You are on page 1of 48

Question 1

Correct
Mark 1.00 out of 1.00

Flag question
Question text
Which of the following statements is NOT correct?

a.
In a multi-family dwelling, each occupant shall have ready access to all overcurrent devices.

b.
Overcurrent devices shall be located where they will not be exposed to physical damage

c.
Overcurrent devices shall be readily accessible.

d.
Overcurrent devices may be located inside clothes closets
Feedback
The correct answer is: Overcurrent devices may be located inside clothes closets
Question 2
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
The symbol S2P shall mean ___.

a.
a two-position switch

b.
a two-way switch

c.
a two-pole switch

d.
duplex switch
Feedback
The correct answer is: a two-pole switch
Question 3
Incorrect
Mark 0.00 out of 1.00
Flag question
Question text
In dwellings, lighting outlets shall be permitted to be controlled by occupancy sensors provided they are
___.

a.
located in the hallway

b.
automatic

c.
within 1 800 m of the door(s)

d.
equipped with a manual override
Feedback
The correct answer is: equipped with a manual override
Question 4
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Which of the following statements on lighting fixtures NOT correct?

a.
Metal fixtures and enclosures rated at 250 V and installed up in the ceiling shall be grounded.

b.
Stranded conductors shall be used in wiring a fixture supporting chain and other movable flexible parts.

c.
Outdoor lighting fixtures and associated equipment shall be permitted to be supported by trees.

d.
Fixtures and lighting equipment operating at over 250 V shall be grounded.
Feedback
The correct answer is: Fixtures and lighting equipment operating at over 250 V shall be grounded.
Question 5
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Electrical continuity is required by the Code for metallic conduit ___. `

a.
to reduce static electricity

b.
to assure equipment grounding

c.
to trace electrical wiring

d.
to reduce inductive heat
Feedback
The correct answer is: to assure equipment grounding
Question 6
Correct
Mark 1.00 out of 1.00

Flag question
Question text
What is the reason the Code requires each separate phase conductor to be located in the same
raceway?

a.
To improve workmanship

b.
To provide identification of a circuit

c.
To reduce inductive heat

d.
To assure balance resistance
Feedback
The correct answer is: To reduce inductive heat
Question 7
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The letters MTR on the drawing would indicate ___.
a.
middle of run

b.
motor

c.
manufacture

d.
motor-tie-resistor
Feedback
The correct answer is: motor
Question 8
Correct
Mark 1.00 out of 1.00

Flag question
Question text
How many 1.5 A lighting fixtures can be connected to a 20-A non-continuous duty branch circuit?

a.
14

b.
13

c.
15

d.
12
Feedback
The correct answer is: 13
Question 9
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Branch circuits are classified according to the maximum ___.

a.
load being served
b.
voltage across it

c.
setting of the overcurrent device

d.
power consumed
Feedback
The correct answer is: setting of the overcurrent device
Question 10
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
Most wires used in residential house wiring are usually insulated by ___.

a.
varnished

b.
asbestos

c.
thermoplastic

d.
cambric

e.
cotton
Feedback
The correct answer is: asbestos
Question 11
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Guest rooms and suites that are provided with ___ shall have branch circuits and outlets installed to
meet the rules for dwelling units.

a.
electric appliances

b.
permanent provisions for cooking

c.
air conditioning

d.
electric heat
Feedback
The correct answer is: permanent provisions for cooking
Question 12
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The electrical plans for residential house (single family dwelling) include the following items EXCEPT one.
Which one is this?

a.
Substation Plan

b.
Layout and wiring plan for general lighting and receptacle outlets

c.
Floor plan showing location of service

d.
Location Plan
Feedback
The correct answer is: Substation Plan
Question 13
Correct
Mark 1.00 out of 1.00

Flag question
Question text
A panelboard for residence shall NOT be installed in ___.

