bcol. = 200 mm
l = 1.5 m
dftg. = 0.3 m
qe = qa - Ʃɣh
qe = 120- 23.6(0.3)-15.6(1-0.3)
qe = 102 kPa
DL = 23.6(1)(4)(0.2)
= 18.88 kN
LL = 4.8(1)(3.3)
= 15.84 kN
L(1) = 18.88+15.84
102
qu = 1.4DL + 1.7LL
L(1)
qu = 1.4(18.88) + 1.7(15.84)
1.2(1)
qu = 44.47 kPa
Mu = 44.47(0.1)(1)(0.1/2)
Mu = 0.23 kN-m
Mu = 230000 N-mm
ρ = wfc'
fy
ρ = 0.000174(17.3)
149
ρ = 0.0001
ρmin = 1.4
fy
ρmin = 0.0094
use ρ = 0.0094
As = ρbd
As = 0.0094(1000)(300)
As = 2820 mm²
1000(25)²(π) 2820
=
4S
S = 174.07
200.00 mm O.C.
Use 3-12mmΦ continuous bars and 10mmΦ stirrups spaced @200mm OC.
DESIGN CRI
fs =
fy =
fc' =
fc =
fv =
β =
Wt. of Concrete =
Live Loads =
=
Soil Pressure =
DESIGN CRITERIA
124.30 Mpa E = 200,000.00 Mpa
149.00 Mpa n = 10.00
17.30 Mpa k = 0.39
7.80 Mpa j = 0.87
23.60 KN/m³
1.92 kPa for rooms
4.80 kPa for stairs, halls, etc.
m = Ls m = Ls
Lb Lb
= 4 = 4
5 3.5
= 0.8 = 1.142857143
Ls = length of clear span in short direction Ls = length of clear span in short direction
Lb = length of clear span in long direction Lb = length of clear span in long direction
Ca, neg. = 0.065 w = 1.4 DL + 1.7 LL Ca, neg. = 0.065 w = 1.4 DL + 1.7 LL
Cb, neg. = 0.027 = 3.6344 + 8.16 Cb, neg. = 0.027 = 0 + 8.16
= 11.7944 kN/m = 8.16 kN/m
𝑀_𝑎 = 𝐶_𝑎wL𝑠 𝑀_𝑎 = 𝐶_𝑎wL𝑠
= ^2
0.065(11.794)(4)² = ^2 0.065(11.794)(4)²
= 12.27 kN-m = 8.49 kN-m
DEADLOAD DEADLOAD
+ Ma = 0.026(3.6344)(4)² + Ma = 0.026(3.6344)(4)²
= 1.51 kN-m = 0.00 kN-m
LIVELOAD LIVELOAD
+ Ma = 0.041(8.16)(4)² + Ma = 0.041(8.16)(4)²
= 5.35 kN-m = 5.35 kN-m
DEADLOAD DEADLOAD
+ Mb = 0.011(3.6344)(5)² + Mb = 0.011(3.6344)(5)²
= 1.00 kN-m = 0.00 kN-m
LIVELOAD LIVELOAD
+ Mb = 0.017(8.16)(5)² + Mb = 0.017(8.16)(5)²
= 3.47 kN-m = 1.70 kN-m
Negative moment @ Continuous Edges equal Negative moment @ Continuous Edges equal
1/3 of positive moment 1/3 of positive moment
1) Midspan: 1) Midspan:
Mu = 6.86 kN-m Mu = 5.35 kN-m
Mu = φFc'bd²w(1-0.59w) Mu = φFc'bd²w(1-0.59w)
6.86 = 0.9(17.3)(1000)(85)²w(1-0.59w) 5.35 = 0.9(17.3)(1000)(85)²w(1-0.59w)
w = 0.06335 w = 0.06335
ρ = wfc' ρ = wfc'
fy fy
ρ = 0.06335(17.3) ρ = 0.06335(17.3)
149 149
= 0.007355402685 = 0.007355403
As = ρbd As = ρbd
= 625.21 mm² = 551.66 mm²
1000π(12)² 1000π(12)²
= 625.21 = 551.66
S(4) S(4)
ρ = wfc' ρ = wfc'
fy fy
