You are on page 1of 1

PROJECT

T20x @ 150 T20x @ 150 T20x @ 150


PB PC CONC PLINTH LEVEL 01 LEVEL 01 LEVEL 01
300 42600 42600 42600
COLUMN COLUMN PER PLAN (6) T16 CONT
OWNER
PER PLAN PER PLAN
T12 @ 300
Ortigas&Company

Lsb
Lsb 5 80

5 80
Lsb 5 80
600
(23) T16 Limited Partnership
SOG 9/F ORTIGAS BUILDING,ORTIGAS AVENUE, PASIG CITY
LEVEL B7 LEVEL B7 TELEPHONE: (632)631-1231 TO 38 FAX:(632)631-6517

16900 16900
750

MAT FDN

1 47

Ldh MIN
COVER
ADDL T16x3000 @ 300

75
(23) T25 VOF, CTR ON RAMP
BETWEEN B1 & LVL 1 THOMAS F. MIRASOL
(18) T25 T&B COMBINED
COLUMN FTG CHIEF OPERATING OFFICER, SENIOR VICE
PRESIDENT & GENERAL MANAGER
REAL ESTATE DIVISION

LEVEL B1 LEVEL B1 LEVEL B1


38400 38400 38400
RED - Technical Planning Department

SECTION SECTION
1 2
TECHNICAL PLANNING MANAGER

1 : 50 1 : 25
ARCHITECT OF RECORD

GF & Partners
A r c h i t e c t s

ANNETTE F. GADDI-LIGANOR
LEVEL B2 LEVEL B2 LEVEL B2 PRC REG. NO. : 6813
PTR NO. : 4754954
A R C H I T E C T
DATE: 11-12-1982 TIN : 108-782-800
PLACE : MAKATI CITY
DATE: 01-12-2015
35300 35300 35300 TEODORO H. NARCISO
ANNETTE F. GADDI-LIGANOR
TEOFILO A. SANTIAGO JR.
ARNULFO M. VILLANUEVA
XAVIER ANTONIO J. GARCIA
11TH FLOOR, BDO PLAZA, 8737 PASEO DE ROXAS, MAKATI CITY, PHILIPPINES
TELEPHONE (632) 553-7232 FAX (632) 553-7230 E-MAIL: postmaster@gfparchitects.com

STRUCTURAL

T16 @ 300 VOF, T16 @ 300 VOF,


TYP UNO TYP UNO incorporated
ASSOCIATES JOSE A. SY
T16 @ 300 VOF, STRUCTURAL ENGINEER
TYP UNO Unit 504 Pryce Center, 1179 Chino Roces Avenue
cor. Bagtican St., Makati City REG. NO. 22404 TIN 123-489-697
Telephone No. 896-97-04 to 05
Fax No. 896-97-60 to 61 PTR NO. 5330036 DATE 01-07-16
e-mail address: info@sysquared.com PLACE MAKATI CITY

ELECTRICAL
LEVEL B3 LEVEL B3 LEVEL B3 EBCRUZ & PARTNERS
32200 32200 32200 ELECTRICAL ENGINEERS

1335 A. MABINI ST., KALOOKAN CITY.


TEL. NOS. 287-5631 288-7054
email : ebc@philonline.com.ph

T16 @ 300 VIF, T25 @ 300 VOF E


PROFESSIONAL
F R E N B.
ELECTRICAL ENGINEER
C R U Z

TYP UNO T20 @ 300 VOF MECHANICAL

DCCD ENGINEERING CORPORATION


SOL BUILDING 112 AMORSOLO ST., MAKATI M.M.
TEL. NOS. 892-45-86 TO 89

PROF. MECHANICAL ENGINEER


LEVEL B4 LEVEL B4 LEVEL B4 PTR NO. REG. NO.
29100 29100 29100 ISSUED ON. TIN
ISSUED AT

T25 @ 300 VOF T16 @ 300 VIF,


TYP UNO DCCD ENGINEERING CORPORATION
SOL BUILDING 112 AMORSOLO ST., MAKATI M.M.
T20 @ 300 VOF, T20 @ 200 HEF, T20 @ 300 VOF, TEL. NOS. 892-45-86 TO 89
T25 @ 300 VIF T20 @ 200 HEF, TYP UNO TYP UNO TYP UNO
TYPICAL UNO. SANITARY ENGINEER
T25 @ 175 AT SIM PTR NO. REG. NO.
ISSUED ON. TIN
ISSUED AT

FIRE PROTECTION

LEVEL B5 LEVEL B5 LEVEL B5 DCCD ENGINEERING CORPORATION


SOL BUILDING 112 AMORSOLO ST., MAKATI M.M.
26000 26000 26000 TEL. NOS. 892-45-86 TO 89

400
THICKNESS THICKNESS FIRE PROTECTION ENGINEER
PER PLAN
400

PER PLAN PTR NO. REG. NO.