a.
a clothes closet or bathroom
b.
a basement

c.
a garage

d.
an uncovered patio
Feedback
The correct answer is: a clothes closet or bathroom
Question 14
Correct
Mark 1.00 out of 1.00

Flag question
Question text
A lighting fixture is to be controlled independently from two different locations. The type of switch
required in each of the two locations is a ___.

a.
single-pole, double-throw

b.
single-pole, single-throw

c.
double-pole, single-throw

d.
double-pole, double-throw
Feedback
The correct answer is: single-pole, double-throw
Question 15
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The electrical drawing of a single-family dwelling shall show the following EXCEPT ___.

a.
floor plan

b.
one-line diagram
c.
computation of illumination

d.
location plan
Feedback
The correct answer is: computation of illumination
Question 16
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Receptacles in residential wiring are regularly connected in ___.

a.
Diagonal

b.
parallel

c.
series

d.
perpendicular
Feedback
The correct answer is: parallel
Question 17
Correct
Mark 1.00 out of 1.00

Flag question
Question text
___ is a wiring method using knobs, tubes, and flexible non-metallic tubing for the protection and
support of single insulated conductors concealed in hollow spaces of walls and ceilings of buildings.

a.
Open wiring with knobs, tubes, etc.

b.
Concealed knob and tube wiring

c.
Open wiring on insulators

d.
Knob and tube wiring
Feedback
The correct answer is: Concealed knob and tube wiring
Question 18
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The advantage(s) of a 4-wire, three-phase source over a 3-wire, three-phase source is/are ___. (I.) two
voltage levels, (II.) a grounded neutral, (III.) less copper required

a.
II only

b.
I only

c.
III only

d.
I and II
Feedback
The correct answer is: I and II
Question 19
Correct
Mark 1.00 out of 1.00

Flag question
Question text
A dwelling unit has a front entrance on the north side of the house along with an attached garage with a
2.5 m wide door, also a back-entrance door on the south side of the house. How many lighting outlets
are required for these outdoor entrances?

a.
3

b.
1

c.
2

d.
none of these
Feedback
The correct answer is: 2
Question 20
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Illumination shall be provided for working spaces containing battery systems. The lighting outlets shall
not be controlled by ___ means only.

a.
timers

b.
low voltage

c.
automatic

d.
photocell
Feedback
The correct answer is: automatic
Question 21
Correct
Mark 1.00 out of 1.00

Flag question
Question text
At least one receptacle outlet per unit, accessible at grade level, shall be installed at the front and back
on ___.

a.
motels

b.
commercial buildings

c.
one- and two-family dwellings
d.
office buildings only
Feedback
The correct answer is: one- and two-family dwellings
Question 22
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The branch-circuit loads specified by the Code for lighting and receptacles are considered ___.

a.
peak loads

b.
maximum loads

c.
minimum loads

d.
loads to be served
Feedback
The correct answer is: minimum loads
Question 23
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
In a 3-phase, 4-wire cable, the cross-sectional area of neutral conductor is ___.

a.
double the area of phase conductor

b.
more than the area of phase conductor

c.
equal to the area of phase conductor

d.
less than the area of phase conductor
Feedback
The correct answer is: equal to the area of phase conductor
Question 24
Correct
Mark 1.00 out of 1.00

Flag question
Question text
A lighting fixture under a canopy is considered to be in a ___ location.

a.
dry

b.
hazardous

c.
wet

d.
damp
Feedback
The correct answer is: damp
Question 25
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
The Code requires that a conduit with more than two conductors to be filled to a maximum of 40
percent. The reason for the limitation on the fill area is ___.

a.
to reduce the heat from induction

b.
to allow for future fill

c.
to make the pulling of wires easier without abrasion

d.
for better circulation of air
Feedback
The correct answer is: to make the pulling of wires easier without abrasion
Question 26
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
For a one-family dwelling, at least one receptacle outlet is required in each ___.