ρ = 0.1172(17.3) ρ = 0.1172(17.3)
149 149
= 0.013608 = 0.013608
As = ρbd As = ρbd
= 1156.66 mm² = 1020.58 mm²
1000π(12)² 1000π(10)²
= 1156.66 = 1020.58
S(4) S(4)
ROOF SLAB DESIGN DESIGN CRITERIA FLOOR SLAB DESIGN/ SLAB 1 DESIGN CRITERIA
m = Ls m = Ls
Lb Lb
= 4 = 4
5 3.5
= 0.80 = 1.14
Ls = length of clear span in short direction Ls = length of clear span in short direction
Lb = length of clear span in long direction Lb = length of clear span in long direction
Ca, neg. = 0.044 w = 1.4 DL + 1.7 LL Ca, neg. = 0.044 w = 1.4 DL + 1.7 LL
Cb, neg. = 0.019 = 3.6344 + 8.16 Cb, neg. = 0.019 = 3.304 + 8.16
= 11.7944 kN/m = 11.464 kN/m
𝑀_𝑎 = 𝐶_𝑎wL𝑠 𝑀_𝑎 = 𝐶_𝑎wL𝑠
= 0.044(11.794)(4)²
^2 = ^2 0.044(11.794)(4)²
= 8.30 kN-m = 8.07 kN-m
DEADLOAD DEADLOAD
+ Ma = 0.032(3.6344)(4)² + Ma = 0.032(3.6344)(4)²
= 1.86 kN-m = 1.69 kN-m
LIVELOAD LIVELOAD
+ Ma = 0.044(8.16)(4)² + Ma = 0.044(8.16)(4)²
= 5.74 kN-m = 5.74 kN-m
DEADLOAD DEADLOAD
+ Mb = 0.015(3.6344)(5)² + Mb = 0.015(3.6344)(5)²
= 1.36 kN-m = 0.61 kN-m
LIVELOAD LIVELOAD
+ Mb = 0.019(8.16)(5)² + Mb = 0.019(8.16)(5)²
= 3.88 kN-m = 1.90 kN-m
Negative moment @ Continuous Edges equal Negative moment @ Continuous Edges equal
1/3 of positive moment 1/3 of positive moment
1) Midspan: 1) Midspan:
Mu = 7.61 kN-m Mu = 7.44 kN-m
Mu = φFc'bd²w(1-0.59w) Mu = φFc'bd²w(1-0.59w)
7.61 = 0.9(17.3)(1000)(85)²w(1-0.59w) 7.44 = 0.9(17.3)(1000)(85)²w(1-0.59w)
w = 0.07059 w = 0.07059
ρ = wfc' ρ = wfc'
fy fy
ρ = 0.07059(17.3) ρ = 0.07059(17.3)
149 149
= 0.008196020134 = 0.00819602
As = ρbd As = ρbd
= 696.66 mm² = 0.82 mm²
1000π(12)² 1000π(10)²
= 696.66 = 0.82
S(4) S(4)
ρ = wfc' ρ = wfc'
fy fy
ρ = 0.0773(17.3) ρ = 0.0773(17.3)
149 149
= 0.008975 = 0.008975
As = ρbd As = ρbd
= 762.88 mm² = 0.90 mm²
1000π(12)² 1000π(12)²
= 762.88 = 0.90
S(4) S(4)
ρ = wfc' ρ = wfc'
fy fy
ρ = 0.05576(17.3) ρ = 0.05576(17.3)
149 149
= 0.006474 = 0.006474
As = ρbd As = ρbd
= 511.46 mm² = -38.20 mm²
1000π(10)² 1000π(12)²
= 511.46 = -38.20
S(4) S(4)
ρ = wfc' ρ = wfc'
fy fy
ρ = 0.05134(17.3) ρ = 0.05134(17.3)
149 149
= 0.005961 = 0.005961
As = ρbd As = ρbd
= 506.68 mm² = 0.60 mm²
1000π(12)² 1000π(12)²
= 506.68 = 0.60
S(4) S(4)
ROOF SLAB DESIGN DESIGN CRITERIA FLOOR SLAB DESIGN DESIGN CRITERIA
SLAB 3 SLAB 3
