TWO WAY SLAB DESIGN

Floor Slab

INPUT DATA
Clear short span of slab ( La ) = 10.67 ft. Strength reduction factor Ø
Clear long span of slab ( Lb ) = 17.34 ft. 0.9 = Ø Flexure
f'c = 3,000 psi. 0.85 = Ø Shear & Torsion
fy = 40,000 psi.
b1 = 0.85 1 = ( α ) Location factor
Concrete clear cover = 1" in. 1 = ( β ) Coating factor
Type of Slab ( Case ) = 2 1 = ( λ ) Concrete factor

Live load = 40 psf. 1.2 = Safety factor of D-L


Dead load = 56.25 psf. 1.6 = Safety factor of L-L
Floor finish = 30 psf.
Factored Dead Load = 103.5 psf.
Factored Live Load = 64 psf.
Total Factored Load Wu = 167.5 psf.

Lb / La = 1.6251172 < 2 Two way slab analysis


minimum thick of slab = 3.7346667 in.
Use slab tk. h = 4.5 in.

La / Lb = 0.6153403
Use ( La / Lb ) = 0.60

OUTPUT DATA
Temperature and shrinkage steel
As(min) = 0.002 x Ag
= 0.108 in2/ft
Required development length (Ld)= [(fy α λ β)/(25 fc'^0.5)] db
Required Ld = 11.50 in.

Check Shear
coefficient ( Ca ) = 0.890 ( from Table 12.6 )
Short direction ( Vu.a ) = Ca Wu La / 2
= 795.31513 lb./ ft.

coefficient ( Cb ) = 0.110 ( from Table 12.6 )


Long direction ( Vu.b ) = Cb Wu Lb / 2
= 159.74475 lb./ ft.

Allowable shear ( Ø Vc ) = 2 Ø ( f'c )0.5 bw d


= #VALUE! lb./ ft. ### 795.315 lb./ ft. ###
Analysis by moment coefficient method ( Continued-1 )
Middle Strip Moment & Reinforcements
Negative moment at continuous edge
Ca.neg = 0.081 ( from Table 12.3 )
Ma.neg = Ca.neg wu La^2
= 18.535739 kip.in./ft.

Provided steel, # 8 mmØ @ 6 in. c/c


Provided, As = 0.1558 in2/ ft ###
a = 0.2037 in
Check Resisting, Mu = #VALUE! kip.in./ft. ### Mu = 18.54 kip.in./ft. ###
Check Req. Eff., d = #VALUE! in. ### Eff 'd' = ### in. ###
Steel cut off point ( Ld.a ) = La / 3
= 42.680 in. > Ld = 11.501 in. OK

Cb.neg = 0.010 ( from Table 12.3 )


Mb.neg = Cb.neg Wu Lb^2
= 6.0435796 kip.in./ft.

Provided steel, # 10 mmØ @ 4 in. c/c


Provided, As = 0.3652 in2/ ft ###
a = 0.4774 in
Check Resisting, Mu = #VALUE! kip.in./ft. ### Mu = 6.04 kip.in./ft. ###
Check Req. Eff., d = #VALUE! in. ### Eff 'd' = ### in. ###
Steel cut off point ( Ld.b ) = Lb / 3
= 69.360 in. > Ld = 11.501 in. OK

Positive moment at middle span


Ca.dl = 0.034 ( from Table 12.4 )
Ma.dl = Ca.dl Wu.dl La^2
= 4.8076113 kip.in./ft.

Ca.ll = 0.058 ( from Table 12.5 )


Ma.ll = Ca.ll Wu.ll La^2
= 5.0712854 kip.in./ft.

Ma.pos = 9.8788968 kip.in./ft.

Provided steel, # 10 mmØ @ 8 in. c/c


Provided, As = 0.1826 in2/ ft ###
a = 0.2387 in
Check Resisting, Mu = #VALUE! kip.in./ft. ### Mu = 9.88 kip.in./ft. ###
Check Req. Eff., d = #VALUE! in. ### Eff 'd' = ### in. ###
Cb.dl = 0.004 ( from Table 12.4 ) ( Continued-2 )
Mb.dl = Cb.dl Wu.dl Lb^2
= 1.4937564 kip.in./ft.

