FUNCTIONAL DESCRIPTION:
The water cooled ACS AC drive is equipped with a deionizer vessel for the drive internal cooling
water (or water/glycol mixture). This deionizer is a combination of Glassfibre Reinforced epoxy
wound outer shell with a Polyethylene inner tank (GRP-vessel) filled with mixed-bed ion exchanger
resin (mixture of cation and anion resins).
The deionizer vessel is located in the cooling system treatment circuit. The factory setting for the
treatment circuit flow is 5 liters/min.
1.1 The nominal lifetime is more than 2 years. The lifetime of deionizer depends on the
amount and the quality of the used makeup water for the cooling circuit, but also
component failures in a drive main circuit can shorten the expected lifetime. ABB
recommend replacing of deionizer if conductivity alarm level is reached.
Figure 1: Deionizer
WHERE USED:
All MV ACS water cooled converters.