fs = 124.3 Mpa E = 200000 Mpa fs = 124.3 Mpa E = 200000 Mpa
Lb= 5 m fy = 149 Mpa n = 10 Lb= 5 m fy = 149 Mpa n = 10
Ls= 5 m fc' = 17.3 Mpa k = 0.386 Ls= 5 m fc' = 17.3 Mpa k = 0.386
fc = 7.8 Mpa j = 0.871 fc = 7.8 Mpa j = 0.871
fv = 110.5 Mpa R = 1.31 Mpa fv = 110.5 Mpa R = 1.31 Mpa
Minimum thickness, t= 2(5+ 5)(1000) Minimum thickness, t= 2(5+ 5)(1000)
180 180
Wt. of Concrete = 23.6 KN/m³ Wt. of Concrete = 23.6 KN/m³
= 112 say 120 mm 0.12 m Live Loads = 1.92 kPa for rooms = 112 say 120 mm 0.12 m Live Loads = 1.92 kPa for rooms
= 4.8 kPa for stairs, halls, etc. = 4.8 kPa for stairs, halls, etc.
Therefore try 120 mm Slab Soil Pressure = 120 kPa (ordinary soil) Therefore try 120 mm Slab Soil Pressure = 120 kPa (ordinary soil)
m = Ls m = Ls
Lb Lb
= 5 = 5
5 5
= 1.0 = 1.0
Ls = length of clear span in short direction Ls = length of clear span in short direction
Lb = length of clear span in long direction Lb = length of clear span in long direction
Ca, neg. = 0.05 w = 1.4 DL + 1.7 LL Ca, neg. = 0.05 w = 1.4 DL + 1.7 LL
Cb, neg. = 0.05 = 3.9648 + 8.16 Cb, neg. = 0.05 = 3.9648 + 8.16
= 12.1248 kN/m = 12.1248 kN/m
𝑀_𝑎 = 𝐶_𝑎wL𝑠 𝑀_𝑎 = 𝐶_𝑎wL𝑠
= ^2
0.05(12.125)(5)² = ^2 0.05(12.125)(5)²
= 15.16 kN-m = 15.16 kN-m
DEADLOAD DEADLOAD
+ Ma = 0.027(3.9648)(5)² + Ma = 0.027(3.9648)(5)²
= 2.68 kN-m = 2.68 kN-m
LIVELOAD LIVELOAD
+ Ma = 0.032(8.16)(5)² + Ma = 0.032(8.16)(5)²
= 6.53 kN-m = 6.53 kN-m
DEADLOAD DEADLOAD
+ Mb = 0.027(3.304)(5)² + Mb = 0.027(3.304)(5)²
= 2.68 kN-m = 2.68 kN-m
LIVELOAD LIVELOAD
+ Mb = 0.032(8.16)(4.35)² + Mb = 0.032(8.16)(4.35)²
= 6.53 kN-m = 6.53 kN-m
Negative moment @ Continuous Edges equal Negative moment @ Continuous Edges equal
1/3 of positive moment 1/3 of positive moment
1) Midspan: 1) Midspan:
Mu = 9.20 kN-m Mu = 9.20 kN-m
Mu = φFc'bd²w(1-0.59w) Mu = φFc'bd²w(1-0.59w)
9.20 = 0.9(17.3)(1000)(95)²w(1-0.59w) 9.20 = 0.9(17.3)(1000)(95)²w(1-0.59w)
w = 0.06822 w = 0.06822
ρ = wfc' ρ = wfc'
fy fy
ρ = 0.06822(17.3) ρ = 0.06822(17.3)
149 149
= 0.007920845638 = 0.007920846
As = ρbd As = ρbd
= 752.48 mm² = 752.48 mm²
1000π(12)² 1000π(12)²
= 752.48 = 752.48
S(4) S(4)
ρ = wfc' ρ = wfc'
fy fy
ρ = 0.1156(17.3) ρ = 0.1156(17.3)
149 149
= 0.013422 = 0.013422
As = ρbd As = ρbd
= 1275.09 mm² = 1275.09 mm²
