RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV1-MDB1 Location: U-HUB TYPE 4 FEEDER PHASE 4-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 4x1C 300 mm² LS0H
Supplied From: TR1 Volts: 400/230
No. of 3P Ways: 10 Phase: 3 CABLE
LENGTH
Incoming Device Rating: 2500AT/2500AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 288.29

L2/1 FP-RA1-1-1 Radial A 2 4C 185 185 MCCB 400 3 0 0 0 0 288.29

L3/1 288.29

L1/2 288.29

L2/2 FP-RA1-1-2 Radial A 2 4C 185 185 MCCB 400 3 0 0 0 0 288.29

L3/2 288.29

L1/3 288.29

L2/3 FP-RA1-2-1 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 288.29

L3/3 288.29

L1/4 288.29

L2/4 FP-RA1-2-2 Radial A 2 4C 95 95 MCCB 400 3 0 0 0 0 288.29

L3/4 288.29

L1/5 288.29

L2/5 FP-RA1-3-1 Radial A 1 4C 185 95 MCCB 400 3 0 0 0 0 288.29

L3/5 288.29

L1/6 288.29

L2/6 FP-RA1-3-2 Radial A 1 4C 185 95 MCCB 400 3 0 0 0 0 288.29

L3/6 288.29

L1/7 288.29

L2/7 FP-RA1-4-1 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 288.29

L3/7 288.29

L1/8

L2/8 PFC-1, 500 KVAR Radial A 2 4C 300 300 ACB 1000 3 22 0 0 0

L3/8

L1/9

L2/9 SPARE MCCB 400 3

L3/9

L1/10

L2/10 SPACE

L3/10

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 2018.06 2018.06 2018.06

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 464.15 464.15 464.15

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 1113.97

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 1392.46
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV1-MDB2 Location: U-HUB TYPE 4 FEEDER PHASE 4-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 4x1C 300 mm² LS0H
Supplied From: TR2 Volts: 400/230
No. of 3P Ways: 11 Phase: 3 CABLE
LENGTH
Incoming Device Rating: 2500AT/2500AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

ACB 2500 3 21 0.15 0.40 0.40 2018.06 2018.06 2018.06

L1/1 288.29

L2/1 FP-RA1-4-2 Radial A 2 4C 120 120 MCCB 400 3 0 0 0 0 288.29

L3/1 288.29

L1/2 288.29

L2/2 FP-RA1-5-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 288.29

L3/2 288.29

L1/3 288.29

L2/3 FP-RA1-5-2 Radial A 1 4C 185 95 MCCB 400 3 0 0 0 0 288.29

L3/3 288.29

L1/4 288.29

L2/4 FP-RA1-6-1 Radial A 2 4C 185 185 MCCB 400 3 0 0 0 0 288.29

L3/4 288.29

L1/5 288.29

L2/5 FP-RA1-6-2 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 288.29

L3/5 288.29

L1/6 288.29

L2/6 FP-RA1-7-1 Radial A 2 4C 120 120 MCCB 400 3 0 0 0 0 288.29

L3/6 288.29

L1/7 288.29

L2/7 FP-RA1-7-2 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 288.29

L3/7 288.29

L1/8

L2/8 PFC-1, 500 KVAR Radial A 2 4C 300 300 ACB 1000 3 18 0 0 0

L3/8

L1/9

L2/9 SPARE MCCB 400 3

L3/9

L1/10

L2/10 SPARE MCCB 400 3

L3/10

L1/11

L2/11 SPACE

L3/11

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 2018.06 2018.06 2018.06

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 464.15 464.15 464.15

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 1113.97

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 1392.46
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV1-MDB3 Location: U-HUB TYPE 4 FEEDER PHASE 4-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 4x1C 300 mm² LS0H
Supplied From: TR2 Volts: 400/230

No. of 3P Ways: 14 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 2500AT/2500AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 288.29

