Rev. 0 Page 1 of 34
GDC-KLIA
PRE-REQUISITES
Rev. 0 Page 2 of 34
GDC-KLIA
Visually inspect Air Inlet Rain Hood and Bird Screen. Mechanical DONE
Inspect and if necessary change Air Inlet Final Filter Mechanical DONE
Inspect and clean filter housing and Intake Plenum Chamber. Look
for signs of corrosion and flanking paintwork. Look for any Mechanical DONE
“sunlight” in the plenum. Refer GEK 28156k
Perform Crank Soak wash. Check if crank wash fluids are as per
Mechanical NA
GEK requirement.
Carry out Detailed Gas Generator External Inspection especially
Fuel Gas Pipes and Manifold; oil and hydraulic lines and for external
leakages.
Visually inspect Gas Generator Air vent and Bleed Ducting Mechanical NA
Rev. 0 Page 3 of 34
GDC-KLIA
Inspect the static oil level in the intake guide vanes ram and
Mechanical NA
replenish, if necessary as instructed in chapter 7 para 5.3
Remove and clean any dirty fuel burners as per Para 11, chapter 7 of
Mechanical NA
GEK maintenance.
Inspect GG air intake (intake flare, extension rings, front bearing
housing, starter fairing,) as per para 10.2 chapter 6 of GEK
maintenance manual.
Pay special attention to checks mentioned at Para 14,chapter 7 of GEK
maintenance book. Mechanical NA
Check IGV linkage and bushing for freedom of movement –Remove
linkage pin and operate the IGV’s by hand.
Check for freedom of movement or excessive play in linkages and
bushings. Restricted or tight movement is not acceptable
Remove and inspect the oil feed filter for cleanliness as instructed in
Mechanical NA
chapter 7,para 8.3.3 to 8.3.5
DONE
Verify (note down) that operator is using correct lube oil brand. Mechanical
(ESSO TURBO OIL)
Inspect Lube Oil Magnetic Chip Detectors as per chapter 7 Para 8.3.6
Mechanical NA
to 8.3.8 of GEK maintenance book
Rev. 0 Page 4 of 34
GDC-KLIA
DONE
Visually inspect the structural integrity of the Acoustic Enclosure Mechanical
Remove and clean the inlet filter (located on the side of the actuator NA
Control
housing under the solenoid)
Verify if fuel gas analysis is done at 4K intervals as per (GEK 28156k) Mechanical NA
4. Power turbine
Rev. 0 Page 5 of 34
GDC-KLIA
Check the fasteners at the exhaust volute split lines and at the
Mechanical DONE
interface with the transition duct for security (GEK 28156k)
Check oil leakages near PT bearing case as per GEK 28156k.) Mechanical DONE
Check the offset and gap between GG air extension and bell
Mechanical NA
mouth.
5. Gear Box
Check all systems hoses, fittings and pipe work for degradation
(visual check for chafing or frottage of piping/hoses/tubing) and
tightness (leakages) on following oil and hydraulic systems Mechanical NA
• Main lube oil systems
• GG oil systems
Attend filters on oil circuits as under.
1. Change (if required) on-line filter elements on filter located
on GG lube oil supply, hydraulic supply and PT Cool down
supply lines (wherever fitted)
2. Clean demister pads fitted on
a. Vent lines of GG lube oil tank
b. Vent line of PT bearing casing
c. Vent lines on compressor bearings. Mechanical
3. Clean breathers on NA
a. GG lube oil tank
b. Low and high speed couplings
c. Gear box
4. Clean strainer elements on
a. Strainers on GG LP/scavenge pump suction.
b. Strainer on wash tank skid.
Accumulator – check inert (N2) gas pressure in the bladder (should NA
be 500 psi), when the unit is not running. Charge the accumulator Mechanical
bladder if necessary.
NA
Verify that G.G lube analysis is carried out at regular intervals
Mechanical
(3 months)
Rev. 0 Page 6 of 34
GDC-KLIA
Check the air inlet systems for degradation and moisture buildup.
