i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 1 / 28
i‐con Control System
Faults and Diagnosis Manual
Thanks for choosing the advanced & safe control system: i‐con for escalator & moving walks.
This manual generally introduces detailed faults causes and corresponding solutions.
The document is of commercial confidential. Please keep it safe.
2015‐07‐16 issue 2015‐07‐16 implement
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 2 / 28
Catalog
1. System framework ............................................................................................................................................. 4
2. Device introduction ........................................................................................................................................... 5
2.1 Main controller ............................................................................................................................................ 5
2.2 Safety SPC .................................................................................................................................................... 5
2.3 Board A5 ...................................................................................................................................................... 6
2.4 Board A7 ...................................................................................................................................................... 6
2.5 Touch screen ................................................................................................................................................ 7
2.6 Display board ............................................................................................................................................... 7
2.7 Remote monitor board A9 ........................................................................................................................... 8
3. Faults and status information ............................................................................................................................ 8
4. Faults diagnosis and Solution .......................................................................................................................... 12
4.1 Classification and definition of fault .......................................................................................................... 12
4.2 Description of faults and solution .............................................................................................................. 12
4.2.1 Soft errors monitored by PLC .................................................................................................................. 12
4.2.2 Errors monitored by Safety SPC .............................................................................................................. 18
4.2.3 Error monitored by A5, A7 ...................................................................................................................... 20
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 4 / 28
1. System framework
Figure 1 – standardized i‐con System framework
The picture shows the mainly framework of i‐con system:
PLC, as a controller, controls escalator operation and monitors a part of safety device.
SPC, safety controller, monitors a part of safety device, sends the fault information to the
PLC.
The board A5, A7 (CIO), monitors safety switches, sends the information to PLC.
Display board (FD), communicates with PLC and displays operation status and fault
information of escalator.
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 5 / 28
2. Device introduction
2.1 Main controller
Figure 2 – Main controller PLC
PLC, as a controller, controls escalator operation and monitors a part of safety device.
2.2 Safety SPC
Figure 3 –SPC (G9SP)
SPC, safety controller, monitors a part of safety device, sends the fault information to the PLC.
If fault is detected, SPC will stop output SO1, SO2 and cut safety circuit, escalator will be stopped
immediately.
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 6 / 28
2.3 Board A5
Figure 4 –Board A5
Board A5 collects operation information of safety switch located at up part of escalator and sends to PLC.
2.4 Board A7
Figure 5 –Board A7
Board A7 collects operation information of safety switch located at down part of escalator and sends to PLC.
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 7 / 28
2.5 Touch screen
Figure 6 –HMI
Touch screen, also named HMI, monitors escalators running real‐time. When a failure occurs, it stores the
fault name and information. It communicates with PLC.
2.6 Display board
Figure 7–Display board
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 8 / 28
2.7 Remote monitor board A9
Bit1:ON
The others:OFF