a.
detached garage with power

b.
all of these

c.
basement

d.
attached garage
Feedback
The correct answer is: all of these
Question 27
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
How do you call a diagram showing the physical location of the components such as coils, contacts,
motors and the like in their actual positions?

a.
Ladder diagram

b.
Schematic diagram

c.
Power flow diagram

d.
Power flow diagram
Feedback
The correct answer is: Power flow diagram
Question 28
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
To open a single-throw switch, the switch should be mounted so that the switch blade must move ___.

a.
twice

b.
slowly

c.
downward

d.
upward
Feedback
The correct answer is: downward
Question 29
Correct
Mark 1.00 out of 1.00

Flag question
Question text
A dwelling unit is ___.

a.
a single unit, providing complete and independent living facilities for one or more persons, including
permanent provisions for living, sleeping, cooking and sanitation

b.
one or more rooms used by one or more persons

c.
one unit of an apartment

d.
one or more rooms with space for eating, living, and sleeping
Feedback
The correct answer is: a single unit, providing complete and independent living facilities for one or more
persons, including permanent provisions for living, sleeping, cooking and sanitation
Question 30
Correct
Mark 1.00 out of 1.00
Flag question
Question text
In kitchens of dwelling units, a receptacle outlet shall be installed at each wall countertop space that is
at LEAST ___ or wider.

a.
450 mm

b.
300 mm

c.
750 mm

d.
600 mm
Feedback
The correct answer is: 300 mm
Question 31
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
Electrical symbol represented by a rectangle with a circle inside.

a.
Fluorescent lamp outlet

b.
Lighting panelboard

c.
Safety switch

d.
Incandescent lamp outlet
Feedback
The correct answer is: Fluorescent lamp outlet
Question 32
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
To measure the area of a dwelling to determine the lighting load, the following dimensions are used:

a.
The area 150 mm (6 inches) from the inside walls

b.
The floor area computed from the inside dimension

c.
The floor area computed from the outside dimension

d.
The cubic feet of each room
Feedback
The correct answer is: The floor area computed from the outside dimension
Question 33
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Electrical symbol represented by a circle with two solid lines inside it.

a.
Antenna outlet

b.
Cooking range outlet

c.
Single convenience outlet

d.
Special purpose outlet
Feedback
The correct answer is: Single convenience outlet
Question 34
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The minimum allowable number of 120-volt, 15-ampere, 2-wire lighting branch circuits required for
residence 70 feet by 30 feet are ___.
a.
5

b.
3

c.
2

d.
4
Feedback
The correct answer is: 4
Question 35
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Branch lighting circuits shall be protected by overcurrent devices NOT rated more than ___.

a.
40 A

b.
50 A

c.
30 A

d.
20 A
Feedback
The correct answer is: 20 A
Question 36
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Single-phase cord-and-plug-connected room air conditioners shall be provided with factory-installed
LCDI or AFCI protection, the LCDI or AFCI protection shall be an integral part of the attachment plug or
be located in the power supply cord within ___ mm of the attachment plug.
a.
350

b.
300

c.
760

d.
500
Feedback
The correct answer is: 300
Question 37
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Intermediate metal conduit shall be shipped in standard lengths of ___ mm.

a.
3 000

b.
2 000

c.
5 000

d.
4 000
Feedback
The correct answer is: 3 000
Question 38
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
The rating of the electric service for a one-family residence shall not be less than ___.

a.
100 amperes when the initial load is 10 kW or less
b.
100 amperes

c.
60 amperes

d.
150 amperes when the initial load is 15 kW or less
Feedback
The correct answer is: 60 amperes
Question 39
Correct
Mark 1.00 out of 1.00

Flag question
Question text
A room air conditioner rated 3-phase or rated over 250 volts shall be connected ___.

