Professional Documents
Culture Documents
CT Burden
The CT burden is defined as the load connected across its secondary, which is usually
expressed in volt amperes (VA). It can also be expressed in terms of impedance at the
rated secondary current at a given power factor, usually 0.7 lagging. From the given
impedance at rated secondary current, the burden in VA can be calculated.
Suppose the burden is 0.5 W at 5 A secondary current. Its volt amperes will be equal to
𝐼 2 R = 52 × 0.5 = 1.25 VA. The total burden on the CT is that of the relays, meters,
connecting leads and the burden due to the resistance of the secondary winding of the CT.
The relay burden is defined as the power required to operate the relay. The burden of
relays and meters is given by the manufactures or it can be calculated from the
manufacturer’s specifications as the burden depends on their type and design.
The burden of leads depends on their resistance and the secondary current. Lead
resistance is appreciable if long wires run from the switchyard to the relay panels placed in
the control room. Lead burden can also be reduced using low secondary currents.
Usually secondary current of 5 A are used, but current of 2 A or even 1 A can be used to
reduce the lead burden. Suppose, the lead resistance is 5 Ω. Then lead burden at 5 A will
be 52 × 5 = 125 VA. The burden at 1 A is only 12 × 5 = 5 VA.
The rated VA output of the CT selected should be the higher standard value nearest
to the calculated value. If the VA rating of the CT selected is very much in excess of
the burden, it makes the choice uneconomical and the CT becomes unduly large.
Switchgear – Definition [1],[2]
In power system, all lines and other equipments operate at high voltages
and carry large currents. When a short circuit occurs on the system,
heavy current flowing through the equipment may cause considerable
damage. In order to interrupt such heavy fault currents, automatic
circuit breakers (or simply circuit breakers) are used along with
protective relay.
(ii) Indoor type. For voltages below 66 kV, switchgear is generally installed
indoor because of economic considerations. The indoor switchgear is generally
of metal-clad type. In this type of construction, all live parts are completely
enclosed in an earthed metal casing
Location of Switchgear in Typical Power System –
- Single Line Diagram [2],[3]