Exova Warringtonfire T : +44 (0 1925 655116

Holmesfield Road F : +44 (0) 1925 655419


Warrington E : warrington@exova.com
WA1 2DS W: www.exova.com
United Kingdom

BS 6387: 2013

Date: 15th June 2017


Specification For Performance Requirements
For Cables Required To Maintain Circuit Issue No.: 1
Integrity Under Fire Conditions
Page 1

A Report To: Italcond S.r.l.

Document Reference: 383766

Registered Office: Exova (UK) Ltd, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Reg No.SC 70429
This report in issued in accordance with our terms and conditions, a copy of which is available on request.
BS 6387: 2013

Executive Summary
Objective To determine the performance of the following cable when it is subjected to the
conditions of test specified in BS 6387: 2013.

Generic Description Product reference Thickness / Weight per unit


c.s.a. area / length or
density
Cable product which the “ITAL082” 8.50±0.30mm 114.50kg/km
sponsor has confirm will
be used for fire alarms
Individual components used to manufacture composite:
Outer sheath “HF 0106/2” 1.30mm 1.52g/cm3
Conductor insulation “Silicone Quality EI2 refer to 0.70mm Unwilling to provide
EN50363”
Tape “Polyester And Aluminium / Polyester 12 microns 21g/m²
Tape” 40/15 104g/m²
Conductors “Solid Copper Bare (IEC60228 – 1.50mm² 13.25g/m
Class 1)”
Conductor surrounds “Solid Copper Bare (IEC60228 – 1.50mm² 13.28g/m
Class 1”
Please see pages 6 & 7 of this test report for the full description of the product tested
Test Sponsor Italcond S.r.l., Via Erideo Marinucci, 42/44 – 62019 Recanati (MC) Italy

Test Results: When tested in accordance with BS 6387: 2013: Clauses 6, 7 and 8, the cable
meets the criteria for Protocols C, W and Z, and can be designated as
“Category CWZ”

Date of Test 5th & 6th June 2017

Signatories

Responsible Officer Authorised


C. Meachin * B. Dean *
Technical Officer Technical Leader
* For and on behalf of Exova Warringtonfire.

Report Issued: 15th June 2017

This version of the report has been produced from a .pdf format electronic file that has been provided
by Exova Warringtonfire to the sponsor of the report and must only be reproduced in full. Extracts or
abridgements of reports must not be published without permission of Exova Warringtonfire.

Document No.: 383766 Page No.: 2 of 9


th
Author: C. Meachin Issue Date: 15 June 2017
Client: Italcond S.r.l. Issue No.: 1
BS 6387: 2013

CONTENTS PAGE NO.

EXECUTIVE SUMMARY ........................................................................................................................... 2

SIGNATORIES........................................................................................................................................... 2

TEST DETAILS .......................................................................................................................................... 4

DESCRIPTION OF TEST SPECIMENS .................................................................................................... 6

TEST RESULTS ........................................................................................................................................ 8

REVISION HISTORY ................................................................................................................................. 9

Document No.: 383766 Page No.: 3 of 9


th
Author: C. Meachin Issue Date: 15 June 2017
Client: Italcond S.r.l. Issue No.: 1
BS 6387: 2013

Test Details
Purpose of test To determine the performance of a specimen of a cable when it is subjected to
the conditions of test specified in BS6387: 2013 "Specification for performance
requirements for cables required to maintain circuit integrity under fire
conditions".

The tests were performed in accordance with the procedures specified in BS


6387: 2013: Clauses 6, 7 and 8, and this report should be read in conjunction
with that Standard.

Scope of test BS 6387: 2013 is applicable to cables of rated voltage not exceeding
600/1000V and of overall diameter less than or equal to 20 mm.

The test is applicable to cables having two or more insulated conductors,


whether or not the cables incorporate other metallic elements such as armour,
screen or circuit protective conductor. The test is also applicable to cables
having one insulated conductor provided that the cable incorporates at least
one other metallic element. The test is not applicable to cables having one
insulated conductor but no other metallic element.