Visually inspect Air Inlet Rain Hood and Bird Screen. Replace filters
Mechanical DONE
in GG air intake and in ventilation system (if required). Check seals
around door and lubricate hinges.
Inspect all joint bolts on the air system for tightness. Visually
inspect system welds for failure and /or cracks. Inspect intake Mechanical DONE
flexible joint assembly.
Check the interior of the GG enclosure/Plenum. Look for signs of
corrosion and flanking paintwork in the plenum. Look for any
“sunlight” in the plenum. Refer GEK 28156k. Check all lights fixture.
Mechanical DONE
Check operation of the door proximity switches and adjust if
necessary. Inspect the GG enclosure/plenum access door
gasketing for wear and deterioration. Lubricate door hinges.
Carry out functional test on automatic transfer on stand by unit for
Ventilation fan. Check tension on fan belts (if used) in enclosure
ventilation system. Check operation of the back-draught dampers Mechanical NA
to ensure free movement of the damper blades. Lubricate
dampers.
Visually inspect the exhaust expansion joint assembly to ensure
the unit is in good working order. Check for leakages between the
Mechanical DONE
exhaust expansion joint flanges. If necessary tighten bolts and
check gaskets for wear or deterioration.
Rev. 0 Page 7 of 34
GDC-KLIA
9. Electrical motors
10. Others
Rev. 0 Page 8 of 34
GDC-KLIA
1. General Comments:
NOT APPLICABLE
2. Corrective Maintenance
Rev. 0 Page 9 of 34
GDC-KLIA
NOT APPLICABLE
Priority X Urgent (Do not use machine until complete) A As soon as possible (Next Service)
Code
B Within 6 months or 4000 Hours C Plan as appropriate to coincide with other
works
3. Unit Start-Up
Rev. 0 Page 10 of 34
GDC-KLIA
DATE OF INSPECTION :
INSPECTED BY :
NOT APPLICABLE
ENGINE
Rev. 0 Page 11 of 34
GDC-KLIA
NO OF
AREA / VIEWING Height/Width of DAMAGE
PORT STATORS / COMMENTS
DIRECTION blades (MM) FOUND
ROTORS
VIGVs S 23
R22
00 Stage
S31
NOT APPLICABLE
AIR INTAKE
R29
0 Stage
S47
1 8
2 VIEW LOOKING 7
FORWARD
3 6
BOROSCOPE
PORTS
4 5
Rev. 0 Page 12 of 34
GDC-KLIA
5
NOT APPLICABLE
1 8
2 VIEW LOOKING 7
FORWARD
3 6
BOROSCOPE
PORTS
4 5
Rev. 0 Page 13 of 34
GDC-KLIA
4 NOT APPLICABLE
1 8
2 VIEW LOOKING 7
FORWARD
3 6
BOROSCOPE
PORTS
4 5
Rev. 0 Page 14 of 34
GDC-KLIA
AREA / NO OF LENGTH
DAMAGE
PORT VIEWING STATORS / (APPROX) COMMENTS
FOUND
DIRECTION ROTORS MM
HP Turbine
Blades Trailing
ENTRY DUCT/OR THRU T4
INSPECTION PORTS IN PT
Edges
NOT APPLICABLE
LP Turbine
Blades Trailing
Edges
PORT
Rev. 0 Page 15 of 34
GDC-KLIA
PS: During the rebuild period all parts will have their preservation and FME protection
systematically remove, be cleaned and fully blown down with plant air then closely
inspected prior to being considered acceptable to be re-installed and returned to
service.
Rev. 0 Page 16 of 34
GDC-KLIA
PS: During the rebuild period all parts will have their preservation and FME protection
systematically remove, be cleaned and fully blown down with plant air then closely
inspected prior to being considered acceptable to be re-installed and returned to
service.