Cb.ll = 0.007 ( from Table 12.5 )


Mb.ll = Cb.ll Wu.ll Lb^2
= 1.616432 kip.in./ft.

Mb.pos = 3.1101884 kip.in./ft.

Provided steel, # 10 mmØ @ 8 in. c/c


Provided, As = 0.1826 in2/ ft ###
a = 0.2387 in
Check Resisting, Mu = #VALUE! kip.in./ft. ### Mu = 3.11 kip.in./ft. ###
Check Req. Eff., d = #VALUE! in. ### Eff 'd' = ### in. ###

10 8

Column Strip Moment & Reinforcements


Negative moment at continuous edge
Ma.neg = Ma.neg x 2/3 ( middle strip neg moment at continuous edge )
= 12.35716 kip.in./ft.

Provided steel, # 10 mmØ @ 8 in. c/c


Provided, As = 0.1826 in2/ ft ###
a = 0.2387 in

( Continued-3 )

Check Resisting, Mu = #VALUE! kip.in./ft. ### Mu = 12.36 kip.in./ft. ###


Check Req. Eff., d = #VALUE! in. ### Eff 'd' = ### in. ###

Mb.neg = Mb.neg x 2/3 ( middle strip neg moment at continuous edge )


= 4.029053 kip.in./ft.

Provided steel, # 10 mmØ @ 8 in. c/c


Provided, As = 0.1826 in2/ ft ###
a = 0.2387 in
Check Resisting, Mu = #VALUE! kip.in./ft. ### Mu = 4.03 kip.in./ft. ###
Check Req. Eff., d = #VALUE! in. ### Eff 'd' = ### in. ###

Positive moment at middle span


Ma.pos = Ma.pos x 2/3 ( middle strip positive moment )
Ma.pos = 6.5859312 kip.in./ft.

Provided steel, # 10 mmØ @ 8 in. c/c


Provided, As = 0.1826 in2/ ft ###
a = 0.2387 in
Check Resisting, Mu = #VALUE! kip.in./ft. ### Mu = 6.59 kip.in./ft. ###
Check Req. Eff., d = #VALUE! in. ### Eff 'd' = ### in. ###

Mb.pos = Mb.pos x 2/3 ( middle strip positive moment )


Mb.pos = 2.0734589 kip.in./ft.

Provided steel, # 10 mmØ @ 8 in. c/c


Provided, As = 0.1826 in2/ ft ###
a = 0.2387 in
Check Resisting, Mu = #VALUE! kip.in./ft. ### Mu = 2.07 kip.in./ft. ###
Check Req. Eff., d = #VALUE! in. ### Eff 'd' = ### in. ###
( Continued-4 )

10 8
( As = 12 x Ab / S )
( a = As fy / 0.85 fc' b )
( Mu = F As fy ( d - a / 2 ))
(Mu = F r fy b d2 ( 1 - ( 0.59 r fy / fc')))
TWO WAY SLAB DESIGN

Floor Slab

INPUT DATA
Clear short span of slab ( La ) = 10.67 ft. Strength reduction factor Ø
Clear long span of slab ( Lb ) = 17.34 ft. 0.9 = Ø Flexure
f'c = 3,000 psi. 0.85 = Ø Shear & Torsion
fy = 40,000 psi.
b1 = 40 1 = ( α ) Location factor
Concrete clear cover = 1 in. 1 = ( β ) Coating factor
Type of Slab ( Case ) = 1 1 = ( λ ) Concrete factor

Live load = 60 psf. 1.4 = Safety factor of D-L


Dead load = 56.25 psf. 1.7 = Safety factor of L-L
Floor finish = 30 psf.
Factored Dead Load = 120.75 psf.
Factored Live Load = 102 psf.
Total Factored Load Wu = 222.75 psf.

Lb / La = 1.6251172 < 2 Two way slab analysis


minimum thick of slab = 3.7346667 in.
Use slab tk. h = 4.5 in.

La / Lb = 0.6153403
Use ( La / Lb ) = 0.60

OUTPUT DATA
Temperature and shrinkage steel
As(min) = 0.002 x Ag
= 0.108 in2/ft
Required development length (Ld)= [(fy α λ β)/(25 fc'^0.5)] db
Required Ld = 11.50 in.