L2/1 FP-RA1-8-1 Radial A 3 4C 150 150 MCCB 400 3 0 0 0 0 288.29

L3/1 288.29

L1/2 288.29

L2/2 FP-RA1-8-2 Radial A 2 4C 185 185 MCCB 400 3 0 0 0 0 288.29

L3/2 288.29

L1/3 288.29

L2/3 FP-RA1-9-1 Radial A 2 4C 185 185 MCCB 400 3 0 0 0 0 288.29

L3/3 288.29

L1/4 288.29

L2/4 FP-RA1-9-2 Radial A 2 4C 120 120 MCCB 400 3 0 0 0 0 288.29

L3/4 288.29

L1/5 288.29

L2/5 FP-RA1-10-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 288.29

L3/5 288.29

L1/6 288.29

L2/6 FP-RA1-10-2 Radial A 1 4C 150 95 MCCB 400 3 0 0 0 0 288.29

L3/6 288.29

L1/7 288.29

L2/7 FP-RA1-10-3 Radial A 1 4C 150 95 MCCB 400 3 0 0 0 0 288.29

L3/7 288.29

L1/8 0.00

L2/8 PFC-1, 500 KVAR Radial A 2 4C 300 300 ACB 1000 3 11 0 0 0 0.00

L3/8 0.00

L1/9 0.00

L2/9 Gen panel/ESMDB-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 0.00

L3/9 0.00

L1/10 2018.06

L2/10 Gen panel/ESMDB-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 2018.06

L3/10 2018.06

L1/11 288.29

L2/11 MCC-CWP-EV1 Radial A 1 4C 150 70 MCCB 320 3 0 0 0 0 288.29

L3/11 288.29

L1/12 7.38

L2/12 SMDB-1 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 7.38

L3/12 7.38

L1/13

L2/13 SPARE MCCB 400 3

L3/13

L1/14

L2/14 SPACE

L3/14

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 4331.80 4331.80 4331.80

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 996.31 996.31 996.31

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 2391.15

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 2988.94
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-MV1-MDB1 Location: U-HUB TYPE 3 FEEDER PHASE 4-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 4x1C 300 mm² LS0H
Supplied From: TR1 Volts: 400/230

No. of 3P Ways: 9 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 2500AT/2500AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 245.81

L2/1 FP-RA2-1 Radial A 1 4C 185 95 MCCB 400 3 0 0 0 0 245.81

L3/1 245.81

L1/2 245.81

L2/2 FP-RA2-2 Radial A 1 4C 150 70 MCCB 400 3 0 0 0 0 245.81

L3/2 245.81

L1/3 245.81

L2/3 FP-RA2-3 Radial A 1 4C 95 50 MCCB 400 3 0 0 0 0 245.81

L3/3 245.81

L1/4 245.81

L2/4 FP-RA2-7 Radial A 2 4C 120 120 MCCB 400 3 0 0 0 0 245.81

L3/4 245.81

L1/5 245.81

L2/5 FP-RA2-4 Radial A 2 4C 95 50 MCCB 400 3 0 0 0 0 245.81

L3/5 245.81

L1/6 245.81

L2/6 FP-RA2-8 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 245.81

L3/6 245.81

L1/7 0.00

L2/7 PFC-1,500 KVAR Radial A 2 4C 300 300 ACB 1000 3 18 0 0 0 0.00

L3/7 0.00

L1/8

L2/8 SPARE MCCB 400 3 0.00

L3/8 0.00

L1/9

L2/9 SPACE 0.00

L3/9 0.00

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 1474.86 1474.86 1474.86

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 339.22 339.22 339.22

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 814.12

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 1017.65
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-MV1-MDB2 Location: U-HUB TYPE 3 FEEDER PHASE 4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 4x1C 300 mm² LS0H
Supplied From: TR2 Volts: 400/230

No. of 3P Ways: 12 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 2500AT/2500AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 245.81