a.
with a grounding plug

b.
directly to a wiring method recognized in Chapter 3

c.
with a 3-prong attachment plug

d.
with a 4-prong attachment plug
Feedback
The correct answer is: directly to a wiring method recognized in Chapter 3
Question 40
Correct
Mark 1.00 out of 1.00

Flag question
Question text
DPDT stands for ___.

a.
double pole duplex switch

b.
none of these
c.
double pole double throw switch

d.
duplex switch
Feedback
The correct answer is: double pole double throw switch
Question 41
Correct
Mark 1.00 out of 1.00

Flag question
Question text
To provide for a small appliance load in a dwelling unit, the feeder should be computed at ___.

a.
3 000 watts

b.
2 400 watts

c.
1 500 watts

d.
3 600 watts
Feedback
The correct answer is: 1 500 watts
Question 42
Correct
Mark 1.00 out of 1.00

Flag question
Question text
When applying the demand factors of Table 2.20.3.17, in no case can the feeder or service demand load
be less than the sum of the ___.

a.
heat and air conditioning loads

b.
total receptacle load

c.
largest two kitchen equipment loads
d.
rating of the appliance loads
Feedback
The correct answer is: largest two kitchen equipment loads
Question 43
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Appliance outlets installed for a specific appliance shall be installed within ___ mm of the intended
location of the appliance.

a.
6 000

b.
1 500

c.
1 800

d.
900
Feedback
The correct answer is: 1 800
Question 44
Correct
Mark 1.00 out of 1.00

Flag question
Question text
What is meant by “traveller wires”?

a.
Wiring to a split receptacle

b.
Out of state electrician

c.
Wiring to a door bell

d.
Two-wires between 3-way switches
Feedback
The correct answer is: Two-wires between 3-way switches
Question 45
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Air conditioning load has a demand load of ___.

a.
150 %

b.
125 %

c.
100 %

d.
80 %
Feedback
The correct answer is: 100 %
Question 46
Correct
Mark 1.00 out of 1.00

Flag question
Question text
For dwelling units, a branch circuit supplying ___ receptacle outlets are permitted to also supply
receptacle outlets in attached garage.

a.
bathroom

b.
kitchen small appliance

c.
laundry room

d.
outdoor
Feedback
The correct answer is: outdoor
Question 47
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
When calculating the demand load for a one family dwelling, what total MINIMUM volt amperes (VA)
must be included in the calculation for the small appliance and laundry circuit loads?

a.
4 500 VA

b.
1 500 VA

c.
3 000 VA

d.
6 000 VA
Feedback
The correct answer is: 3 000 VA
Question 48
Correct
Mark 1.00 out of 1.00

Flag question
Question text
S3 is a symbol used on a drawing to indicate a ___ switch.

a.
three-way

b.
flush

c.
four-way

d.
single pole
Feedback
The correct answer is: three-way
Question 49
Correct
Mark 1.00 out of 1.00

Flag question
Question text
For dwelling units, all of the following are true EXCEPT ___.

a.
the outlet for kitchen refrigerator equipment may be supplied by an individual 15 A branch circuit

b.
the clothes washer shall be supplied by a 20 A branch circuit and outlets outside the laundry area are
not permitted on this circuit

c.
bathroom receptacles shall be supplied by a 20 A branch circuit which shall have no other outlets

d.
outdoor outlets are permitted to be supplied through the small appliance branch circuits
Feedback
The correct answer is: outdoor outlets are permitted to be supplied through the small appliance branch
circuits
Question 50
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
Generally ___ wiring is used for domestic purpose.

a.
busbar

b.
batten

c.
lead covered

d.
clear
Feedback
The correct answer is: batten
Question 51
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The Code refers to low voltage as ___.

a.
120 volts

b.
12 volts

c.
600 volts and under

d.
240 volts
Feedback
The correct answer is: 600 volts and under
Question 52
Correct
Mark 1.00 out of 1.00

Flag question
Question text
In a 3Ø circuit, how many electrical degrees separate each phase?