Check Shear
coefficient ( Ca ) = 0.890 ( from Table 12.6 )
Short direction ( Vu.a ) = Ca Wu La / 2
= 1057.6504 lb./ ft.

coefficient ( Cb ) = 0.110 ( from Table 12.6 )


Long direction ( Vu.b ) = Cb Wu Lb / 2
= 212.43668 lb./ ft.

Allowable shear ( Ø Vc ) = 2 Ø ( f'c )0.5 bw d


= lb./ ft. > 1057.65 lb./ ft. OK
Analysis by moment coefficient method ( Continued-1 )

10 6

10 6

Positive moment at middle span


Ca.dl = 0.081 ( from Table 12.4 )
Ma.dl = Ca.dl Wu.dl La^2
= 13.362332 kip.in./ft.

Ca.ll = 0.081 ( from Table 12.5 )


Ma.ll = Ca.ll Wu.ll La^2
= 11.287435 kip.in./ft.

Ma.pos = 24.649767 kip.in./ft.

Provided steel, # 10 mmØ @ 6 in. c/c


Provided, As = 0.2435 in2/ ft
a = 0.3183 in
Check Resisting, Mu = 27.557 kip.in./ft. > Mu = 24.65 kip.in./ft. OK
Check Req. Eff., d = 3.12 in. < Eff 'd' = 3.3031 in. OK
Cb.dl = 0.010 ( from Table 12.4 ) ( Continued-2 )
Mb.dl = Cb.dl Wu.dl Lb^2
= 4.3567894 kip.in./ft.

Cb.ll = 0.010 ( from Table 12.5 )


Mb.ll = Cb.ll Wu.ll Lb^2
= 3.6802693 kip.in./ft.

Mb.pos = 8.0370588 kip.in./ft.

Provided steel, # 10 mmØ @ 6 in. c/c


Provided, As = 0.2435 in2/ ft
a = 0.3183 in
Check Resisting, Mu = 24.107 kip.in./ft. > Mu = 8.04 kip.in./ft. OK
Check Req. Eff., d = 1.68 in. < Eff 'd' = 2.9094 in. OK

10 6

10 6
10 6

( Continued-3 )

10 6

Positive moment at middle span


Ma.pos = Ma.pos x 2/3 ( middle strip positive moment )
Ma.pos = 16.433178 kip.in./ft.

Provided steel, # 10 mmØ @ 6 in. c/c


Provided, As = 0.2435 in2/ ft
a = 0.3183 in
Check Resisting, Mu = 27.557 kip.in./ft. > Mu = 16.43 kip.in./ft. OK
Check Req. Eff., d = 2.55 in. < Eff 'd' = 3.3031 in. OK

Mb.pos = Mb.pos x 2/3 ( middle strip positive moment )


Mb.pos = 5.3580392 kip.in./ft.

Provided steel, # 10 mmØ @ 6 in. c/c


Provided, As = 0.2435 in2/ ft
a = 0.3183 in
Check Resisting, Mu = 24.107 kip.in./ft. > Mu = 5.36 kip.in./ft. OK
Check Req. Eff., d = 1.37 in. < Eff 'd' = 2.9094 in. OK

10 7
( Continued-4 )

10 6
( As = 12 x Ab / S )
( a = As fy / 0.85 fc' b )
( Mu = F As fy ( d - a / 2 ))
(Mu = F r fy b d2 ( 1 - ( 0.59 r fy / fc')))
Table 12.3 Coefficients for negative moment in slabs
Ma.neg = Ca.neg w Ln2
Mb.neg = Cb.neg w Ln2 Where ( w ) = total uniform dead load plus live load

