You are on page 1of 1

Load Loss Temperature Rise Test - HV Winding temperature rise

Before start of
Cold Resistance Rc (Ω) = 0.26743 Test
Hot Resistance Rh (Ω) = 0.296392 From Graph
Cold Temperature Tc (Deg C) = 23
Th (Deg
Hot Temperature C) = ?
Ta (Deg
Ambient Temperature C) = 21.1

Formula for conversion


Rc = (225+Tc)
Rh (225+Th)

Tc (Deg C) = 49.85787

Temperature Rise = Tc-Ta


28.76 Deg. C

Load Loss Temperature Rise Test - LV Winding temperature rise

Before start of
Cold Resistance Rc (Ω) = 0.001316 Test
Hot Resistance Rh (Ω) = 0.001501 From Graph
Cold Temperature Tc (Deg C) = 23
Th (Deg
Hot Temperature C) = ?
Ta (Deg
Ambient Temperature C) = 21.1

Formula for conversion


Rc (225+Tc)
Rh (225+Th)

Tc (Deg C) = 57.82024

Temperature Rise = Tc-Ta


36.72 Deg. C