Cable Schedule for Induction Furnace - FES

AIL Doc. No. AIL-221080-CS-R0


End Client M/s. Mayavaram Rolling Mill Pvt. Ltd
Description Cable Schedule for 15 TON Furnace

ACTUAL
REQUIRED
SL. NO. EMANATING FROM TERMINATING AT CABLE TYPE & SIZE LENGTH IN MARGIN
LENGTH
METER
SIZE TYPE
1 Hood Bearing 2.2 kW Main Panel by Client 3C X 2.5 sq.mm2 (Cu) CONTROL Suit at site
2 ID Fan motor 250kW Main Panel by Client 2 X 3C X 90 sq.mm2 (CU) POWER Suit at site
3 RAV motor 0.37 KW (Spark Arrestor) Main Panel by Client 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
4 RAV motor 0.37 KW (Bag Filter-1) Main Panel by Client 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
5 RAV motor 0.37 KW (Bag Filter-2) Main Panel by Client 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
6 RAV motor 0.37 KW (Bag Filter-3) Main Panel by Client 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
7 RAV motor 0.37 KW (Bag Filter-4) Main Panel by Client 3C X 1.5 sq.mm2 (Cu) POWER Suit at site

8 Pn outlet damper-1 Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
9 Pn outlet damper-2 Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
10 Pn outlet damper-3 Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
11 Pn outlet damper-4 Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
12 Limit switch for Pn outlet damper-1 Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
13 Limit switch for Pn outlet damper-2 Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
14 Limit switch for Pn outlet damper-3 Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
15 Limit switch for Pn outlet damper-4 Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
16 Pressure Switch Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) CONTROL Suit at site
17 DP switch Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) CONTROL Suit at site
18 Temperature Controller Timer Panel by AIL 3C X 1.5 sq.mm2 (Shield C) POWER Suit at site
19 Pn dilution damper Timer Panel by AIL 3C X 1.5 sq.mm2 (Cu) POWER Suit at site
20 Solenoid Valve 01 to 12 for Compartment - 1 Timer Panel by AIL 15C X 1.5 sq.mm2 (Cu) POWER Suit at site
21 Solenoid Valve 01 to 12 for Compartment - 2 Timer Panel by AIL 15C X 1.5 sq.mm2 (Cu) POWER Suit at site
22 Solenoid Valve 01 to 12 for Compartment - 3 Timer Panel by AIL 15C X 1.5 sq.mm2 (Cu) POWER Suit at site
23 Solenoid Valve 01 to 12 for Compartment - 4 Timer Panel by AIL 15C X 1.5 sq.mm2 (Cu) POWER Suit at site
Total
Prepared By: Shashikant
Approved By: Mohan

Note:
ALL THE ABOVE SIZE MENTIONED ARE FOR COPPER CABLE IF YOU WANT TO USE ALUMINIUM CONSIDER 2 RATING HIGHER TO THE MENTIONED
1
SIZES.
2 MAIN CONTROL PANEL BY CLIENT SCOPE
3 TIMER PANEL FOR PULSING BY ASWATHI