Figure 8 –Remote monitor board(four‐dry contact)
3. Faults and status information
Escalator state display device receives broadcast from master controller PLC via RS485, shows so real‐time
operation of escalator by LCD screen.
Error information in the following table:
Error code Name
Soft errors monitored by PLC
E001 ERR_001_SafetyChainBroken
E002 ERR_002_PhaseRelay
E003 ERR_003_M1_OverHeat
E004 ERR_004_M2_OverHeat
E005 ERR_005_M1_OverLoad
E006 ERR_006_M2_OverLoad
E007 ERR_007_BrakeLiningWorn
E008 ERR_008_Brake_II_LiningWorn
E009 ERR_009_R_BrakeOpenDetect
E010 ERR_010_L_BrakeOpenDetect
E011 ERR_011_R_Brake_II_OpenDetect
E012 ERR_012_L_Brake_II_OpenDetect
E013 ERR_013_Adhered
E014 ERR_014_Adhered_II
E015 ERR_015_
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 9 / 28
Error code Name
E016 ERR_016_Inspect_Protection
E017 ERR_017_Inverter
E018 ERR_018_Contactor_OpenDetect
E019 ERR_019_Contactor_II_OpenDetect
E020 ERR_020_
E021 ERR_021_T_Float
E022 ERR_022_B_Float
E023 ERR_023_T_KeySwitch_Adhere
E024 ERR_024_B_KeySwitch_Adhere
E025 ERR_025_Main_Controller
E026 ERR_026_Main_Controller_realtime_clock
E027 ERR_027_Main_Controller_EEPROM
E028 ALM_028_CIO1_Communication
E029 ALM_029_CIO2_Communication
E030 ALM_030_CIO3_Communication
E031 ALM_031_CIO4_Communication
E032 ALM_032_SPC_Communication
E033 ERR_033_LackofOil
E034 ERR_034_LackofOil
E035 ERR_035_MaintenanceOverTime
E036 ERR_036_Fire_Stop
E037 ERR_037_Lock
E038 ERR_038_PowerFailure
E039 ERR_039_ResetButtonStuck
E040 ERR_040_R_BrakeCloseDetect
E041 ERR_041_L_BrakeCloseDetect
E042 ERR_042_R_Brake_II_CloseDetect
E043 ERR_043_L_Brake_II_CloseDetect
E044 ALM_044_CIO9_Communication
E045 ALM_045_CIO10_Communication
E046 ERR_046_Gate
E047 ERR_047_Flywheel
E048~099
Errors monitored by Safety SPC
E100 ERR_100_
E101 ERR_101_OverSpeed
E102 ERR_102_OverSpeed_1.4Times
E103 ERR_103_UnintendedReverse
E104 ERR_104_BrakeDistance
E105 ERR_105_L_H_Speed
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 10 / 28
Error code Name
E106 ERR_106_R_H_Speed
E107 ERR_107_T_Step/PalletMissing
E108 ERR_108_B_Step/PalletMissing
E109 ERR_109_Brake_Open_Failed
E110 ERR_110_BrakeCloseFailed
E111 ERR_111_Stop_With_ABPulses
E112 ERR_112_Without_ABPulses_within4s
E113 ERR_113_SpeedSensor/UnderSpeed
E114 ERR_114_SafetyRelay_Y1Adhere
E115 ERR_115_Storage_Initialize_Failed
E116 ERR_116_CPU_Compared_Failed
E117 ERR_117_Parameter_Setting
E125 ERR_125_E_Brake_Failed
E126 ERR_126_UnderSpeed
E127 ERR_127_L_HandSpeedDetector
E128 ERR_128_R_HandSpeedDetector
E132 ERR_132_ResetButtonAdhered
E133 ERR_133_Running_Signal
E134 ERR_134_EBrakeControl_Failure
E135 ERR_135_EDM
E136 ERR_136_StepMissingDetector
E137~199
Errors monitored by board A5
E200 ERR_200_ECP_Mushroom_EStop
E201 ERR_201_T_Mushroom_EStop
E202 ERR_202_T_EStop
E203 ERR_203_T_In_EStop
E204 ERR_204_T_Out_EStop
E205 ERR_205_Mid_Estop_1
E206 ERR_206_Mid_Estop_2
E207 ERR_207_Mid_Estop_3
E208 ERR_208_T_L_Comb
E209 ERR_209_T_R_Comb
E210 ERR_210_T_L_Comb_Vertical
E211 ERR_211_T_R_Comb_Vertical
E212 ERR_212_T_L_HandInlet
E213 ERR_213_T_R_HandInlet
E214 ERR_214_T_Upthrust
E215 ERR_215_T_Pallet_Falling
E216 ERR_216_Ebrake_Switch
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 11 / 28
Error code Name
E219 ERR_219_T_L_Skirting
E220 ERR_220_T_R_Skirting
E221 ERR_221_M_L_Skirting_1
E222 ERR_222_M_R_Skirting_1
E223 ERR_223_M_L_Skirting_2
E224 ERR_224_M_R_Skirting_2
E227 ERR_227_T_INS_Socket_Open
E228 ERR_228_INS_Estop
E230 ERR_230_T_Step/Pallet_Sag
E231 ERR_231_T_LandingPlate
E232 ERR_232_T_Relevancy_Stop
E233 ERR_233_SafetyChain_Power_off
E234 ERR_234_T_Fire(110Vac)
E235 ERR_235_Motor_Displace
E236~E299 ERR_236_T_Reserve_Switch
Errors monitored by board A7
E300 ERR_300_
E301 ERR_301_B_Mushroom_EStop
E302 ERR_302_B_Estop
E303 ERR_303_B_In_Estop
E304 ERR_304_B_Out_Estop
E305 ERR_305_Mid_Estop_4
E306 ERR_306_Mid_Estop_5
E307 ERR_307_Mid_Estop_6
E308 ERR_308_B_L_Comb
E309 ERR_309_B_R_Comb
E310 ERR_310_B_L_Comb_Vertical
E311 ERR_311_B_R_Comb_Vertical
E312 ERR_312_B_L_HandInlet
E313 ERR_313_B_R_HandInlet
E314 ERR_314_B_Upthrust
E315 ERR_315_B_Pallet_Falling
E316 ERR_316_L_StepChain
E317 ERR_317_R_StepChain
E318 ERR_318_
E319 ERR_319_B_L_Skirting
E320 ERR_320_B_R_Skirting
E321 ERR_321_M_L_Skirting_1
E322 ERR_322_M_R_Skirting_1
E323 ERR_323_M_L_Skirting_2
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 12 / 28
Error code Name
E324 ERR_324_M_R_Skirting_2
E325 ERR_325_B_L_Hand_Broken
E326 ERR_326_B_R_Hand_Broken
E327 ERR_327_B_INS_Socket_Open
E328 ERR_328_INS_Estop
E330 ERR_330_B_Step/Pallet_Sag
E331 ERR_331_B_LandingPlate
E332 ERR_332_B_Relevancy_Stop
E333 ERR_333_Connector_Plug_Break
E334 ERR_334_B_Fire(110Vac)
E335 ERR_335_B_Reserve_Switch
4. Faults diagnosis and Solution
4.1 Classification and definition of fault
Faults are divided into hard error and soft error.