a.
90

b.
180

c.
360

d.
120
Feedback
The correct answer is: 120
Question 53
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The PEC requires at least two small appliance branch circuits for dwelling unit. Either or both of these
two circuits shall be permitted to supply circuits in which of the following four rooms?

a.
Kitchen, dining room, recreation room and breakfast room

b.
Kitchen, dining room, breakfast room and living room

c.
Kitchen, pantry, breakfast room and hallway

d.
Kitchen, pantry, breakfast room and dining room
Feedback
The correct answer is: Kitchen, pantry, breakfast room and dining room
Question 54
Correct
Mark 1.00 out of 1.00

Flag question
Question text
How many outside receptacles, accessible at grade level, are required for a single-family dwelling?

a.
4

b.
1

c.
3

d.
2
Feedback
The correct answer is: 1
Question 55
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Temporary holiday decorative lighting installations for dwellings are permitted to be in use for NOT
MORE than ___.

a.
90 days

b.
30 days

c.
60 days

d.
120 days
Feedback
The correct answer is: 90 days
Question 56
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Which of the following is NOT true?

a.
The size of the conductor determines the rating of the circuit.

b.
Splices and joints shall be covered with an insulation equivalent to the conductor insulation.

c.
All receptacles on 15 and 20 amp branch circuits must be of the grounding type.

d.
All 15 and 20 amp receptacles installed in a dwelling bathroom shall have GFCI protection.
Feedback
The correct answer is: The size of the conductor determines the rating of the circuit.
Question 57
Correct
Mark 1.00 out of 1.00

Flag question
Question text
All branch circuits that supply 125 volt, 15 and 20 ampere outlets installed in dwelling unit ___ shall be
protected by an arc-fault circuit interrupter listed to provide protection of the entire branch circuit.
a.
all of these

b.
family and dining rooms

c.
kitchens and laundry area

d.
closets and hallways
Feedback
The correct answer is: all of these
Question 58
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
Wall-switch controlled receptacles in dwelling units in lieu of lighting outlets are allowed in all habitable
rooms except ___.

a.
kitchen and bath

b.
living and family

c.
basement and attic

d.
bedrooms
Feedback
The correct answer is: kitchen and bath
Question 59
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
When the ground resistance exceeds the allowable value of 25 ohms, the resistance can be reduced by
___. (I.) paralleling ground rods, (II.) using a longer ground rod, (III.) using a larger diameter ground rod,
(IV.) chemical treatment of the soil
a.
I,II and III only

b.
I,II,III and IV

c.
II and III only

d.
II,III and IV only
Feedback
The correct answer is: I,II,III and IV
Question 60
Correct
Mark 1.00 out of 1.00

Flag question
Question text
In general, all 125 volt and/or 250-volt, single phase, 15 and 20 amperes receptacle outlets installed in
the following listed locations of dwelling units EXCEPT ___, shall be protected by a listed ground fault
circuit interrupter.

a.
bathrooms

b.
hallways

c.
outdoors

d.
garages
Feedback
The correct answer is: hallways
Question 61
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Which of the following best describes the symbol normally used for duplex receptacles?
a.
A square box with an “X” drawn inside

b.
A circle with two parallel lines drawn through it

c.
A square box with the letter “R” next to it

d.
A circle with one line drawn through it
Feedback
The correct answer is: A circle with two parallel lines drawn through it
Question 62
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Which type of wiring has a minimum span of life?

a.
Batten wiring

b.
Cleat wiring

c.
LCC wiring

d.
Conduit pipe wiring
Feedback
The correct answer is: Cleat wiring
Question 63
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The switch symbol SRC shall mean a ___ switch.

a.
room control
b.
roller type control

c.
remote control

d.
rocker type control
Feedback
The correct answer is: remote control
Question 64
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
What is the total VA rating of 230-V, single-phase circuit supplied by a 20-A circuit breaker?