Ratio Case 1 Case 2 Case 3 Case 4 Case 5 Case 6 Case 7 Case 8


m = L a / Lb
1 Ca.neg 0.045 0.050 0.075 0.071 0.033
1 Cb.neg 0.045 0.076 0.050 0.071 0.061
0.95 Ca.neg 0.050 0.055 0.079 0.075 0.038
0.95 Cb.neg 0.041 0.072 0.045 0.067 0.056
0.9 Ca.neg 0.055 0.060 0.080 0.079 0.043
0.9 Cb.neg 0.037 0.070 0.040 0.062 0.052
0.85 Ca.neg 0.060 0.066 0.082 0.083 0.049
0.85 Cb.neg 0.031 0.065 0.034 0.057 0.046
0.8 Ca.neg 0.065 0.071 0.083 0.086 0.055
0.8 Cb.neg 0.027 0.061 0.029 0.051 0.041
0.75 Ca.neg 0.069 0.076 0.085 0.088 0.061
0.75 Cb.neg 0.022 0.056 0.024 0.044 0.036
0.7 Ca.neg 0.074 0.081 0.086 0.091 0.068
0.7 Cb.neg 0.017 0.050 0.019 0.038 0.029
0.65 Ca.neg 0.077 0.085 0.087 0.093 0.074
0.65 Cb.neg 0.014 0.043 0.015 0.031 0.024
0.6 Ca.neg 0.081 0.089 0.088 0.095 0.080
0.6 Cb.neg 0.010 0.035 0.011 0.024 0.018
0.55 Ca.neg 0.084 0.092 0.089 0.096 0.085
0.55 Cb.neg 0.007 0.028 0.008 0.019 0.014
0.5 Ca.neg 0.086 0.094 0.090 0.097 0.089
0.5 Cb.neg 0.006 0.022 0.006 0.014 0.010

Table 12.4 Coefficients for dead load positive moments in slabs


Ma.pos.d l = Ca.d l w L n
2

Mb.pos.d l = Cb.d l w Ln2 Where ( w ) = total uniform dead load


Ratio Case 1 Case 2 Case 3 Case 4 Case 5 Case 6 Case 7 Case 8
m = L a / Lb
1 Ca.d l 0.036 0.018 0.018 0.027 0.027 0.033 0.027 0.020
1 Cb.d l 0.036 0.018 0.027 0.027 0.018 0.027 0.033 0.023
0.95 Ca.d l 0.040 0.020 0.021 0.030 0.028 0.036 0.031 0.022
0.95 Cb.d l 0.033 0.016 0.025 0.024 0.015 0.024 0.031 0.021
0.9 Ca.d l 0.045 0.022 0.025 0.033 0.029 0.039 0.035 0.025
0.9 Cb.d l 0.029 0.014 0.024 0.022 0.013 0.021 0.028 0.019
0.85 Ca.d l 0.050 0.024 0.029 0.036 0.031 0.042 0.040 0.029
0.85 Cb.d l 0.026 0.012 0.022 0.019 0.011 0.017 0.025 0.017
0.8 Ca.d l 0.056 0.026 0.034 0.039 0.032 0.045 0.045 0.032
0.8 Cb.d l 0.023 0.011 0.020 0.016 0.009 0.015 0.022 0.015
0.75 Ca.d l 0.061 0.028 0.040 0.043 0.033 0.048 0.051 0.036
0.75 Cb.d l 0.019 0.009 0.018 0.013 0.007 0.012 0.020 0.013
0.7 Ca.d l 0.068 0.030 0.046 0.046 0.035 0.051 0.058 0.040
0.7 Cb.d l 0.016 0.007 0.016 0.011 0.005 0.009 0.017 0.011
0.65 Ca.d l 0.074 0.032 0.054 0.050 0.036 0.054 0.065 0.044
0.65 Cb.d l 0.013 0.006 0.014 0.009 0.004 0.007 0.014 0.009
0.6 Ca.d l 0.081 0.034 0.062 0.053 0.037 0.056 0.073 0.048
0.6 Cb.d l 0.010 0.004 0.011 0.007 0.003 0.006 0.012 0.007
0.55 Ca.d l 0.088 0.035 0.071 0.056 0.038 0.058 0.081 0.052
0.55 Cb.d l 0.008 0.003 0.009 0.005 0.002 0.004 0.009 0.005
0.5 Ca.d l 0.095 0.037 0.080 0.059 0.039 0.061 0.089 0.056
0.5 Cb.d l 0.006 0.002 0.007 0.004 0.001 0.003 0.007 0.004