Hard error means error caused by safety switch opens. All other errors are called soft error.
When fault occurs, the buzzer will sound 0.5 second every second.
This system provides complete safety switches and safety devices, to form safety circuit. The safety circuit
can directly cut the power supply of contactor of main circuit and brake circuits, to ensure safe and reliable.
4.2 Description of faults and solution
The faults are divided into three types as below.
4.2.1 Soft errors monitored by PLC
After safety switch action, buzzer will continue buzzing until the safety switch reset. Fault display will still
show the last fault occurred, by pressing the reset button to reset display.
Soft errors monitored by PLC
Soft errors monitored by PLC
1. The right brake switch defective
1. Check and adjust right brake switch and
or not adjusted properly;
ERR_009_R_Brake_ restart;
E009 2. PLC: I03 input damaged;
Open_Failed 2. Check right brake operation
3. Right brake switch wrong
3. Check PLC: I03 input terminal and wiring.
wiring.
1. Left brake switch defective or 1. Check and adjust left brake switch and
ERR_010_L_Brake_
E010 not adjusted properly; restart;
Open_Failed
2. PLC: I02 input damaged; 2. Check left brake open operation.
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 14 / 28
Soft errors monitored by PLC
1. The right brake switch defective
1. Check and adjust right brake switch and
or not adjusted properly;
ERR_011_R_Brake_ restart;
E011 2. PLC: I08 input damaged;
II_Open_Failed 2. Check right brake open operation
3. Right brake switch wrong
3. Check PLC: I08 input terminal and wiring.
wiring.
1. Left brake switch defective or
1. Check and adjust left brake switch and
not adjusted properly;
ERR_012_L_Brake_ restart;
E012 2. PLC: I07 input damaged;
II_Open_Failed 2. Check left brake open operation.
3. The left brake switch wrong
3. Check PLC: I07 input terminal and wiring.
wiring.
1. After Escalator/moving walk
stop, contactors KM4, KM5, KM8
1. Check contactor, reset fault and restart;
or KM10 not release;
2. Check contactor’s auxiliary normal
2. PLC: I13 input damaged;
ERR_013_Contacto closed contact and it’s wiring;
E013 3. After escalator shutdown,
r_Adhered 3. Check if contactor is stuck;
contactors KM4, KM5, KM8 or
4. Check if PLC: I13 input terminal is
KM10 auxiliary normally closed
defective.
contact is not closed;
4. Abnormal wiring.
1. After Escalator/moving walk
stop, contactors KM6, KM7, or
1. Check contactor, reset fault and restart;
KM11 not release;
2. Check contactor’s auxiliary normal
2. PLC: I14 input damaged;
ERR_014_Contacto closed contact and its wiring;
E014 3. After escalator shutdown,
r_II_Adhered 3. Check if contactor is stuck;
contactors KM6, KM7, or KM11
4. Check if PLC: I14 input terminal is
auxiliary normally closed contact
defective.
is not closed;
4. Abnormal wiring.
1. During normal operation, top
or bottom inspection socket
wiring loosen; 1. Check top and bottom inspection socket;
ERR_016_Inspectio 2. Top or bottom inspection 2. Check if PLC: I11 input terminal
E016
n_Protection socket cover loosen; defective;
3. PLC: I11 input defective; 3. Check inspection socket wiring.
4. During normal operation,
connection between top and
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 15 / 28
Soft errors monitored by PLC
1. Check Inverter is faulty or not;
1. Inverter is faulty;
2. Check PLC: I23 input terminal and
ERR_017_Inverter_ 2. PLC: I23 input or inverter’s fault
E017 inverter’s fault output terminal;
Protection output terminals defective;
3. Check inverter’s fault output terminals
3. Wiring fault.
wiring.