L2/1 FP-RA2-5 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 245.81

L3/1 245.81

L1/2 245.81

L2/2 FP-RA2-9 Radial A 1 4C 185 95 MCCB 400 3 0 0 0 0 245.81

L3/2 245.81

L1/3 245.81

L2/3 FP-RA2-6 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 245.81

L3/3 245.81

L1/4 245.81

L2/4 FP-RA2-10 Radial A 1 4C 120 70 MCCB 400 3 0 0 0 0 245.81

L3/4 245.81

L1/5 0.00

L2/5 FP-RA2-11 Radial A 1 4C 95 50 MCCB 225 3 0 0 0 0 0.00

L3/5 0.00

L1/6 0.00

L2/6 FP-RA2-12 Radial A 1 4C 95 50 MCCB 225 3 0 0 0 0 0.00

L3/6 0.00

L1/7 0.00

L2/7 PFC--2, 500 KVAR Radial A 2 4C 300 300 ACB 1000 3 14 0 0 0 0.00

L3/7 0.00

L1/8 50.02

L2/8 Gen panel/ESMDB-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 50.02

L3/8 50.02

L1/9 139.39

L2/9 MCC-CWP-MV1 Radial A 1 4C 95 50 MCCB 225 3 0 0 0 0 139.39

L3/9 139.39

L1/10 12.51

L2/10 SMDB-1 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 12.51

L3/10 12.51

L1/11

L2/11 SPARE MCCB 400 3 0.00

L3/11 0.00

L1/12

L2/12 SPACE

L3/12

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 1185.15 1185.15 1185.15

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 272.59 272.59 272.59

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 654.21

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 817.76
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-MV4-MDB1 Location: U-HUB TYPE 3 FEEDER PHASE 4-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 4x1C 300 mm² LS0H
Supplied From: TR1 Volts: 400/230

No. of 3P Ways: 8 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 2500AT/2500AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 225.58

L2/1 FP-COM-001 Radial A 1 4C 120 70 MCCB 320 3 0 0 0 0 225.58

L3/1 225.58

L1/2 345.95

L2/2 FP-COH-001 Radial A 1 4C 240 120 MCCB 500 3 0 0 0 0 0.00 345.95

L3/2 345.95

L1/3 345.95

L2/3 FP-COE-001 Radial A 2 4C 185 185 MCCB 500 3 0 0 0 0 345.95

L3/3 345.95

L1/4 345.95

L2/4 FP-COE-002 Radial A 2 4C 185 185 MCCB 500 3 0 0 0 0 345.95

L3/4 345.95

L1/5 0.00

L2/5 PFC-1, 500 KVAR Radial A 2 4C 300 300 ACB 1000 3 18 0 0 0 0.00

L3/5 0.00

L1/6 225.58

L2/6 FP-COM-002 Radial A 1 4C 120 70 MCCB 320 3 0 0 0 0 225.58

L3/6 225.58

L1/7 0.00

L2/7 SPARE MCCB 500 3 0.00

L3/7 0.00

L1/8 50.02

L2/8 SPACE 50.02

L3/8 50.02

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 1539.03 1539.03 1539.03

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 353.98 353.98 353.98

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 849.55

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 1061.93
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-MV4-MDB2 Location: U-HUB TYPE 3 FEEDER PHASE 2-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 2x1C 300 mm² LS0H
Supplied From: TR2 Volts: 400/230

No. of 3P Ways: 11 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 1600AT/1600AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b


Tabulated Voltage Cummulative,
Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 462.43

