Battery Configuration

1. Formula
P ( VA ) × PF
W(cell)=
η× S
P(VA):capacity
PF:power factor
η:inv. efficiency
S:number of battery strings
2. Requirements
UPS capacity Backup time Power factor Inv. Efficiency
200KVA 30 0.9 0.95
120KVA 30 0.9 0.95

3. Calculation process
A. 200KVA UPS
a) 150KW@ 30 minutes (PF 0.9) Parallel redundant for Full load of each UPS and
Common battery bank
P ( VA ) × PF
W(cell)= =150*1000*0.9/(192*0.96)= 732.42 watts
η× S
W(block)= 732.42*6= 4394 watts

Accu Force 12V - 150Ah battery can provide 1503 watt/cell @ 1.80V
So, 3 string of 150AH batteries required.

Two UPS sharing Common Battery of (3*32 pcs 150AH).

B. 120KVA UPS
a) 84 KW@ 30 minutes (PF 0.9) Parallel redundant for Full load of each UPS and
Common battery bank
P ( VA ) × PF
W(cell)= =84*1000*0.9/(192*0.96)= 415.03 watts
η× S
W(block)= 415.03*6= 2490 watts

Accu Force 12V - 120AH battery can provide 1202 watt/cell @ 1.80V
So, 2 string of 120 AH batteries required.

Two UPS sharing Common Battery of (2*32 pcs 120AH).