You are on page 1of 2

1.

We presume
contractor has drafted all
dimensions based on
actual survey of the
existing mullion and
transom.
2. All materials make
and specification to be
separately mentioned
and submitted for review
and approval by client
and consultant this
includes, aluminum
extrusion,
gaskets,screws etc.
Groove size to be
mentioned,
minimum
5mmx5mm
Specify material weather sealant
application with
backer rod.
This junction to be reviewed with
water testing to confirm its
tightness

Setting block as per Identify the material


calculation to be provided. and specification of
glazing tape and
Size of gasket to silicone
confirm overlap
Specify and comfortably
confirm Multi-point
locking
Restrictor to be
installed and
opening angle/
distance to be
specified.