L2/1 IPF Radial A 2 4C 240 240 ACB 1000 3 0 0 0 0 462.43

L3/1 462.43

L1/2 144.51

L2/2 FP-IPS Radial A 1 4C 120 70 MCCB 225 4 0 0 0 0 144.51

L3/2 144.51

L1/3 187.28

L2/3 FP-PCP Radial A 2 4C 240 240 MCCB 250 5 0 0 0 0 187.28

L3/3 187.28

L1/4 225.58

L2/4 FP-COM-003 Radial A 1 4C 185 95 MCCB 320 6 0 0 0 0 225.58

L3/4 225.58

L1/5 0.00

L2/5 PFC-2, 350 KVAR Radial A 2 4C 300 300 ACB 1000 7 14 0 0 0 0.00

L3/5 0.00

L1/6 50.02

L2/6 Gen panel/ESMDB-1 Radial A 1 4C 240 120 MCCB 400 8 0 0 0 0 50.02

L3/6 50.02

L1/7 360.10

L2/7 MCC-CWP-MV4 Radial A 1 4C 300 150 MCCB 500 14 0 0 0 0 360.10

L3/7 360.10

L1/8 12.51

L2/8 SMDB-1 Radial A 1 4C 25 16 MCCB 125 20 0 0 0 0 12.51

L3/8 12.51

L1/9

L2/9 SPARE MCCB 500 3 0.00

L3/9 0.00

L1/10

L2/10 SPARE MCCB 250 3 0.00

L3/10 0.00

L1/11

L2/11 0.00

L3/11 0.00

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 1442.43 1442.43 1442.43

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 331.76 331.76 331.76

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 796.22

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 995.27
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV17-MDB1 Location: U-HUB TYPE 3 FEEDER PHASE 2-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 2x1C 300 mm² LS0H
Supplied From: TR1 Volts: 400/230

No. of 3P Ways: 6 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 1600AT/1600AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 527.17

L2/1 FP-RAO-1 Radial A 2 4C 120 120 ACB 800 3 0 0 0 0 527.17

L3/1 527.17

L1/2 527.17

L2/2 FP-RAO-2 Radial A 2 4C 120 120 ACB 800 3 0 0 0 0 527.17

L3/2 527.17

L1/3 316.47

L2/3 FP-RZ1-1 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 316.47

L3/3 316.47

L1/4 0.00

L2/4 PFC-1, 350 KVAR Radial A 2 4C 150 150 MCCB 630 3 18 0 0 0 0.00

L3/4 0.00

L1/5

L2/5 SPARE ACB 800 3 0.00

L3/5 0.00

L1/6

L2/6 SPACE 0.00

L3/6 0.00

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 1370.81 1370.81 1370.81

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 315.29 315.29 315.29

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 756.69

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 945.86
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV17-MDB2 Location: U-HUB TYPE 3 FEEDER PHASE 2-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 2x1C 300 mm² LS0H
Supplied From: TR2 Volts: 400/230

No. of 3P Ways: 9 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 1600AT/1600AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 527.17

L2/1 FP-RAO-3 Radial A 2 4C 120 120 ACB 800 3 0 0 0 0 527.17

L3/1 527.17

L1/2 316.47

L2/2 FP-RZ1-2 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 316.47

L3/2 316.47

L1/3 316.47

L2/3 FP-RZ1-3 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 316.47

L3/3 316.47

L1/4 0.00

L2/4 PFC-2, 350 KVAR Radial A 2 4C 150 150 MCCB 630 3 14 0 0 0 0.00

L3/4 0.00

L1/5 50.02

L2/5 Gen panel/ESMDB-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 50.02

L3/5 50.02

L1/6 87.15

L2/6 MCC-CWP-EV17 Radial A 1 4C 35 25 MCCB 125 3 0 0 0 0 87.15

L3/6 87.15

L1/7 12.51

L2/7 SMDB-1 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 12.51

L3/7 12.51

L1/8

L2/8 SPARE MCCB 400 3 0.00

L3/8 0.00

L1/9

L2/9 SPACE 0.00

L3/9 0.00

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 1309.79 1309.79 1309.79

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 301.25 301.25 301.25

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 723.01

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 903.76
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV13-MDB1 Location: U-HUB TYPE 3 FEEDER PHASE 2-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 2x1C 300 mm² LS0H
Supplied From: TR1 Volts: 400/230

No. of 3P Ways: 7 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 1600AT/1600AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 316.47

L2/1 FP-RZ2-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 316.47

L3/1 316.47

L1/2 316.47

L2/2 FP-RZ2-2 Radial A 2 4C 185 185 MCCB 400 3 0 0 0 0 316.47

L3/2 316.47

L1/3 316.47

L2/3 FP-RZ2-3 Radial A 2 4C 185 185 MCCB 400 3 0 0 0 0 316.47

L3/3 316.47

L1/4 300.58

L2/4 FP-P_C Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 300.58

L3/4 300.58

L1/5 0.00

L2/5 PFC-1, 350 KVAR Radial A 2 4C 150 150 MCCB 630 3 18 0 0 0 0.00

L3/5 0.00

L1/6 87.15

L2/6 SPARE MCCB 400 3 87.15

L3/6 87.15

L1/7 12.51

L2/7 SPACE 12.51

L3/7 12.51

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 1349.66 1349.66 1349.66

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 310.42 310.42 310.42

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 745.01

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 931.27
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV13-MDB2 Location: U-HUB TYPE 3 FEEDER PHASE 2-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 2x1C 300 mm² LS0H
Supplied From: TR2 Volts: 400/230

