r= Radius of pipe in meter, which is D / 2

y= Depth of flow in meter


A= Cross sectional area in square meter
P= Wetted perimeter in meter
Rh = Hydraulic radius in meter

Using 8 inches diameter RTR pipe


D= 0.208 m
r= 0.10 m
q = 2 arccos [ ( r - h ) / r ] (r-h)/r= 0.500 m
y= 0.156 m ( q - sin q ) = 1.228 radians
h= 2r-y = 0.052 m
q= 2.094 radian
A = ( p r2 ) - [ r2 ( q - sin q ) ] / 2
A= 0.027 m2
P= 2pr-rq = 0.436 m
Rh = A / P = 0.063 m

Using Mannings Formula:


Design flow velocities shall be determined by Manning's formula.

Average Velocity ( V ):
V = Rh2/3 S1/2 / n
Rh = Hydraulic radius = 0.063 m
S = Hydraulic slope = 0.005 m/m
n = Roughness coefficient of pipe, from Table 2 of SAES-S-030 ( RTR pipe )
= 0.013
V= 0.859 m/sec > 0.77 m/sec (SAFE)

Discharge Capacity ( Q ):
Q= VA
V= 0.859 M/sec
A= 0.027 M²
Q= 0.023 M³/sec
Q= 23.48 L/sec > 0.129 L/sec (SAFE)

5.2 DESIGN OF OILY WATER SEWER LINE

5.2.1 Design of Sub-Lateral Line

Minimum flow rate is based on Saudi Aramco Engineering Standard SAES-S-020


Section 4.4.2.