Table 12.5 Coefficients for live load positive moments in slabs


Ma.pos.l l = Ca.l l w Ln2
Mb.pos.l l = Cb.l l w Ln2 Where ( w ) = total uniform live load
Ratio Case 1 Case 2 Case 3 Case 4 Case 5 Case 6 Case 7 Case 8
m = L a / Lb
1 Ca.l l 0.036 0.027 0.027 0.032 0.032 0.035 0.032 0.028
1 Cb.l l 0.036 0.027 0.032 0.032 0.027 0.032 0.035 0.030
0.95 Ca.l l 0.040 0.030 0.031 0.035 0.034 0.038 0.036 0.031
0.95 Cb.l l 0.033 0.025 0.029 0.029 0.024 0.029 0.032 0.027
0.9 Ca.l l 0.045 0.034 0.035 0.039 0.037 0.042 0.040 0.035
0.9 Cb.l l 0.029 0.022 0.027 0.026 0.021 0.025 0.029 0.024
0.85 Ca.l l 0.050 0.037 0.040 0.043 0.041 0.046 0.045 0.040
0.85 Cb.l l 0.026 0.019 0.024 0.023 0.019 0.022 0.026 0.022
0.8 Ca.l l 0.056 0.041 0.045 0.048 0.044 0.051 0.051 0.044
0.8 Cb.l l 0.023 0.017 0.022 0.020 0.016 0.019 0.023 0.019
0.75 Ca.l l 0.061 0.045 0.051 0.052 0.047 0.055 0.056 0.049
0.75 Cb.l l 0.019 0.014 0.019 0.016 0.013 0.016 0.020 0.016
0.7 Ca.l l 0.068 0.049 0.057 0.057 0.051 0.060 0.063 0.054
0.7 Cb.l l 0.016 0.012 0.016 0.014 0.011 0.013 0.017 0.014
0.65 Ca.l l 0.074 0.053 0.064 0.062 0.055 0.064 0.070 0.059
0.65 Cb.l l 0.013 0.010 0.014 0.011 0.009 0.010 0.014 0.011
0.6 Ca.l l 0.081 0.058 0.071 0.067 0.059 0.058 0.077 0.065
0.6 Cb.l l 0.010 0.007 0.011 0.009 0.007 0.008 0.011 0.009
0.55 Ca.l l 0.088 0.062 0.080 0.072 0.063 0.073 0.085 0.070
0.55 Cb.l l 0.008 0.006 0.009 0.007 0.005 0.006 0.009 0.007
0.5 Ca.l l 0.095 0.066 0.088 0.077 0.067 0.078 0.092 0.076
0.5 Cb.l l 0.006 0.004 0.007 0.005 0.004 0.005 0.007 0.005

Table 12.6 Ratio of load W in La and Lb direction for shear in slab and load on supports.
Ratio Case 1 Case 2 Case 3 Case 4 Case 5 Case 6 Case 7 Case 8
m = L a / Lb
1 Wa 0.50 0.50 0.17 0.50 0.83 0.71 0.29 0.33
1 Wb 0.50 0.50 0.83 0.50 0.17 0.29 0.71 0.67
0.95 Wa 0.55 0.55 0.20 0.55 0.86 0.75 0.33 0.38
0.95 Wb 0.45 0.45 0.80 0.45 0.14 0.25 0.67 0.62
0.9 Wa 0.60 0.60 0.23 0.60 0.88 0.79 0.38 0.43
0.9 Wb 0.40 0.40 0.77 0.40 0.12 0.21 0.62 0.57
0.85 Wa 0.66 0.66 0.28 0.66 0.90 0.83 0.43 0.49
0.85 Wb 0.34 0.34 0.72 0.34 0.10 0.17 0.57 0.51
0.8 Wa 0.71 0.71 0.33 0.71 0.92 0.86 0.49 0.55
0.8 Wb 0.29 0.29 0.67 0.29 0.08 0.14 0.51 0.45
0.75 Wa 0.76 0.76 0.39 0.76 0.94 0.88 0.56 0.61
0.75 Wb 0.24 0.24 0.61 0.24 0.06 0.12 0.44 0.39
0.7 Wa 0.81 0.81 0.45 0.81 0.95 0.91 0.62 0.68
0.7 Wb 0.19 0.19 0.55 0.19 0.05 0.09 0.38 0.32
0.65 Wa 0.85 0.85 0.53 0.85 0.96 0.93 0.69 0.74
0.65 Wb 0.15 0.15 0.47 0.15 0.04 0.07 0.31 0.26
0.6 Wa 0.89 0.89 0.61 0.89 0.97 0.95 0.76 0.80
0.6 Wb 0.11 0.11 0.39 0.11 0.03 0.05 0.24 0.20
0.55 Wa 0.92 0.92 0.69 0.92 0.98 0.96 0.81 0.85
0.55 Wb 0.08 0.08 0.31 0.08 0.02 0.04 0.19 0.15
0.5 Wa 0.94 0.94 0.76 0.94 0.99 0.97 0.86 0.89
0.5 Wb 0.06 0.06 0.24 0.06 0.01 0.03 0.14 0.11