a.
none of these

b.
3 680 VA

c.
3 500 VA

d.
4 400 VA
Feedback
The correct answer is: none of these
Question 65
Correct
Mark 1.00 out of 1.00

Flag question
Question text
PVC is also known in the field as____.

a.
rigid non-metallic conduit

b.
cable tray
c.
rigid metallic conduit

d.
flexible conduit
Feedback
The correct answer is: rigid non-metallic conduit
Question 66
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
Fixtures in clothes closets shall be ___.

a.
a surface-mounted light emitting diode

b.
all of these

c.
pendant fixture

d.
a surface-mounted or recessed incandescent or fluorescent fixtures with a completely enclosed lamp
Feedback
The correct answer is: a surface-mounted or recessed incandescent or fluorescent fixtures with a
completely enclosed lamp
Question 67
Correct
Mark 1.00 out of 1.00

Flag question
Question text
To provide for a small appliance load in a dwelling unit, the feeder should be computed at ___.

a.
2 400 watts

b.
3 000 watts

c.
1 500 watts
d.
3 600 watts
Feedback
The correct answer is: 1 500 watts
Question 68
Correct
Mark 1.00 out of 1.00

Flag question
Question text
For dwelling units, a branch circuit supplying ___ receptacle outlets are permitted to also supply
receptacle outlets in attached garage.

a.
outdoor

b.
bathroom

c.
laundry room

d.
kitchen small appliance
Feedback
The correct answer is: outdoor
Question 69
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
The minimum allowable current rating of 3-wire service entrance conductors for a residence with an
initial net computed load of 6 kVA or more is ___.

a.
150 A

b.
100 A

c.
125 A
d.
60 A
Feedback
The correct answer is: 60 A
Question 70
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text

A high spot temperature in a corroded electrical connection is caused by a ___.

a.
decrease in the effective resistance of the connection

b.
increase in the voltage drop across the connection

c.
decrease in the voltage drop across the connection

d.
increase in the flow of current through the connection
Feedback
The correct answer is: decrease in the voltage drop across the connection
Question 71
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
Where galvanized conduit is used, the main purpose of the galvanizing is to ___.

a.
provide better strength

b.
provide better continuity

c.
provide a better surface for painting

d.
slow down rust
Feedback
The correct answer is: provide a better surface for painting
Question 72
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
In long conduit runs, pull boxes are sometimes installed at intermediate points to ___.

a.
facilitate pulling wires

b.
support the conduit

c.
make use of short lengths of conduit

d.
avoid using coupling
Feedback
The correct answer is: facilitate pulling wires
Question 73
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
Electrical symbol represented by a rectangle with a circle inside.

a.
Safety switch

b.
Fluorescent lamp outlet

c.
Incandescent lamp outlet

d.
Lighting panelboard
Feedback
The correct answer is: Fluorescent lamp outlet
Question 74
Correct
Mark 1.00 out of 1.00

Flag question
Question text
A wire or other mechanical member having one end secured and the other end fastened to a pole
maintained under tension is a ___.

a.
Tie wire

b.
Split-bolt

c.
Guy

d.
Cable rack
Feedback
The correct answer is: Guy
Question 75
Correct
Mark 1.00 out of 1.00

Flag question
Question text
To fasten an outlet box between the studs in wall constructed of metal lath and plaster, you would use
___.

a.
cement or mortar

b.
nylon lath twine

c.
iron wire

d.
an approved box hanger
Feedback
The correct answer is: an approved box hanger
Question 76
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Hidden edges in objects are represented in blueprints by ___..

a.
a thin solid line

b.
dashed lines having alternating long and short dashes

c.
dashed lines having approximately equal length dashes

d.
a thick solid line
Feedback
The correct answer is: dashed lines having approximately equal length dashes
Question 77
Correct
Mark 1.00 out of 1.00

Flag question
Question text
What does the symbol consisting of a rectangle with solid shading indicate?