No. of 3P Ways: 9 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 1600AT/1600AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 316.47

L2/1 FP-RZ2-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 316.47

L3/1 316.47

L1/2 316.47

L2/2 FP-RZ2-2 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 316.47

L3/2 316.47

L1/3 316.47

L2/3 FP-RZ2-3 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 316.47

L3/3 316.47

L1/4 0.00

L2/4 PFC-2, 350 KVAR Radial A 2 4C 150 150 MCCB 630 3 14 0 0 0 0.00

L3/4 0.00

L1/5 50.02

L2/5 Gen panel/ESMDB-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 50.02

L3/5 50.02

L1/6 168.42

L2/6 MCC-CWP-EV13 Radial A 1 4C 95 50 MCCB 250 3 0 0 0 0 168.42

L3/6 168.42

L1/7 12.51

L2/7 SMDB-1 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 12.51

L3/7 12.51

L1/8

L2/8 SPARE MCCB 400 3 0.00

L3/8 0.00

L1/9

L2/9 SPACE 0.00

L3/9 0.00

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 1180.37 1180.37 1180.37

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 271.49 271.49 271.49

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 651.57

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 814.46
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV24-MDB1 Location: U-HUB TYPE 3 FEEDER PHASE 2-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 2x1C 300 mm² LS0H
Supplied From: TR1 Volts: 400/230

No. of 3P Ways: 6 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 1600AT/1600AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 316.47

L2/1 FP-RZ2-1 Radial A 2 4C 120 120 MCCB 400 3 0 0 0 0 316.47

L3/1 316.47

L1/2 316.47

L2/2 FP-RZ2-2 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 316.47

L3/2 316.47

L1/3 316.47

L2/3 FP-RZ2-3 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 316.47

L3/3 316.47

L1/4 0.00

L2/4 PFC-1, 350 KVAR Radial A 2 4C 150 150 MCCB 630 3 18 0 0 0 0.00

L3/4 0.00

L1/5

L2/5 SPARE MCCB 400 3 0.00

L3/5 0.00

L1/6

L2/6 SPACE 0.00

L3/6 0.00

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 0.00 949.42 949.42

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 0.00 218.37 218.37

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 349.39

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 436.73
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV24-MDB2 Location: U-HUB TYPE 3 FEEDER PHASE 2-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 2x1C 300 mm² LS0H
Supplied From: TR2 Volts: 400/230
No. of 3P Ways: 10 Phase: 3 CABLE
LENGTH
Incoming Device Rating: 1600AT/1600AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 316.47

L2/1 FP-RZ2-4 Radial A 2 4C 150 150 MCCB 400 3 0 0 0 0 316.47

L3/1 316.47

L1/2 316.47

L2/2 FP-RZ2-5 Radial A 2 4C 240 240 MCCB 400 3 0 0 0 0 316.47

L3/2 316.47

L1/3 316.47

L2/3 FP-RZ2-6 Radial A 2 4C 240 240 MCCB 400 3 0 0 0 0 316.47

L3/3 316.47

L1/4 23.12

L2/4 PS SEWERAGE Radial A 1 4C 25 16 MCCB 63 3 0 0 0 0 23.12

L3/4 23.12

L1/5 0.00

L2/5 PFC-2, 350 KVAR Radial A 2 4C 150 150 MCCB 630 3 14 0 0 0 0.00

L3/5 0.00

L1/6 50.02

L2/6 Gen panel/ESMDB-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 50.02

L3/6 50.02

L1/7 126.61

L2/7 MCC-CWP-EV24 Radial A 1 4C 50 25 MCCB 160 3 0 0 0 0 126.61

L3/7 126.61

L1/8 12.51

L2/8 SMDB-1 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 12.51

L3/8 12.51

L1/9

L2/9 SPARE MCCB 400 3

L3/9

L1/10

L2/10 SPACE

L3/10

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 0.00 1161.68 1161.68

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 0.00 267.19 267.19

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 427.50

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 534.37
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV21-MDB1 Location: U-HUB TYPE 3 FEEDER PHASE 4-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 4x1C 300 mm² LS0H
Supplied From: TR1 Volts: 400/230