* A crosshatched edge indicates that the slab continues across,or is fixed at the support; an unmarked edge
indicates a support at which torsional resistance is negligible.
Case 9

0.061
0.033
0.065
0.029
0.068
0.025
0.072
0.021
0.075
0.017
0.078
0.014
0.081
0.011
0.083
0.008
0.085
0.006
0.086
0.005
0.088
0.003

Case 9

0.023
0.020
0.024
0.017
0.026
0.015
0.028
0.013
0.029
0.010
0.031
0.007
0.033
0.006
0.034
0.005
0.036
0.004
0.035
0.003
0.038
0.002

Case 9

0.030
0.028
0.032
0.025
0.036
0.022
0.039
0.020
0.042
0.017
0.046
0.013
0.050
0.011
0.054
0.009
0.059
0.007
0.063
0.006
0.067
0.004

Case 9
0.67
0.33
0.71
0.29
0.75
0.25
0.79
0.21
0.83
0.17
0.86
0.14
0.89
0.11
0.92
0.08
0.94
0.06
0.95
0.05
0.97
0.03

nmarked edge
ONE WAY SLAB DESIGN

Subject : Date : 6-May-23

Concrete strength, f'c' = 3 ksi


Yield Strength of steel fy = 40 ksi
Strength reduction factor Ø
Clear span length, L = 3 ft. 0.9 = Ø Flexure
0.85 = Ø Shear & Torsion
Own Wt. of slab, DL = 50 psf 1.4 = Safety factor of D-L
Super Dead Load, SDL = 30 psf 1.7 = Safety factor of L-L
Live Load, LL = 40 psf

Total factored load, Wu = 180 psf

Defined type of slab = 1 ( 1 ) One end continuous = L/24


Min Thickness of Slab h = 1.5 ( 2 ) Both end continuous = L/28

Applied thickness of slab, h = 4 in.


Concrete Clear Cover = 1 in.

Maximum steel ratio, rmax = 0.0278 , As(max) = 0.936 in2/ ft


Minimum steel ratio, rmin = 0.0020 , As(min) = 0.067 in2/ ft

Design moment at critical section may be found using the ACI moment coefficients.

At interior support: Mu = 1/12 Wu L2


= 0.135 ft-kips

At midspan: Mu = 1/14 Wu L2
= 0.116 ft-kips

At exterior support: Mu = 1/12 Wu L2


= 0.135 ft-kips

At interior support:

Provided main steel, # 10 mm F @ 8 in. c/c


As,prov = 0.1826 in2/ ft
a = 0.2387 in
Check Ris. Mu = 1.469 ft-kips > Mu = 0.14 ft-kips OK
Check Req Eff 'd' = 0.85 in. < Eff 'd' = 2.802 in. OK
( Continued-1 )
At midspan:

Provided main steel, #


10 mm F @ 8 in. c/c
As,prov = 0.1826 in2/ ft
a = 0.2387 in
Check Ris. Mu = 1.470 ft-kips > Mu = 0.12 ft-kips OK
Check Req Eff 'd' = 0.79 in. < Eff 'd' = 2.803 in. OK

At exterior support:

Provided main steel, #


10 mm F @ 8 in. c/c
As,prov = 0.1826 in2/ ft
a = 0.2387 in
Check Ris. Mu = 1.470 ft-kips > Mu = 0.14 ft-kips OK
Check Req Eff 'd' = 0.85 in. < Eff 'd' = 2.803 in. OK

