVE
SOLUTIONS TO
MAKE LIFE BETTER,
EASY AND HEALTHY
The CLIMAVER® pre-insulated ductwork system EcoBuild is already proven through zero phenol-
solution enables you to meet the thermal, acoustic formaldehyde emission certificates, it is the
and fire performance requirements stipulated by latest innovation in terms of performance and
today’s stringent Building Regulations. Sustainably sustainability within the range of glass wool
manufactured from glass mineral wool, the insulation for building application. EcoBuild Mineral
CLIMAVER® insulated panels contains up to 80% wool is Made out of 100% natural resources, its
recycled glass. CLIMAVER® has best in class in performance protects the environment during the
airtightness reducing operational cost and allowing lifetime of a building, with exceptional handling
for optimization of initial HVAC unit design. benefits including superior softer touch and no odor
CLIMAVER® ductworks saves valuable space, reduce It meets the most stringent European requirements,
Installation time and is more cost effective. statutory or voluntary, on emissions of formaldehyde
and VOCs in the indoor air
CLIMAVER® has benefits which sets it apart from
other duct providers as follows: Being non-hazardous to health according to WHO
(World Health Organization), EcoBuild is therefore
• Enhanced Acoustic comfort the ideal solution for building insulation:
• Excellent Fire protection • Natural Product - Made from 100% natural
material
• High Energy Efficiency
• Soft touch & No itch
• Fast Installation
• Odorless
• Light in Weight • Preserves indoor air quality
• Improved Indoor Air Quality and Many more… • Natural Binder
21
INNOVATIVE
SOLUTIONS TO
MAKE LIFE BETTER,
EASY AND HEALTHY
22
TRANSFORM THE
WAY WE BUILD
25
ALL THESE ICONIC PROJECTS AND
MORE, TRUSTED OUR SOLUTIONS
Al Hamra Tower Oman Exhibition & Convention Center Makkah Clock Tower Dubai Metro Khalifa Stadium Masdar City
Kuwait Oman Saudi Arabia Dubai Qatar Abu Dhabi
WE DEVELOP FABRICATORS’ SKILLS
AND LINKING THEM WITH PROJECTS’
CONTRACTORS
www.KIMMCO-ISOVER.com
28
KIMMCO-ISOVER Company Profile October 2020
KIMMCO-ISOVER
www.KIMMCO-ISOVER.com
kimmco@KIMMCO-ISOVER.com
marketing.ki@KIMMCO-ISOVER.com
COUNTRY OF ORIGIN`
Date: 13.09.2021
Ref.: GK/10366/09-21
Country of Origin
We, Kuwait Insulating Material Manufacturing Company (KIMMCO), submit that KIMMCO
Glass wool Insulation products are manufactured in our plant in Kuwait.
Kuwait Insulating Material Manufacturing Co. S.A.K. (C) )ك (م.م.شركة الكويت لصناعة المواد العازلة ش
Head office: P.O.Box 10042 Shuaiba, 65451 Kuwait الكويت65451 منطقة الشعيبة الصناعية10042 .ب. ص:المقر الرئيسي
Paid up Capital: KD 2,650,000 دينار كويتي2,650,000 :رأس المال
Commercial Registration No.: 25470 25470 :رقم السجل التجاري
Tel: +965 2326 2020 Fax: +965 2326 1251 +965 2326 1251 : فاكس+965 2326 2020 :هاتف
email: kimmco@kimmco-isover.com kimmco@kimmco-isover.com :البريد اإللكتروني
Website: www.kimmco-isover.com www.kimmco-isover.com:الموقع اإللكتروني
WARRANTY LETTER AND CERTIFICATES
Date: 21.03.2021
Ref.: GK/10115/03-21
Warranty Certificate
Kuwait Insulating Material Manufacturing Co. S.A.K. (C) (ك )م.م.ﺷرﻛﺔ اﻟﻛوﯾت ﻟﺻﻧﺎﻋﺔ اﻟﻣواد اﻟﻌﺎزﻟﺔ ش
Head office: P.O.Box 10042 Shuaiba, 65451 Kuwait اﻟﻛوﯾت65451 ﻣﻧطﻘﺔ اﻟﺷﻌﯾﺑﺔ اﻟﺻﻧﺎﻋﯾﺔ10042 .ب. ص:اﻟﻣﻘر اﻟرﺋﯾﺳﻲ
Paid up Capital: KD 2,650,000 دﯾﻧﺎر ﻛوﯾﺗﻲ2,650,000 :رأس اﻟﻣﺎل
Commercial Registration No.: 25470 25470 :رﻗم اﻟﺳﺟل اﻟﺗﺟﺎري
Tel: +965 2326 2020 Fax: +965 2326 1251 +965 2326 1251 : ﻓﺎﻛس+965 2326 2020 :ھﺎﺗف
email: kimmco@kimmco-isover.com kimmco@kimmco-isover.com :اﻟﺑرﯾد اﻹﻟﻛﺗروﻧﻲ
Website: www.kimmco-isover.com www.kimmco-isover.com:اﻟﻣوﻗﻊ اﻹﻟﻛﺗروﻧﻲ
CERTIFICATE
OF COMPLIANCE
132766-420
Kuwait Insulating Certificate Number
Blanket
UL 2818 - 2013 Gold Standard for Chemical Emissions for Building Materials, Finishes and Furnishings
Product tested in accordance with UL 2821 test method to show compliance to emission limits on UL 2818. Section 7.1 and 7.2.
UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively
“Agreement”). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report, in accordance with the terms of the Agreement. This Certificate is valid for the identified
dates unless there is non-compliance with the Agreement.
GREENGUARD Gold Certification Criteria for Building Products and Interior Finishes
Maximum Allowable
Criteria CAS Number Predicted Concentration Units
TVOC (A) - 0.22 mg/m³
Formaldehyde 50-00-0 9 (7.3 ppb) µg/m³
Total Aldehydes (B) - 0.043 ppm
4-Phenylcyclohexene 4994-16-5 6.5 µg/m³
Particle Matter less than 10 µm (C) - 20 µg/m³
1-Methyl-2-pyrrolidinone (D) 872-50-4 160 µg/m³
1/2 CREL
Individual VOCs (E) - or -
1/100th TLV
(A) Defined to be the total response of measured VOCs falling within the C6 – C16 range, with responses calibrated to a toluene surrogate. Maximum
allowable predicted TVOC concentrations for GREENGUARD Gold (0.22 mg/m ³) fall in the range of 0.5 mg/m³ or less, as specified in CDPH Standard
Method v1.2.
(B) The sum of all measured normal aldehydes from formaldehyde through nonanal, plus benzaldehyde, individually calibrated to a compound specific
standard. Heptanal through nonanal are measured via TD/GC/MS analysis and the remaining aldehydes are measured using HPLC/UV analysis.
(C) Particle emission requirement only applicable to HVAC Duct Products with exposed surface area in air streams (a forced air test with specific test
method) and for wood finishing (sanding) systems.
(D) Based on the CA Prop 65 Maximum Allowable Dose Level for inhalation of 3,200 ʅg/day and an inhalation rate of 20 m³/day
(E) Allowable levels for chemicals not listed are derived from the lower of 1/2 the California Office of Environmental Health Hazard Assessment (OEHHA)
Chronic Reference Exposure Level (CREL) as required per the CDPH/EHLB/Standard Method v1.2 and BIFMA level credit 7.6.2 and 1/100th of the
Threshold Limit Value (TLV) industrial work place standard (Reference: American Conference of Government Industrial Hygienists, 6500 Glenway,
Building D-7, and Cincinnati, OH 45211-4438).
UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively
“Agreement”). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report, in accordance with the terms of the Agreement. This Certificate is valid for the identified
dates unless there is non-compliance with the Agreement.
CERTIFICATE
OF COMPLIANCE
132767-420
Kuwait Insulating Certificate Number
UL 2818 - 2013 Gold Standard for Chemical Emissions for Building Materials, Finishes and Furnishings
Product tested in accordance with UL 2821 test method to show compliance to emission limits on UL 2818. Section 7.1 and 7.2.
UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively
“Agreement”). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report, in accordance with the terms of the Agreement. This Certificate is valid for the identified
dates unless there is non-compliance with the Agreement.
GREENGUARD Gold Certification Criteria for Building Products and Interior Finishes
Maximum Allowable
Criteria CAS Number Predicted Concentration Units
TVOC (A) - 0.22 mg/m³
Formaldehyde 50-00-0 9 (7.3 ppb) µg/m³
Total Aldehydes (B) - 0.043 ppm
4-Phenylcyclohexene 4994-16-5 6.5 µg/m³
Particle Matter less than 10 µm (C) - 20 µg/m³
1-Methyl-2-pyrrolidinone (D) 872-50-4 160 µg/m³
1/2 CREL
Individual VOCs (E) - or -
1/100th TLV
(A) Defined to be the total response of measured VOCs falling within the C6 – C16 range, with responses calibrated to a toluene surrogate. Maximum
allowable predicted TVOC concentrations for GREENGUARD Gold (0.22 mg/m ³) fall in the range of 0.5 mg/m³ or less, as specified in CDPH Standard
Method v1.2.
(B) The sum of all measured normal aldehydes from formaldehyde through nonanal, plus benzaldehyde, individually calibrated to a compound specific
standard. Heptanal through nonanal are measured via TD/GC/MS analysis and the remaining aldehydes are measured using HPLC/UV analysis.
(C) Particle emission requirement only applicable to HVAC Duct Products with exposed surface area in air streams (a forced air test with specific test
method) and for wood finishing (sanding) systems.
(D) Based on the CA Prop 65 Maximum Allowable Dose Level for inhalation of 3,200 ʅg/day and an inhalation rate of 20 m³/day
(E) Allowable levels for chemicals not listed are derived from the lower of 1/2 the California Office of Environmental Health Hazard Assessment (OEHHA)
Chronic Reference Exposure Level (CREL) as required per the CDPH/EHLB/Standard Method v1.2 and BIFMA level credit 7.6.2 and 1/100th of the
Threshold Limit Value (TLV) industrial work place standard (Reference: American Conference of Government Industrial Hygienists, 6500 Glenway,
Building D-7, and Cincinnati, OH 45211-4438).
UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively
“Agreement”). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report, in accordance with the terms of the Agreement. This Certificate is valid for the identified
dates unless there is non-compliance with the Agreement.
Project Approvals
& References
Project Approvals
& References
SAMPLE TAG
STC Square Project
EMPLOYER ENGINEER CONTRACTOR
SAMPLE
Sample Description :
DUCT WORKS /KIMMCO
1 of 1
BEC
Manufacturer : KIMMCO/ Fawaz Ref. & AC Contracting L.L.C.
Submitted By:
Name : Eng. Adel Morsy
Signature :
Date : 11/2/2022
Approval Status: :
Approved By :
SC
Name: :
Signature :
Date :