No. of 3P Ways: 17 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 2500AT/2500AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 316.47

L2/1 FP-RZ2-1 Radial A 2 4C 240 240 MCCB 400 3 0 0 0 0 316.47

L3/1 316.47

L1/2 316.47

L2/2 FP-RZ2-2 Radial A 2 4C 240 240 MCCB 400 3 0 0 0 0 316.47

L3/2 316.47

L1/3 300.58

L2/3 FP-P_C Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 300.58

L3/3 300.58

L1/4 127.46

L2/4 FP-PMJ Radial A 1 4C 70 35 MCCB 225 3 0 0 0 0 127.46

L3/4 127.46

L1/5 69.54

L2/5 FP-CNN-1 Radial A 1 4C 240 120 MCCB 125 3 0 0 0 0 69.54

L3/5 69.54

L1/6 69.54

L2/6 FP-CNN-2 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 69.54

L3/6 69.54

L1/7 69.54

L2/7 FP-CNN-3 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 69.54

L3/7 69.54

L1/8 69.54

L2/8 FP-CNN-4 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 69.54

L3/8 69.54

L1/9 316.47

L2/9 FP-RZ2-1 Radial A 2 4C 240 240 MCCB 400 3 0 0 0 0 316.47

L3/9 316.47

L1/10 0.00

L2/10 PFC-1, 500 KVAR Radial A 2 4C 300 300 ACB 1000 3 18 0 0 0 0.00

L3/10 0.00

L1/11 50.02

L2/11 Gen panel/ESMDB-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 50.02

L3/11 50.02

L1/12 214.93

L2/12 MCC-CWP-EV21 Radial A 1 4C 150 70 MCCB 320 3 0 0 0 0 214.93

L3/12 214.93

L1/13 12.51

L2/13 SMDB-1 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 12.51

L3/13 12.51

L1/14

L2/14 SPARE MCCB 400 3

L3/14

L1/15

L2/15 SPARE MCCB 125 3

L3/15

L1/16

L2/16 SPACE

L3/16

L1/17

L2/17 SPACE

L3/17

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 0.00 1933.10 1933.10

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 0.00 444.61 444.61

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 711.38

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 889.23
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV21-MDB2 Location: U-HUB TYPE 3 FEEDER PHASE 2-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 2x1C 300 mm² LS0H
Supplied From: TR2 Volts: 400/230

No. of 3P Ways: 6 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 1600AT/1600AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 316.47

L2/1 FP-RZ2-2 Radial A 2 4C 240 240 MCCB 400 3 0 0 0 0 316.47

L3/1 316.47

L1/2 316.47

L2/2 FP-RZ2-3 Radial A 2 4C 240 240 MCCB 400 3 0 0 0 0 316.47

L3/2 316.47

L1/3 300.58

L2/3 FP-P_C Radial A 2 4C 120 120 MCCB 400 3 0 0 0 0 300.58

L3/3 300.58

L1/4 0.00

L2/4 PFC-2, 350 KVAR Radial A 2 4C 150 150 MCCB 630 3 14 0 0 0 0.00

L3/4 0.00

L1/5 69.54

L2/5 SPARE MCCB 400 3 69.54

L3/5 69.54

L1/6 69.54

L2/6 SPACE 69.54

L3/6 69.54

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 0.00 1072.62 1072.62

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 0.00 246.70 246.70

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 394.72

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 493.40
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV14-MDB1 Location: U-HUB TYPE 3 FEEDER PHASE 4-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 4x1C 300 mm² LS0H
Supplied From: TR1 Volts: 400/230