BS 6387: 2013 specifies methods of test for resistance to fire, resistance to fire
with water and resistance to fire and mechanical shock. The specification
categorises cables through the testing to three protocols which are as follows: -

Resistance to fire alone, Protocol C (Clause 6)

Resistance to fire with water, Protocol W (Clause 7),

Resistance to fire and mechanical shock, Protocol Z (Clause 8).

Fire test study Certain aspects of some fire test specifications are open to different
group/EGOLF interpretations. The Fire Test Study Group and EGOLF have identified a
number of such areas and has agreed Resolutions which define common
agreement of interpretations between fire test laboratories which are members
of the Groups. Where such Resolutions are applicable to this test they have
been followed.

Instruction to test The test was conducted on the 5th & 6th June 2017 at the request of Italcond
S.r.l., the sponsor of the test.

Provision of test The specimens were supplied by the sponsor of the test. Exova
specimens Warringtonfire was not involved in any selection or sampling procedure.

Conditioning of The specimens were received on the 17th May 2017.


specimens
Prior to the test the specimens were conditioned for at least 16 hours in an
atmosphere having a temperature of 23 ± 2°C and a relative humidity of 50 ±
5%.

Document No.: 383766 Page No.: 4 of 9


th
Author: C. Meachin Issue Date: 15 June 2017
Client: Italcond S.r.l. Issue No.: 1
BS 6387: 2013

Burner Temperature measurements recorded by each thermocouple were logged


verification using an Omega ‘HH1384’ four channel thermometer and data logger at 1
procedure second intervals over a period of 10 minutes and then averaged. This
determined the gas & air flow rates and the position of the burner that were
used for the subsequent cable test.

The gas and air flows were provided through the use of M&W Instruments mass
flow controllers, model numbers ‘D-6341-DR’ and ‘D-6361-DR’.

Document No.: 383766 Page No.: 5 of 9


th
Author: C. Meachin Issue Date: 15 June 2017
Client: Italcond S.r.l. Issue No.: 1
BS 6387: 2013

Description of Test Specimens


The description of the specimens given below has been prepared from information provided by the
sponsor of the test. All values quoted are nominal, unless tolerances are given.

General description Cable product which the sponsor has confirm


will be used for fire alarms
Product reference “ITAL082”
Name of manufacturer ITALCOND SRL
Diameter 8.50±0.30mm (stated by sponsor)
8.41mm (determined by Exova
Warringtonfire)
Weight per unit length 114.50kg/km (stated by sponsor)
112.8kg/km (determined by Exova
Warringtonfire)
Cable marking “ITALCOND ELECTRIC CABLE 300/500V
BS7629-1 STANDARD 60 BS6387 CWZ 2X1.5
week/year H MADE IN ITALY”
Cable function Fire alarm system and emergency lighting
Number of cores x core size 2 x 1.5mm²
Voltage rating 300/500V
Trade name “HF 0106/2”
Generic type M1
Name of manufacturer Fainplast
Colour “Red RAL3000”
Outer sheath Thickness 1.30mm
Density 1.52g/cm³
Trade name of flame retardant See Note 1 Below
Generic type of flame retardant Idrossido di magnesio (Mg(OH)2)
Amount of flame retardant 55% by weight
Trade name “Silicone Quality EI2 refer to EN50363”
Generic type Silicone
Name of manufacturer Enco srl
Conductor
Colour “Blue,Brown”
insulation
Thickness 0.70mm
Density See Note 1 Below
Flame retardant details See Note 1 Below
Trade name “Polyester And Aluminium / Polyester Tape”
Generic type Polyester and aluminium / polyester
Name of manufacturer Tecnoservice Imballaggi SRL
Tape Colour “Clear (polyester);
(surrounding Grey and blue (aluminium/polyester)”
each conductor) Thickness 12 microns (polyester);
40/15 (aluminium/polyester)
Weight per unit area 21g/m² ; 104g/m²
Flame retardant details See Note 2 Below