T25 @ 150 VOF ISSUED ON. TIN
T25 @ 100 VOF ISSUED AT

T25 @ 300 VEF CONSTRUCTION MANAGER


T25 @ 300 VIF T16 @ 300 VIF,
U-BAR TO MATCH TYP UNO
SIZE & SPCG OF
SOG, REINF VERT REINF SLAB, REINF
PER PLAN PER PLAN MAT SOG
SLAB, TYP

TYP
Lsb

TYP
Lsb
Lsb Ld FOUNDATION

7 00

7 00
503 397

LEVEL B6 LEVEL B6 LEVEL B6 LEVEL B6


22900 22900 22900 22900

TYP
Ld
5 36
Ld
6 30

QUANTITY SURVEYOR
Lsb

474

(5) T12 @ 300


7 15

DWL SIZE & SPCG


Lsb

VERT & HORIZ (4) T20, CONT


DWL SIZE & SPCG TO MATCH VERT
ADDL T25x3000 REINF, TYP
TO MATCH VERT
@ 300 VOF
T25 @ 300 VIF REINFORCEMENT Arcadis Philippines, Inc.
4th Floor King's Court 1, 2129 Pasong Tamo Makati City

T16 @ 300 VEF NOTES: NOTES: Tel: +632 8112971 Fax: +632 8112071
T25 @ 150 VOF E-mail: info-ph@arcadis.com www.arcadis.com

ADDL T25 @ 300 VIF 1. 20mm CLEAR COVER AT VERTICAL INTERIOR FACE, 50mm CLEAR COVER AT 1. 20mm CLEAR COVER AT VERTICAL INTERIOR FACE, 50mm CLEAR COVER AT REVISIONS
VERTICAL EXTERIOR FACE, MINIMUM. VERTICAL EXTERIOR FACE, MINIMUM. NO. DATE DESCRIPTION
T16 @ 300 HEF T20 @ 200 HEF
TYP UNO
SECTION SECTION
COL BEYOND
DWL SIZE & SPCG
TO MATCH VERT 14 1 : 50 15 1 : 50
REINF, TYP (5) T12 @ 300
FTG DWLS TO MATCH VERT & HORIZ
SIZE & SPACING OF TRENCH DRAIN
VERT REINFORCEMENT WHERE OCCURS
PER SANITARY
SOG, REINF NOTES:
MAX

SOG
TYP
150
TYP

Lsb
Lsb

PER PLAN
6 50
6 03

LEVEL B7 LEVEL B7 SHOULD THERE BE DISCREPANCIES, CONFLICTS


AND/OR AMBIGUITIES ON THE CONSTRUCTION
16900 16900 DOCUMENTS (ie. ARCH'L., ENGINEERING DRAWINGS,
600

600

REINF PER BSMT GR TECH'L. SPECS ETC.), THE CONTRACTOR SHOULD


WALL SECTION ID
FIRST CALL THE ATTENTION OF THE DESIGNERS FOR
SLAB STEP CLARIFICATION BEFORE PROCEEDING WITH THE WORK
WHERE TRENCH 1000 (4) T20, CONT PG ON THE AREA CONCERNED.
1250 VERT REINF & TIES
(6) T20, CONT DRAIN OCCURS PER "CONC COL SCHED" THIS DRAWING, AS AN INSTRUMENT OF SERVICE, IS A
PROPERTY OF ORTIGAS AND COMPANY, LIMITED
PARTNERSHIP, AND AS SUCH MUST NOT BE
REPRODUCED OR COPIED IN PART OR IN WHOLE
REINF TO MATCH WITHOUT THEIR CONSENT. ALL DRAWINGS ARE TO BE
SIZE & SPCG OF RETURNED WHEN NO LONGER IN USE.
REPUBLIC ACT 545
HORIZ REINF
PURPOSE OF ISSUANCE

CONSTRUCTION JT PROGRESS PLANS


AT CONTR OPT
SHEET CONTENTS
Lsb
, TY
6 19

P
CONCRETE SECTIONS AND DETAILS
NOTES: NOTES:
DRAWN SHEET NO.
1. 25mm CLEAR COVER AT VERTICAL INTERIOR FACE, 50mm CLEAR COVER AT 1. 20mm CLEAR COVER AT VERTICAL INTERIOR FACE, 50mm CLEAR COVER AT
DATE
VERTICAL EXTERIOR FACE, MINIMUM. VERTICAL EXTERIOR FACE, MINIMUM.
REVISED S5.02
SECTION SECTION DETAIL CHECKED

17 1 : 50 18 1 : 50 20 1 : 25
PROJECT NUMBER : 140721

C:\Revit 2015 Project Files\CapitolCommParcelF__CD_WS2015_ym.rvt 6/16/2017 4:44:35 PM MAG