Supply for small power,


Cable laying method; lights of EMSB room B,
1. Non armoured single core cable in duct buried in the ground. generators, charger/
2. At maximum depth of 0.5m. heater etc.
3. Ducts are touching. FOR THE CONNECTION
4. Thermal resistivity of soil is 2.5 Km/W. OF LOAD BANK
6Y.500 Y.6
85m length 10m length
EMSB-1F-A2 SPARE SPARE
FORM 3b
IP42
CL : 1233kW 4 NOS. 2000/5A 4 NOS. 2250/5A
DL : 1233kW CL5P20 20VA CL5P20 20VA ZCT
PF : 0.92 DTL DTL
2000AT/2000AF 2250AT/2500AF 32AT/100AF 32AT/100AF 32AT/100AF
ACB/4P ACB/4P MCCB/4P MCCB/4P MCCB/4P
WITHDRAWABLE (36kA) (36kA) (36kA) (36kA)
LSI TYPE
(36kA)
2500A TIN PLATED COPPER BUSBAR
36kA @ 1SEC
CT 2250/5A CT 2250/5A
CLASS 1 5VA CLASS 1 5VA
4 NOS. 2250/5A 4 NOS. 2250/5A
CL5P20 20VA IDMTL DTL DTL IDMTL CL5P20 20VA
2250AT/2500AF 2250AT/2500AF
ACB/4P (36KA) M&E ACB/4P (36KA)
MOTORIZED MOTORIZED
WITHDRAWABLE WITHDRAWABLE
LSI TYPE LSI TYPE
2A 2A
STATUS TO AMF TO DPM
7Cx2.5mm2 Cu/PVC CABLE B Y R 2A
2A 315A gG
TO DPM HRC FUSE
B Y R 2A SPD TYPE 1
Up<1.5kV
N 3P+N
TN-S EARTHING Iimp=25kA (L-N)
E
100kA (N-PE)
Cable laying method;
Cable laying method;
1. Non armoured single core cable in duct buried in the ground.
6Z.500 6W.500 1. Non armoured single core cable in duct buried in the ground.
2. At maximum depth of 0.5m.
20m length 20m length 2. At maximum depth of 0.5m.
3. Ducts are touching.
3. Ducts are touching.
4. Thermal resistivity of soil is 2.5 Km/W.
4. Thermal resistivity of soil is 2.5 Km/W.
1500kVA 2250AT/2500AF GENERATOR
33kV/415V-240V ACB/4P SET MOUNT
6.5% IMPEDANCE (36KA) BREAKER
OIL TYPE LSI TYPE
TRANSFORMER-1F-A2
1600kVA
G 415/240V
CONTINUOUS RATED
GENSET-1F-A2
SINGLE LINE D
FROM 33kV RMU