• Interior Columns: 400 mm x 400 mm
1
• Edge Columns: 300 mm x 300 mm
4.0m
D1 D2 D3 D4
2
• Materials: C30-S420 (BS30/BÇ III)
• Finishing+Mortar: 1.50 kN/m2
2
C
• Live Load: q=7.00 kN/m2
4.0m
2
D5 D6 D7 D8
Determine the reinforcement in the flat
slab system in the middle storey level.
2
B
4.0m
D9 D10 D11 D12
2
L1
1
A
Y 1 2 1 1 3 1 1 3 1 1 2 1
X L2
1 2 2 3 2 3 2 2 1
SOLUTION:
2. MATERIAL STRENGTHS
C30 fcd=fck/1.5=20 N/mm2 ; fctd=fctk/1.5=1.25 N/mm2
S420 fyd=fyk/1.15=365 N/mm2
5000mm
1/6
Altınbaş University
Engineering &Natural Science Faculty,
Civil Engineering Department, Reinforced Concrete –II -2020
The design value of the punching shear force Vpd=(4.0 x 5.0 - 0.575 x 0.575) x 20.3 =399 kN
emin =15 mm+0.03h = 15 + 0.03 x 400 = 27 mm
As e 27 mm ex=ey=27 mm
1 1
= = = 0.88
e + ey 27 + 27
1 + 1.5 x 1 + 1.5 575 575
bx by
6. STATİC ANALYSIS:
Moment Coefficient Method (approximate method) can be employed in flat slabs where these conditions are met: This
approximate method is only applicable for vertical load analysis.
a. There are at least 3 continuous spans in each direction;
b. The sides’ ratio in a panel is less or equal to 2.0 (Llong/Lshort<2.0 : 5.0 /4.0 =1.25 < 2.0)
c. Adjacent span lengths in any direction do not differ by more than one third of the longer span (Llong/3);
(5.0-4.0)/5.0 =0.2 <0.33
d. The offset (eccentricity) of a column from the centerline of the axis of the frame is not more than 10% of the span
length in the direction of the frame;
e. The ratio of live load to the dead load does not exceed 2.0 (q/g<2) (1.6 q / 1.4 g = 0.879 < 2)
ANALYSIS IN X DIRECTION
Interior Span:
1 1
M = p L L2 = 20.3 4.0 4.602 = 214.8 kNm
0 d 2 n
8 8
Ln: clear span length in the direction under consideration and is the face to face distance between columns. L2 :
span length in the perpendicular direction and is the axis to axis distance between columns.
Interior span M0 is distributed to the span and supports according to the principles given below:
• Middle Strip Mm
o = 0.25 139.6 = 34.9 kNm
End Span:
1 1
M = p L L2 = 20.3 4.0 3.652 = 135.2 kNm
0 d 2 n
8 8
End span M0 is distributed to the span and supports according to the principles given below:
• Middle Strip o
Mm = 0.25 94.7 = 23.7 kNm
Exterior Support Moment = 0.30 M0 = 40.6 kNm
• Column Strip Mm
k = 1.00 40.6 = 40.6 kNm
• Middle Strip o
Mm =0
2/6
Altınbaş University
Engineering &Natural Science Faculty,
Civil Engineering Department, Reinforced Concrete –II -2020
ANALYSIS IN Y DIRECTION
Interior Span:
1 1
M = p L L2 = 20.3 5.0 3.602 = 164.4 kNm
0 d 2 n
8 8
• Middle Strip Mm
o = 0.25 106.9 = 26.7 kNm
End Span:
1 1
M = p L L2 = 20.3 5.0 3.652 = 169.0 kNm
0 d 2 n
8 8
End span M0 is distributed to the span and supports according to the principles given below:
• Middle Strip Mm
o = 0.25 118.3 = 29.6 kNm
a) x direction 40.6
Column Strip
40.6
45.1
4.0m 5.0m
1 2 3
34.9 34.9
23.7
Middle Strip
27.1
30.1
88.7 88.7
50.7
b) y direction 80.2 80.2
Column Strip
34.5
50.7
4.0m 4.0m
A B C
29.6 29.6
26.7 26.7
3/6
Altınbaş University
Engineering &Natural Science Faculty,
Civil Engineering Department, Reinforced Concrete –II -2020
8. REINFORCEMENT DESIGN:
Material C30/S420
a) Design in x direction
Minimum reinforcement
min(Asx + Asy ) = dort b min = 175 1000 0.0035 = 613 mm2 /m (As,min/2=306.5 mm2/m)
Reinforcement spacing: t 1.5 h=300 mm ; 250 mm
b) Design in y direction
Reinforcements in the middle strips of D2 and D6 slabs are adequate when compared to the minimum reinforcement
amount.
Punching shear safety should be checked again as the %40 of the column moments are transferred to the slab as
torsion which increases the stresses in the critical section. Therefore punching shear safety should be checked with the
moments calculated from the structural analysis.
4/6
Altınbaş University
Engineering &Natural Science Faculty,
Civil Engineering Department, Reinforced Concrete –II -2020
3.4
y direction M = 0.4 (88.7 − 80.2) = 3.4 kNm ex = = 0.008 e
y min = 0.027 m
399
1 1
= = = 0.86
e + ey 34 + 27
1 + 1.5 x 1 + 1.5 575 575
bx by
As it is clear that, the coefficient is not changing so much therefore the first punching shear control would be enough if
the loads are not very large.
The Punching Shear Strength of the slab section (critical perimeter) (dort=175 mm)
Vpr= fctd up d=0.86 x 1.25 x 10-3 x (4 x 575) x 175 = 434 kN > Vpd = 399 kN ( )
5/6
Altınbaş University
Engineering &Natural Science Faculty,
Civil Engineering Department, Reinforced Concrete –II -2020
COLUMN STRIP:
1 2 3
1.15
10/380
10/380
10/380
2.00
4.00
D1 D2
10/190
8/250 10/150
2.00
C 8/300 8/280
8/300 8/280
2.00
4.00
8/360
8/360
D5 D6
2.00
B
MIDDLE STRIP:
1 2 3
D
1.15
D1 D2
8/320
8/320
2.00
4.00
2.00
C
8/320
8/320
8/320
2.00
4.00
8/320
8/320
8/320
D5 D6
2.00
A A
A-A kesiti
0.20
6/6