1. When Escalator starting,
1. Check contactors, reset fault and restart;
contactors KM4, KM5, KM8 or
2. Check contactor auxiliary normal closed
KM10 auxiliary normal closed
ERR_018_Contacto contact and its wiring;
E018 contact not open;
r_Close_Failed 3. Check if contactor is stuck;
2. PLC: I13 input defective;
4. Check if PLC: I13 input terminal is
3. involved wiring is abnormal;
defective.
4. PLC: I13 input is shorted.
1. When Escalator starting,
1. Check contactors, reset fault and restart;
contactors KM6, KM7, or KM11
2. Check contactor auxiliary normal closed
auxiliary normal closed contact
ERR_019_Contacto contact and its wiring;
E019 not open;
r_II_Close_Failed 3. Check if contactor is stuck;
2. PLC: I14 input defective;
4. Check if PLC: I14 input terminal is
3. involved wiring is abnormal;
defective.
4. PLC: I14 input is shorted.
1. Float switch activated because 1. Reset then restart;
E021 ERR_021_T_Float of water in machine room; 2. Check if float switch is activated;
E022 ERR_022_B_Float 2. Float switch defective; 3. Check involved wiring and plug
3. involved wiring anomaly; connection.
1. A5/A6 and A3 communication 1. Check communication wiring between
cable not connected well; A5/A6 and A3,and communications
ALM_028_CIO1_Co
2. A5/A6 or A3 communication interface;
E028 mmunication(A5))
interface damaged; 2. Check board A5/A6 DIP switch address
E029 ALM_029_CIO2_Co
3. Board A5/A6 DIP switch setting setting and communication mode;
mmunication(A6)
wrong; 3. Check PLC communication interface
4. Involved plug‐in wiring loosens. Status.
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 16 / 28
Soft errors monitored by PLC
Soft errors monitored by PLC
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 18 / 28
4.2.2 Errors monitored by Safety SPC
When the error is detected, SPC cuts off safety relay (K20 and K21), thereby cut off the safety circuit, to stop
escalator running. Fault as following:
Errors monitored by Safety SPC
Errors monitored by Safety SPC
Errors monitored by Safety SPC
1. Some faults (for example E‐brake fault) will be hold even after reset the power. Press the reset button
twice within 3 seconds to reset.
2. For E‐brake fault, after reset, KR3 and KR4 which are controlled by SPC: Si02 and SPC: Si03 will be
energized, and then E‐brake coil will be able to be energized.
4.2.3 Error monitored by A5, A7
If safety switch action detected, the buzzer will continue buzzing until the safety switch is reset. Fault display
will still show the last fault occurred, by pressing the reset button to reset display.
4.2.3.1 Errors monitored by board A5
Errors monitored by board A5
Errors monitored by board A5
Errors monitored by board A5
Errors monitored by board A5
1. Top inspection handle E‐stop button
ERR_228_ 1. Check if top inspection handle
is pressed;
E228 INS_Estop E‐stop button is adhered or pressed;
2. Top inspection handle E‐stop button
(optional) 2. Check involved connection.
adhered or connection abnormal.
1. Top pallet/step sags;
1. Reset and then restart;
2. Top pallet/step sag witch activated
2. Check if top pallet/step sags or
ERR_230_ or switch damaged.
switch activated or damaged;
E230 T_Step/Pallet_S 3. Top pallet/step sag switch to
3. Check wiring from top pallet/step
ag terminal A5: XJ16 connection
sag switch to terminal A5: XJ16;
abnormal;
4. Check terminal A5: XJ16.
4. Terminal A5: XJ16 damaged.
1. Reset and then restart;
1. Top landing plate be opened;
2. Check if top landing plate cover is
2. Top landing plate switch activated or
opened or top landing plate switch
ERR_231_ damaged;
E231 activated or damaged;
T_LandingPlate 3. Top landing plate to terminal A5:
3. Check wiring from top landing plate
XJ17 connection abnormal;
to terminal A5: XJ17;