Distribution steel # 10 mm F @ 8 in. c/c


As,prov = 0.1826 in2/ ft > As(min) = 0.067 in2/ ft OK

Check Shear Force


Factored shear force, Vu = 1.15 Wu L/2 - Wu d
= 0.268 kips
Nominal shear strength of the concrete slab,
fVc = 3.13 kips > Vu = 0.268 kips OK
1. Spans are approximately equal : longer span ≤ 1.2 (shorter span)
2. Loads are uniformly distributed.
3. The ratio (live load/dead load ) is less than or equal to 3.
Maximum Spacing of Main Steel : 3h or 18"
Maximum Spacing of Distrubution Steel : 5h or 18"

1/12 1/14 1/12 1/12 1/16 1/12 1/12

( As = 12 x Ab / S )
( a = As fy / 0.85 fc' b )
( Mu = F As fy ( d - a / 2 ))
(Mu = F r fy b d2 ( 1 - ( 0.59 r fy / fc')))
ONE WAY SLAB DESIGN

Subject : Date : 6-May-23

Concrete strength, f'c' = 3 ksi


Yield Strength of steel fy = 40 ksi
Strength reduction factor Ø
Clear span length, L = 10.16 ft. 0.9 = Ø Flexure
0.85 = Ø Shear & Torsion
Own Wt. of slab, DL = 50 psf 1.2 = Safety factor of D-L
Super Dead Load, SDL = 20 psf 1.6 = Safety factor of L-L
Live Load, LL = 60 psf

Total factored load, Wu = 180 psf

Defined type of slab = 2 ( 1 ) One end continuou = L/24


Min Thickness of Slab h = 4.5 ( 2 ) Both end continuou = L/28

Applied thickness of slab, h = 4 in.


Concrete clear cover = 0.75 in.

Maximum steel ratio, rmax = 0.0278 , As(max) = 1.02 in2/ ft


Minimum steel ratio, rmin = 0.0020 , As(min) = 0.073 in2/ ft

Design moment at critical section may be found using the ACI moment coefficients.

At interior support: Mu = 1/11 Wu L2


= 1.689 ft-kips

At midspan: Mu = 1/16 Wu L2
= 1.161 ft-kips

At exterior support: Mu = 1/11 Wu L2


= 1.689 ft-kips

At interior support:

Provided main steel, # 10 mm F @ 6 in. c/c


As,prov = 0.2435 in2/ ft
a = 0.3183 in
Check Ris. Mu = 2.114 ft-kips > Mu = 1.69 ft-kips OK
Check Req Eff 'd' = 2.73 in. < Eff 'd' = 3.053 in. OK
( Continued-1 )
At midspan:

Provided main steel, #


10 mm F @ 6 in. c/c
As,prov = 0.2435 in2/ ft
a = 0.3183 in
Check Ris. Mu = 2.114 ft-kips > Mu = 1.16 ft-kips OK
Check Req Eff 'd' = 2.26 in. < Eff 'd' = 3.053 in. OK

At exterior support:

Provided main steel, #


10 mm F @ 6 in. c/c
As,prov = 0.2435 in2/ ft
a = 0.3183 in
Check Ris. Mu = 2.114 ft-kips > Mu = 1.69 ft-kips OK
Check Req Eff 'd' = 2.73 in. < Eff 'd' = 3.053 in. OK

Distribution steel # 10 mm F @ 8 in. c/c


As,prov = 0.1826 in2/ ft > As(min) = 0.073 in2/ ft OK

Check Shear Force


Factored shear force, Vu = 1.15 Wu L/2 - Wu d
= 1.006 kips
Nominal shear strength of the concrete slab,
fVc = 3.41 kips > Vu = 1.006 kips OK
1. Spans are approximately equal : longer span ≤ 1.2 (shorter span)
2. Loads are uniformly distributed.
3. The ratio (live load/dead load ) is less than or equal to 3.
Maximum Spacing of Main Steel : 3h or 18"
Maximum Spacing of Distrubution Steel : 5h or 18"
Case - 1
Discontinuous end
Unrestrained 0 1/11
Spandrel 1/24 1/14 1/10 1/11 1/16 1/11 1/11
Column 1/16 1/14