a.
Lighting panelboard

b.
Safety switch

c.
Fuse cut out

d.
Telephone exchange
Feedback
The correct answer is: Lighting panelboard
Question 78
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Most wires used in residential house wiring are usually insulated by ___.

a.
varnished cambric

b.
cotton

c.
Asbestos

d.
thermoplastic
Feedback
The correct answer is: thermoplastic
Question 79
Correct
Mark 1.00 out of 1.00

Flag question
Question text
When calculating the general lighting load for a dwelling unit, which of the following listed is NOT to be
included in the calculation?

a.
Bathrooms

b.
Hallways

c.
Open porches

d.
Closets
Feedback
The correct answer is: Open porches
Question 80
Correct
Mark 1.00 out of 1.00

Flag question
Question text
A bathroom is defined by the PEC as a room or area with a wash basin and ___.
a.
a ground-fault circuit-interrupter

b.
a bidet, tub or shower

c.
a locking door

d.
an exhaust fan
Feedback
The correct answer is: a bidet, tub or shower
Question 81
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
Under the optional method of calculation “other loads” are permitted a demand factor from 2.20.4, the
first 10 kVA of “other load” at 100 % and the remainder of the “other load” at 40 %. “Other load” could
consist of which of the following?

a.
electric range

b.
air conditioning

c.
electric heat

d.
none of these
Feedback
The correct answer is: electric range
Question 82
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The Code requires in a dwelling a minimum of the following, EXCEPT ___.
a.
24 volt-ampere per square meter

b.
two small appliance circuits

c.
one laundry circuit

d.
one 8 kW range
Feedback
The correct answer is: one 8 kW range
Question 83
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
If a conductor material is not specified in a particular Article or Section, the material shall be assumed to
be which of the following?

a.
no assumptions shall be made

b.
Copper

c.
Aluminum

d.
Copper-clad aluminum
Feedback
The correct answer is: Aluminum
Question 84
Correct
Mark 1.00 out of 1.00

Flag question
Question text
With the exception of cord and plug-connected appliances, the disconnecting means for air conditioning
and refrigerating equipment shall be ___.

a.
permitted to be installed on or within the equipment

b.
readily accessible

c.
all of these

d.
located within sight
Feedback
The correct answer is: all of these
Question 85
Correct
Mark 1.00 out of 1.00

Flag question
Question text
What is the MAXIMUM allowable voltage between conductors on a branch circuit supplying luminaires
in a residence?

a.
240 V

b.
150 V

c.
250 V

d.
120 V
Feedback
The correct answer is: 120 V
Question 86
Correct
Mark 1.00 out of 1.00

Flag question
Question text
On a 120V 1Ø circuit, ground fault protection for personnel operates on the principal of unbalanced
current between ___.

a.
the grounding conductor and the neutral conductor
b.
the service disconnect and the branch circuit

c.
the grounded and ungrounded conductor

d.
the ungrounded conductors
Feedback
The correct answer is: the grounded and ungrounded conductor
Question 87
Correct
Mark 1.00 out of 1.00

Flag question
Question text
The branch-circuit load for a single 12-kilowatt (12 kW) electric range in a dwelling is ___.

a.
9 kW

b.
8 kW

c.
10 Kw

d.
11 kW
Feedback
The correct answer is: 8 kW
Question 88
Correct
Mark 1.00 out of 1.00

Flag question
Question text
A legend or electrical symbol list is shown on electrical working drawings to ___.

a.
identify all symbols used to indicate electrical outlets or equipment

b.
show the outline of the architect’s floor plan
c.
describe materials and instillation methods

d.
enable the electric service size to be calculated
Feedback
The correct answer is: identify all symbols used to indicate electrical outlets or equipment
Question 89
Correct
Mark 1.00 out of 1.00

Flag question
Question text
For a one-family dwelling, at least one receptacle outlet is required in each ___.