Continued on next page

Document No.: 383766 Page No.: 6 of 9


th
Author: C. Meachin Issue Date: 15 June 2017
Client: Italcond S.r.l. Issue No.: 1
BS 6387: 2013

Trade name “Solid Copper Bare (IEC60228 – Class 1)”


Generic type Copper
Name of manufacturer Enco srl
Total cross-sectional area of 1.50mm²
each conductor
Conductors Cross sectional area of each 1.50mm²
strand
Weight per unit length per 13.25g/m
strand
Number of strands per 1x1.38mm
conductor
Trade name “Solid Copper Bare (IEC60228 – Class 1”
Generic type Copper
Name of manufacturer Enco srl
Total cross-sectional area of 1.50mm²
Conductor
each conductor
surrounds
Cross sectional area of each 1.50mm²
strand
Weight per unit length per 13.28g/m
strand
Brief description of manufacturing process See Note 1 Below

Note 1: The sponsor was unwilling to provide this information.

Note 2: The sponsor of the test has confirmed that no flame retardant additives were utilised in
the production of the component.

Document No.: 383766 Page No.: 7 of 9


th
Author: C. Meachin Issue Date: 15 June 2017
Client: Italcond S.r.l. Issue No.: 1
BS 6387: 2013

Test Results
Applicability of The test results relate only to the behaviour of the specimen of the cable under
test results the particular conditions of test; they are not intended to be the sole criterion for
assessing the potential fire hazards of the product in use.

The test results relate only to the specimen of the cable in the form in which it
was tested. Small differences in the composition of the product may significantly
affect the performance during the test and may therefore invalidate the test
results. Care should be taken to ensure that any product, which is supplied or
used, is fully represented by the specimen, which was tested.

Results Protocol C - Resistance to fire alone (Clause 6)

When tested in accordance with the procedures specified in Clause 6 of the


standard, for a period of 3 hours at a temperature of 950±40°C and a rated
voltage of 500V-rms, the cable maintained its circuit integrity and consequently
satisfied the performance requirements specified in BS 6387: 2013.

Protocol W - Resistance to fire with water (Clause 7)

When tested in accordance with the procedures specified in Clause 7 of the


standard, for a period of 30 minutes at a temperature of 650±40°C and a rated
voltage of 500V-rms, the cable maintained its circuit integrity and consequently
satisfied the performance requirements specified in BS 6387: 2013.

Protocol Z - Resistance to fire and mechanical shock (Clause 8)

When tested in accordance with the procedures specified in Clause 8 of the


standard, for a period of 15 minutes at a temperature of 950±40°C and a rated
voltage of 500V-rms, the cable maintained its circuit integrity and consequently
satisfied the performance requirements specified in BS 6387: 2013.

Conclusion When tested in accordance with BS 6387: 2013: Clauses 6, 7 and 8 the cable
meets the criteria for Protocols C, W and Z and can be designated as “Category
CWZ”.

Validity The specification and interpretation of fire test methods are the subject of
ongoing development and refinement. Changes in associated legislation may
also occur. For these reasons it is recommended that the relevance of test
reports over five years old should be considered by the user. The laboratory that
issued the report will be able to offer, on behalf of the legal owner, a review of
the procedures adopted for a particular test to ensure that they are consistent
with current practices, and if required may endorse the test report.

This report may only be reproduced in full. Extracts or abridgements shall not be
published without permission of Exova Warringtonfire.

Document No.: 383766 Page No.: 8 of 9


th
Author: C. Meachin Issue Date: 15 June 2017
Client: Italcond S.r.l. Issue No.: 1
BS 6387: 2013

Revision History

Issue No : Re-issue Date:


Revised By: Approved By:
Reason for Revision:

Issue No : Re-issue Date:


Revised By: Approved By:
Reason for Revision:

Document No.: 383766 Page No.: 9 of 9


th
Author: C. Meachin Issue Date: 15 June 2017
Client: Italcond S.r.l. Issue No.: 1