Case - 2
Discontinuous end
Unrestrained 0 1/11 1/11 0
Spandrel 1/24 1/14 1/9 1/9 1/14 1/24
Column 1/16 1/14 1/14 1/16

Defined Case of Slab


1,4

Case - 1
One end Continuous Both end Continuous
Unrestrained 1,1
Spandrel 1,2 1,4
Column 1,3

Case - 2
One end Continuous
Unrestrained 2,1
Spandrel 2,2
Column 2,3

( As = 12 x Ab / S )
( a = As fy / 0.85 fc' b )
( Mu = F As fy ( d - a / 2 ))
(Mu = F r fy b d2 ( 1 - ( 0.59 r fy / fc')))
CANTILEVER SLAB DESIGN

Subject : Date : 6-May-23

Concrete strength, f'c' = 3 ksi


Yield Strength of steel fy = 40 ksi

Span length, L = 3.5 ft. Strength reduction factor Ø


0.9 = Ø Flexure
Own Wt. of slab, DL = 62.5 psf 0.75 = Ø Shear & Torsion
Super Dead Load, SDL = 30 psf 1.2 = Safety factor of D-L
Live Load, LL = 40 psf 1.6 = Safety factor of L-L
Point Load SDL 150 p/f

Total factored load, Wu = 175 psf

Min Thickness of Slab h = 4.2

Applied thickness of slab, h = 5 in.


Concrete clear cover = 1 in.

Maximum steel ratio, rmax = 0.0278 , As(max) = 1.271 in2/ ft


Minimum steel ratio, rmin = 0.0020 , As(min) = 0.091 in2/ ft

Design Moment Mu = Wu L2/2 + P L


= 1.597 ft-kips

Provided main steel, #


10 mm F @ 6 in. c/c
As,prov = 0.2435 in2/ ft
a = 0.3183 in
Check Ris. Mu = 2.662 ft-kips > Mu = 1.597 ft-kips OK
Check Req Eff 'd' = 2.95 in. < Eff 'd' = 3.803 in. OK

Distribution steel # 10 mm F @ 6 in. c/c


As,prov = 0.2435 in2/ ft > As(min) = 0.091 in2/ ft OK

Check Shear Force


Factored shear force, Vu = Wu L + P - Wu d
Vu = 0.707 kips
Nominal shear strength of the concrete slab,
fVc = 3.750 kips > Vu = 0.707 kips OK
SIMPLY SUPPORTED SLAB DESIGN

Subject : Date : 6-May-23

Concrete strength, f'c' = 3 ksi


Yield Strength of steel fy = 60 ksi

Clear span length, L = 11.5 ft. Strength reduction factor Ø


0.9 = Ø Flexure
Own Wt. of slab, DL = 87.5 psf 0.85 = Ø Shear & Torsion
Super Dead Load, SDL = 20 psf 1.2 = Safety factor of D-L
Live Load, LL = 100 psf 1.6 = Safety factor of L-L

Total factored load, Wu = 289 psf

Min Thickness of Slab h = 6.9

Applied thickness of slab, h = 7 in.


Concrete clear cover = 0.75 in.

Maximum steel ratio, rmax = 0.0160 , As(max) = 1.157 in2/ ft


Minimum steel ratio, rmin = 0.0018 , As(min) = 0.13 in2/ ft

Design Moment Mu = Wu L2/8


= 4.778 ft-kips

Provided main steel, #


12 mm F @ 6 in. c/c
As,prov = 0.3506 in2/ ft
a = 0.6875 in
Check Ris. Mu = 8.946 ft-kips > Mu = 4.78 ft-kips OK
Check Req Eff 'd' = 4.40 in. < Eff 'd' = 6.014 in. OK

Distribution steel # 10 mm F @ 10 in. c/c


As,prov = 0.1461 in2/ ft > As(min) = 0.13 in2/ ft OK

Check Shear Force


Factored shear force, Vu = Wu L/2 - Wu d
Vu = 1.517 kips
Nominal shear strength of the concrete slab,
fVc = 6.720 kips > Vu = 1.517 kips OK