No. of 3P Ways: 7 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 2500AT/2500AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 316.47

L2/1 FP-RZ2-1 Radial A 1 4C 95 50 MCCB 400 3 0 0 0 0 316.47

L3/1 316.47

L1/2 316.47

L2/2 FP-RZ2-2 Radial A 2 4C 120 120 MCCB 400 3 0 0 0 0 316.47

L3/2 316.47

L1/3 316.47

L2/3 FP-RZ2-3 Radial A 1 4C 150 70 MCCB 400 3 0 0 0 0 316.47

L3/3 316.47

L1/4 316.47

L2/4 FP-RZ2-4 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 316.47

L3/4 316.47

L1/5 0.00

L2/5 PFC-1, 500 KVAR Radial A 2 4C 300 300 ACB 1000 3 18 0 0 0 0.00

L3/5 0.00

L1/6

L2/6 SPARE MCCB 400 3 0.00

L3/6 0.00

L1/7

L2/7 SPACE 0.00

L3/7 0.00

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 0.00 1265.90 1265.90

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 0.00 291.16 291.16

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 465.85

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 582.31
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV14-MDB2 Location: U-HUB TYPE 3 FEEDER PHASE 4-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 4x1C 300 mm² LS0H
Supplied From: TR2 Volts: 400/230

No. of 3P Ways: 11 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 2500AT/2500AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b


Tabulated Voltage Cummulative,
Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 316.47

L2/1 FP-RZ2-5 Radial A 1 4C 185 95 MCCB 400 3 0 0 0 0 316.47

L3/1 316.47

L1/2 316.47

L2/2 FP-RZ2-6 Radial A 2 4C 240 240 MCCB 400 3 0 0 0 0 316.47

L3/2 316.47

L1/3 316.47

L2/3 FP-RZ2-7 Radial A 2 4C 240 240 MCCB 400 3 0 0 0 0 316.47

L3/3 316.47

L1/4 316.47

L2/4 FP-RZ2-8 Radial A 3 4C 185 185 MCCB 400 3 0 0 0 0 316.47

L3/4 316.47

L1/5 316.47

L2/5 FP-RZ2-9 Radial A 3 4C 240 240 MCCB 400 3 0 0 0 0 316.47

L3/5 316.47

L1/6 0.00

L2/6 PFC-2, 500 KVAR Radial A 2 4C 300 300 ACB 1000 3 14 0 0 0 0.00

L3/6 0.00

L1/7 50.02

L2/7 Gen panel/ESMDB-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 50.02

L3/7 50.02

L1/8 304.95

L2/8 MCC-CWP-EV14 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 304.95

L3/8 76.55 304.95

L1/9 12.51

L2/9 SMDB-1 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 12.51

L3/9 12.51

L1/10

L2/10 SPARE MCCB 400 3 0.00

L3/10 0.00

L1/11

L2/11 SPACE 0.00

L3/11 0.00

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 0.00 1949.85 1949.85

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 0.00 448.46 448.46

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 717.54

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 896.93
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV30-MDB1 Location: U-HUB TYPE 3 FEEDER PHASE 2-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 2x1C 300 mm² LS0H
Supplied From: TR1 Volts: 400/230

No. of 3P Ways: 7 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 1600AT/1600AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 127.46

L2/1 FP-CFM Radial A 1 4C 95 50 MCCB 160 3 0 0 0 0 127.46

L3/1 127.46

L1/2 155.68

L2/2 FP-PSN-1 Radial A 1 4C 150 95 MCCB 225 3 0 0 0 0 155.68

L3/2 155.68

L1/3 155.68

L2/3 FP-PSN-2 Radial A 1 4C 150 95 MCCB 225 3 0 0 0 0 155.68

L3/3 155.68

L1/4 266.62

L2/4 FP-POP Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 266.62

L3/4 266.62

L1/5 0.00

L2/5 PFC-1, 350 KVAR Radial A 2 4C 150 150 MCCB 630 3 18 0 0 0 0.00

L3/5 0.00

L1/6

L2/6 SPARE MCCB 225 3 0.00

L3/6 0.00

L1/7

L2/7 SPACE 0.00

L3/7 0.00

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 0.00 705.43 705.43

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 0.00 162.25 162.25

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 259.60

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 324.50
RED SEA COASTAL VILLAGE - S3 B1 UTILITY HUB