4. A5: XJ17 terminal damaged.
4. Check terminal A5: XJ17.
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 24 / 28
Errors monitored by board A5
ERR_303_ Similar to bottom emergency stop
E303 Refer to solution of ERR301
B_In_Estop control cabinet
ERR_304_ Similar to bottom emergency stop
E304 Refer to solution of ERR301
B_Out_Estop control cabinet
ERR_305_ Similar to bottom emergency stop
E305 Refer to solution of ERR301
Mid_Estop_4 control cabinet
ERR_306_ Similar to bottom emergency stop
E306 Refer to solution of ERR301
Mid_Estop_5 control cabinet
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 25 / 28
Errors monitored by board A7
ERR_307_ Similar to bottom emergency stop
E307 Refer to solution of ERR301
Mid_Estop_6 control cabinet
1. Bottom left horizontal comb switch 1. Reset and then restart;
activated or damaged; 2. Check if bottom left comb or
ERR_308_ 2. Bottom left comb horizontal switch horizontal comb switch is stuck;
E308
B_L_Comb to terminal A7: XJ3 connection 3. Check bottom left comb horizontal
abnormal; switch to terminal A7: XJ3 wiring;
3. Terminal A7: XJ3 damaged. 4. Check terminal A7: XJ3.
1. Bottom right comb horizontal switch 1. Reset and then restart;
activated or damaged; 2. Check if bottom right comb or
2. Bottom right horizontal comb switch horizontal comb switch is stuck;
ERR_309_
E309 to terminal A7: XJ4 connection 3. Check bottom right horizontal
B_R_Comb
abnormal; comb switch to terminal A7: XJ4
3. Terminal A7: XJ4 damaged. wiring;
4. Check terminal A7: XJ4.
ERR_310_
Similar to bottom left horizontal comb Similar to bottom left horizontal
E310 B_L_Comb_Vertic
switch comb switch
al
ERR_311_
Similar to bottom right horizontal comb Similar to bottom right horizontal
E311 B_R_Comb_Verti
switch comb switch
cal
1. Reset and then restart;
1. Bottom left handrail inlet switch 2. Check if bottom left handrail inlet
activated or damaged; is stuck, or switch defective;
ERR_312_
E312 2. Bottom left handrail switch to 3. Check wiring from bottom left
B_L_HandInlet
terminal A7: XJ5 connection abnormal; handrail inlet switch to terminal A7:
3. A7: XJ5 terminal damaged. XJ5;
4. Check terminal A7: XJ5.
1. Reset and then restart;
1. Bottom right handrail inlet switch 2. Check if bottom right handrail inlet
activated or damaged; is stuck, or switch defective;
ERR_313_
E313 2. Bottom right handrail switch to 3. Check wiring from bottom right
B_R_HandInlet
terminal A7: XJ6 connection abnormal; handrail inlet switch to terminal A7:
3. A7: XJ6 terminal damaged. XJ6;
4. Check terminal A7: XJ6.
ERR_314_ 1. Bottom upthrust switch activated or 1. Reset and then restart;
E314 B_Upthrust damaged; 2. Check if upthrust switch activated
(optional for 2. Bottom upthrust switch to terminal or damaged;
i‐con Control System Faults and Diagnosis Manual NO.: JSS56008E Ver.:C 26 / 28
Errors monitored by board A7
Errors monitored by board A7
Errors monitored by board A7
1. Reset and then restart;
2. Check if relevancy stop switch
ERR_332_ 1. Relevancy stop switch to terminal
activated or damaged;
E332 B_Relevancy_Sto A7: XJ18 connection abnormal;
3. Check wiring from relevancy stop
p 2. Terminal A7: XJ18 damaged.
switch to terminal A7: XJ18;
4. Check terminal A5: XJ18.
1. Safety circuit power off;
1. Reset and restart;
2. Terminal A7: XJ0 connection
ERR_333_ 2. Check terminal A7: XJ0 connection;
abnormal;
E333 Connector_Plug_ 3. Check terminal A7: XJ0;
3. Terminal A7: XJ0 damaged.
Break 4. Check connection between A3 and
4. Connection between A3 and A4
A4.
abnormal.
1. Reset and then restart;
1. Fire happens or switch activated or
2. Check if fire happens or fire signal
damaged;
ERR_334_ activated;
E334 2. Fire switch and terminal A7: XJ15
B_Fire (110Vac) 3. Check wiring from fire signal to
connection abnormal;
terminal A7: XJ15;
3. Terminal A7: XJ15 damaged.
4. Check terminal A7: XJ15.