Rev. 0 Page 17 of 34
GDC-KLIA
Rev. 0 Page 18 of 34
GDC-KLIA
Bellmouth/IGV inspection hatch found 10% GG/PT-Engine Removal Hatch door found in
corroded and Structurally found Acceptable Acceptable condition and need to check on
condition. the rubber seal condition prior to CSU.
Entry door(Hinges & slide handhold) found Enclosure grating,beams,gussets and related
in Acceptable condition. mechanism found in Acceptable condition.
Rev. 0 Page 19 of 34
GDC-KLIA
Lifting handling gears-chain blocks, web Best practices had been adopted during the
slings, shackles and trolleys found EXPIRED last GT6001A major overhaul in March
on 20/1/2022. 2021.No indicative of oil leakages, opening
manifolds, piping and connectors found at
site/enclosure.
Rev. 0 Page 20 of 34
GDC-KLIA
Rev. 0 Page 21 of 34
GDC-KLIA
PT-Lifting gears are installed as per GEK All the cling wrapping,piping
compliance. openings,manifolds and connectors were well
encapsulated and do a thorough inspection
on every each components within enclosure
expanse.
Rev. 0 Page 22 of 34
GDC-KLIA
PT-Lifting gears are installed as per GEK PT-Lifting gears are installed as per GEK
compliance. compliance.
PT-Lifting gears are installed as per GEK PT-Lifting gears are installed as per GEK
compliance. compliance.
Rev. 0 Page 23 of 34
GDC-KLIA
PT-Lifting gears are installed as per GEK PT-Lifting gears are installed as per GEK
compliance. compliance.
PT-Lifting gears are installed as per GEK PT-Lifting gears are installed as per GEK
compliance. compliance.
Rev. 0 Page 24 of 34
GDC-KLIA
PT-Lifting gears are installed as per GEK PT-Lifting gears are installed as per
compliance. GEK compliance.
PT-Lifting gears are installed as per GEK PT-Lifting gears are installed as per
compliance. GEK compliance.
Rev. 0 Page 25 of 34
GDC-KLIA
PT-Lifting gears are installed as per GEK PT-Lifting gears are installed as per GEK
compliance. compliance.
PT-Lifting gears are installed as per GEK All the cling wrapping,piping
compliance. openings,manifolds and connectors were well
encapsulated and do a thorough inspection
on every each components within enclosure
expanse.
Rev. 0 Page 26 of 34
GDC-KLIA
Rev. 0 Page 27 of 34
GDC-KLIA
PT-Observed the Oil Wetting PRESENT PT-Observed the Oil Wetting PRESENT
during the inspection at site and found during the inspection at site and found
Acceptable condition. Acceptable condition.
PT-Observed the Oil Wetting PRESENT PT-Observed the Oil Wetting PRESENT
during the inspection at site and found during the inspection at site and found
Acceptable condition. Performed manual Acceptable condition.
5% droplets on the PT for Oil Wetting.
Rev. 0 Page 28 of 34
GDC-KLIA
Close up PT with cling wrapping after Oil Performed manual 5% droplets on the
wetting was done. PT for Oil Wetting.
Rev. 0 Page 29 of 34
GDC-KLIA
Close up PT with cling wrapping after Oil PT-Lifting gears are installed as per
wetting was done. GEK compliance.
PT-Lifting gears are installed as per GEK PT-Lifting gears are installed as per
compliance. GEK compliance.
Rev. 0 Page 30 of 34
GDC-KLIA
LO tank-To acquire Lube Oil from the No water ingress & moisture found
tank prior to perform “Shake test”. from the LO tank.
Rev. 0 Page 31 of 34
GDC-KLIA
Rev. 0 Page 32 of 34
GDC-KLIA
No water ingress & moisture found No water ingress & moisture found from
from the LO tank and LO drum the LO tank and LO drum
Rev. 0 Page 33 of 34
GDC-KLIA
Rev. 0 Page 34 of 34