Professional Documents
Culture Documents
REHABILITATION OF
UNIVERSITY OF NUEVA
CACERES
(BUILDING A, B, C & D)
12 April 2024
Dear Sir,
We are pleased to submit to your good office the design of the rehabilitation of the electrical
system for the incoming supply up to feeder protection in BLDG ABCD University of Nueva
Caceres. The design Includes:
The above designs were based on the Job description and specifications required by your
company. These schemes for your perusal and acceptance.
Sincerely yours,
The present electrical system of University of Nueva Caceres is 3 phase, 3 wire system. Its power
supply is coming from a transformer rated 2-75 KVA, secondary open delta connection (provided by
Penelco). After the KWhr meter tapped on the main feeder via current transformer, its electrical
loads are subdivided into two feeders. Feeder 1 is protected by 800 AT circuit breaker, in which the
electrical loads are Building A, Building A 4 th floor and guard house/ covered court. While Feeder 2 is
protected by 800 AT circuit breaker in which the electrical loads are Building B, Building C, Building C
4th floor, Building D, Air conditioning unit and Board room. Air Conditioning Unit and Unknown load
are connected on the line side of Feeder 2. (See table 1 below).
FEEDER 1 FEEDER 2
SIZE OF FEEDER ___MM2 SIZE OF FEEDER ___MM2
___AT / ___ AT / ___AT ___AT / ___ AT / ___AT
LOAD AREA AMPERE LOAD AREA AMPERE LOAD AREA AMPERE
BLDG A 87.3 BLDG B 41 ACU 14
BLDG A 4 FLR.
th
41.3 BLDG C 73 39
GUARD HOUSE / BLDG C 4 th FLR. 78 ACU
10
COVERED COURT BLDG D 160 BOARD ROOM 28
The existing two-unit transformer serving the University of Nueva Caceres are rated 75 KVA
respectively. Mathematically, it can serve a maximum load of (75,000 √3) /240 V = 541.27 Amperes.
The measured values were gathered using clamp Ammeter during site visit. The capacities of the
Main Distribution Panel in amperes are the minimum requirements from latest edition of Philippine
Electrical Code for the stated feeder sizes.
TABLE 3 COMPATABILITY OF CONDUCTORS AND MAIN DISTRIBURION PANEL
ALLOW ABLE CURRENT COMPATIBLE EXISTING MEASURED
AREA ACTUAL SIZE OF FEEDER REMARKS
(AMPACITIES) PROTECTION (ACB) PROTECTION (ACB) AMPERE
OV ERATED CB &
MDP 3 - 20 0 mm2 THHN/THWN 2 55 AMPERES 5 00 AT 1 00 0 AT 4 01
OV ERLOAD
B. UNDERSIZED CONDUCTORS/ OVERRATED CIRCUIT BREAKERS
Each conductor size has allowable ampacity required by the Philippine Electrical Code as maximum
current it can carry. Any amount of current that exceeds the required ampacities may be unsafe for
any electrical installation and usage. The conductor (feeder) should be protected by circuit breaker
that compatible to the required ampacities of the conductor. So that when the current exceeds the
required ampacity, the breaker will trip before the conductor starts to melt its insulators.
Table 3 shows the incompatibility settings in all areas, between the existing conductors with their
corresponding circuit breaker protections. All of the existing breakers are way over rated causing
them not to trip as intended when the circuit experience an overload, leading to overheating of the
wiring and increase risk of electrical fires.
Loose connections, improper conductor splicing and buried conductor with no conduits making
exposed in moisture are the initial seen reason that causes overheating.
RISKY, PERPLEXING AND
IMPROPER EXISTING ONE LINE
DIAGRAM
EXISTING ONE LINE DIAGRAM
SITE INVESTIGATION AND DATA
MEASUREMENTS
HAPHAZARD SERVICE ENTRANCE / ELECTRICAL ROOM
- Electrical rooms contain high-voltage equipment and wiring, which can pose serious
safety hazards if not properly organized and maintained. Electrical equipment
generates heat, and combustible materials stored nearby can fuel a fire, leading to
rapid escalation and extensive damage.
- It is difficult for maintenance personnel to access equipment for repairs, inspections, or
upgrades. Limited access can impede troubleshooting efforts and prolong downtime in
the event of a malfunction.
-
Changes or additions to the electrical system that are not documented in an updated electrical plan
can create safety hazards. Without accurate documentation, individuals working on the electrical
system may not be aware of potential risks, such as overloaded circuits or improperly installed
equipment. Without an updated electrical plan, it may be challenging to efficiently manage
resources such as materials, labor, and time. Contractors may need to spend additional time and
effort troubleshooting or making modifications based on outdated information, leading to delays
and increased costs.
LOAD MEASUREMENT
EXPOSED OUTDOOR UNDER GROUND FEEDER
The conduits and cables are exposed and not buried properly in the ground. It can lead to
deterioration, corrosion, and eventually failure of the wire. This can result in short circuits,
electrical shocks, or even fires.
SEVERAL LOCATIONS OF FEEDER
PROTECTIONS
(CIRCUIT BREAKERS / PANEL
BOARDS)
LOCATION OF PANEL BOARDS
BUILDING A PANEL BOARDS
BUILDING B PANEL BOARDS
BUILDING C PANEL BOARDS
BUILDING D PANEL BOARDS
PROPOSED LOCATION OF PANEL BOARDS
BUILDING A PANEL BOARDS
BUILDING B PANEL BOARDS
BUILDING C PANEL BOARDS
BUILDING D PANEL BOARDS
PROPOSED SINGLE LINE DIAGRAM
PROPOSED SCHEME
AMPERE TRIP RATING AND WIRE SIZE:
GUARD HOUSE /
60 2 - 14mm2 THHN/THWN
COVERED COURT
SPARE 125
SPARE 125
TRANSFORMER:
TRANSFORMER 230V, 3 – 75KVA
DISTRIBUTION TRANSFORMER, OIL EMERSED
13.2KV/7.62KV WYE PRIMARY
230V DELTA SECONDARY
ELECTRICAL PLAN:
UPDATE ELECTRICAL PLAN (AS-BUILT DRAWING).