Distribution Board Ref.: IP-EV30-MDB2 Location: U-HUB TYPE 3 FEEDER PHASE 2-4x1C 630 mm² XLPE/LS0H/SWA
CABLE EARTHING 2x1C 300 mm² LS0H
Supplied From: TR2 Volts: 400/230

No. of 3P Ways: 12 Phase: 3 CABLE


LENGTH
Incoming Device Rating: 1600AT/1600AF IP Rating: IP55 (M)

Short Circuit Level, S.C. (KA): 65 Load Spare Capacity(%): 25

Form Type: Form-4b

Tabulated Voltage Cummulative,


Protective Length,L LOAD CURRENT,IL(Amps)
Circuit Cable Installation Line Cable CPC Cable Protective VD, Drop, VD1 VD3
CKT No. CIRCUIT DESCRIPTION No. of runs No. of Cores Device Rating Poles
Type Type Method Size(mm²) Size(mm²) Device Type
(AT) m mV/m/A % % Phase A Phase B Phase C

L1/1 462.43

L2/1 FP-IPF Radial A 2 4C 150 150 MCCB 630 3 0 0 0 0 462.43

L3/1 462.43

L1/2 5.78

L2/2 FP-IWT Radial A 1 4C 25 16 MCCB 40 3 0 0 0 0 5.78

L3/2 5.78

L1/3 23.12

L2/3 FP-IPS Radial A 1 4C 70 35 MCCB 63 3 0 0 0 0 23.12

L3/3 23.12

L1/4 115.61

L2/4 FP-IPI Radial A 1 4C 70 35 MCCB 160 3 0 0 0 0 115.61

L3/4 115.61

L1/5 57.80

L2/5 FP-IPW Radial A 1 4C 25 16 MCCB 80 3 0 0 0 0 57.80

L3/5 57.80

L1/6 115.61

L2/6 FP-IES Radial A 1 4C 70 35 MCCB 160 3 0 0 0 0 115.61

L3/6 115.61

L1/7 0.00

L2/7 PFC-2, 350 KVAR Radial A 2 4C 150 150 MCCB 630 3 14 0 0 0 0.00

L3/7 0.00

L1/8 50.02

L2/8 Gen panel/ESMDB-1 Radial A 1 4C 240 120 MCCB 400 3 0 0 0 0 50.02

L3/8 50.02

L1/9 87.14

L2/9 MCC-CWP-EV30 Radial A 1 4C 35 25 MCCB 125 3 0 0 0 0 87.14

L3/9 87.14

L1/10 12.51

L2/10 SMDB-1 Radial A 1 4C 25 16 MCCB 125 3 0 0 0 0 12.51

L3/10 12.51

L1/11

L2/11 SPARE MCCB 160 3 0.00

L3/11 0.00

L1/12

L2/12 SPACE MCCB 630 3 0.00

L3/12 0.00

Lh = length of homerun cable/wire; Lb= length of looping/branch cable/wire Biggest Voltage Drop % 0.00 0.00

Cable Types: % VD Cummulative, VD3 = % Cummulative VD,VD2 + % VD branch circuit,VD1 CONNECTED LOAD per PHASE(A) 0.00 930.01 930.01

A = XLPE/LS0H Multicore B= PVC/LS0H Single Core C = PVC/PVC/LS0H Where: CONNECTED LOAD per PHASE(KVA) 0.00 213.90 213.90

D = XLPE/LS0H E= XLPE/LS0H/Fire Resistant F= LS0H / Fire Resistant % VD Cummulative, VD2 = % VD measured from the upstream to the Panel

Average Demad Factor 0.80

Installation Method: Demand Load(KVA) 342.24

Refer to BS 7671 Table 4A2, B = Conduit/Trunking, E= Tray, F= Cable Duct Total Demand Load(KVA)(Incl. spare capacity) 427.81