a.
all of these

b.
detached garage with power

c.
basement

d.
attached garage
Feedback
The correct answer is: all of these
Question 90
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Which of the following grounding electrodes is the only one that shall be supplemented by an additional
electrode?

a.
Building steel

b.
Ground ring

c.
Metal underground water pipe

d.
Concrete-encased
Feedback
The correct answer is: Metal underground water pipe
Question 91
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
To measure the area of a dwelling to determine the lighting load, the following dimensions are used:

a.
The cubic feet of each room

b.
The floor area computed from the outside dimension

c.
The area 150 mm (6 inches) from the inside walls

d.
The floor area computed from the inside dimension
Feedback
The correct answer is: The floor area computed from the outside dimension
Question 92
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
A 120/208-V, 3-phase circuit has a total connected load of 28 800 VA. What is the ampacity?

a.
65 A

b.
100 A

c.
80 A

d.
135 A
Feedback
The correct answer is: 80 A
Question 93
Correct
Mark 1.00 out of 1.00

Flag question
Question text
For dwelling units, the computed floor area at 24 VA per square meter does not include ___.

a.
all of these

b.
garages

c.
unused spaces not adaptable for future use

d.
open porches
Feedback
The correct answer is: all of these
Question 94
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
The difference between a thread on a bolt and a thread on a conduit is ___.

a.
the conduit thread is tapered

b.
the conduit thread is deeper

c.
no lubrication required in threading conduit

d.
the conduit thread always has the same pitch for any diameter
Feedback
The correct answer is: the conduit thread is tapered
Question 95
Correct
Mark 1.00 out of 1.00

Flag question
Question text
For dwelling units, all of the following are true EXCEPT ___.

a.
bathroom receptacles shall be supplied by a 20 A branch circuit which shall have no other outlets

b.
outdoor outlets are permitted to be supplied through the small appliance branch circuits

c.
the clothes washer shall be supplied by a 20 A branch circuit and outlets outside the laundry area are
not permitted on this circuit

d.
the outlet for kitchen refrigerator equipment may be supplied by an individual 15 A branch circuit
Feedback
The correct answer is: outdoor outlets are permitted to be supplied through the small appliance branch
circuits
Question 96
Correct
Mark 1.00 out of 1.00

Flag question
Question text
What is the approximate neutral current in a 4-wire system with phase A carrying 68 A, phase B carrying
88 A and phase C carrying 96 A?

a.
20 A

b.
30 A

c.
15 A

d.
25 A
Feedback
The correct answer is: 25 A
Question 97
Correct
Mark 1.00 out of 1.00

Flag question
Question text
Open wiring on insulators shall be permitted for wiring systems of ___ or less.

a.
600 V

b.
300 V

c.
150 V

d.
240 V
Feedback
The correct answer is: 600 V
Question 98
Incorrect
Mark 0.00 out of 1.00

Flag question
Question text
The advantage of using conduit pipe wiring is that it ___.

a.
is lighter

b.
is stronger

c.
has long life

d.
resist mechanical damage and has long life
Feedback
The correct answer is: resist mechanical damage and has long life
Question 99
Correct
Mark 1.00 out of 1.00
Flag question
Question text
Which of the following statements is NOT correct?

a.
Overcurrent devices shall be readily accessible.

b.
In a multi-family dwelling, each occupant shall have ready access to all overcurrent devices.

c.
Overcurrent devices shall be located where they will not be exposed to physical damage.

d.
Overcurrent devices may be located inside clothes closets
Feedback
The correct answer is: Overcurrent devices may be located inside clothes closets
Question 100
Correct
Mark 1.00 out of 1.00

Flag question
Question text
A one-family dwelling unit that is at grade level shall have ___ outdoors.

a.
one receptacle at front and one at the back

b.
one receptacle at the back

c.
two receptacles at the back

d.
one receptacle at the front
Feedback
The correct answer is: one receptacle at front and one at the back