The designers of low-rise buildings have for many years used their engineering judgement
to interpret the phrase realistic combination, and this has led to many different views. In
particular, Load Combination 3 (dead load, imposed load and wind load) appears to have
had a wide range of interpretations and hence many related questions. Questions arise
from the perceived improbability of full imposed load on a roof when the wind load is also
at its maximum.
Firstly, it is difficult to imagine a maintenance load of 0.6kN/m² over more than a small
proportion of a large single storey roof at any one time. It is even more difficult to imagine
a maintenance load over an entire roof with the wind at its most onerous. It is improbable
that the roof will be maintained or cleaned during a windstorm.
Secondly, many designers find it difficult to imagine that snow will remain on a roof when
the wind is at maximum speed, although they would accept that it is unlikely that wind
will blow away the snow when the snowfall has frozen or is close to melting point. Thus it
is recommended that the combinations of wind and the various snow loads be considered
realistic combinations. BS 6399-3: 1988 should be referred to for an understanding of the
various snow loads – uniform, asymmetric and drifted.
It is recommended that low-rise buildings should be designed for the following load
combinations:
100% roof imposed load. i.e. The greater of the snow loads (uniform or asymmetric)
and the minimum roof (maintenance) load, e.g. 0.6kN/m²
1/2
100% wind load
80% snow load (uniform or asymmetric)+ 80% wind load
Other reasonable combinations that may arise from real and definable loads.
Note that AD 273 gives recommendations for the wind loads to considered when checking
deflections.
Load combination 1: Dead load and imposed load (gravity load). The roof
imposed load should be taken as the greater of the snow load (uniform, asymmetric
or drifted (1)) and the minimum roof (maintenance) load(2), e.g. 0.6 kN/m².
Load combination 2: Dead load and wind load.
Load combination 3: Dead load, imposed load and wind load. The roof imposed
load should be taken as the snow load (uniform, asymmetric or drifted) and/or
other real and definable loads, but not the minimum roof (maintenance) load (e.g.
0.6 kN/m²).