1000π(12)² 1000π(12)²
= 1275.09 = 1275.09
S(4) S(4)
ρ = wfc' ρ = wfc'
fy fy
ρ = 0.07821(17.3) ρ = 0.07821(17.3)
149 149
= 0.009081 = 0.009081
As = ρbd As = ρbd
= 808.19 mm² = 808.19 mm²
1000π(12)² 1000π(12)²
= 808.19 = 808.19
S(4) S(4)
S = 139.8685335635 say 140 mm S = 139.8685336 say 140 mm
ρ = wfc' ρ = wfc'
fy fy
ρ = 0.1158(17.3) ρ = 0.1158(17.3)
149 149
= 0.013445 = 0.013445
As = ρbd As = ρbd
= 1277.30 mm² = 1277.30 mm²
1000π(12)² 1000π(12)²
= 1277.30 = 1277.30
S(4) S(4)
ROOF BEAM 2 4 4
4.00
4 4
4.00
DEADLOAD = 3.09 kPa DEADLOAD = 16.29 kPa Soil Pressure = 120.00 kPa (ordinary soil) DEADLOAD = 17.76 kPa Soil Pressure = 120.00 kPa (ordinary soil)
Mu = 1.4 D.L + 1.7 L.L Mu = 1.4 D.L + 1.7 L.L Mu = 1.4 D.L + 1.7 L.L
= 18.78 kN-m = 47.29 kN-m = 53.43 kN-m
Check for the minimum thickness in table 2-1: Check for the minimum thickness in table 2-1: Check for the minimum thickness in table 2-1:
h = L/16 (0.4 + fy/700) h = L/16 (0.4 + fy/700) h = L/16 (0.4 + fy/700)
= 4000/16 (0.4 + 149/700) = 4000/16 (0.4 + 149/700) = 4000/16 (0.4 + 149/700)
= 153.22 mm ( OK ) = 153.21428571 mm ( ok ) = 153.214285714 mm ( ok )
use h=300 h=d+80 h=d+80
THEREFORE USE 250mm x 300mm 380 350
say 400 mm say 350 mm
ρb = 0.85fc'β600 ρb = 0.85fc'β600
fy (600+ fy) fy (600+ fy)
= 0.85(17.3)(0.85)600 = 0.85(17.3)(0.85)600
149(600+ 149) 149(600+ 149)
= 0.06719967 = 0.0671996667
= 1.4 = 1.4
149 149
= 0.00939597 = 0.0093959732
w = ρfy w = ρfy
fc' fc'
= 0.34726302 = 0.3472630174
Mu = φ Ru bd² Mu = φ Ru bd²
bd² = Mu bd² = Mu
φRu φRu
Check for the minimum thickness in table 2-1: Check for the minimum thickness in table 2-1:
h = L/16 (0.4 + fy/700) h = L/16 (0.4 + fy/700)
= 1.35/16 (0.4 + 149/700) = 2000/16 (0.4 + 149/700)
= 51.7098214 mm ( ok ) = 187.69 mm ( ok )
As = ρbd As = ρbd
As = 0.04032bd As = 0.04032bd
As = 1230.06 mm² As = 2580.47 mm²
RB3 fs = 124.3 Mpa E = 200000 Mpa FB3 fs = 124.3 Mpa E = 200000 Mpa
a = 5m 5000 fy = 149 Mpa n = 10 a = 5m 5000 fy = 149 Mpa n = 10
b = 0m fc' = 17.3 Mpa k = 0.386 b = 0m fc' = 17.3 Mpa k = 0.386
h = 2.5 m fc = 7.8 Mpa j = 0.871 h = 2.5 m fc = 7.8 Mpa j = 0.871
t = 0.12 m fv = 110.5 Mpa R = 1.31 Mpa t = 0.12 m fv = 110.5 Mpa R = 1.31 Mpa
β = 0.85 β = 0.85
TOTAL FLOOR AREA CARRIED: TOTAL FLOOR AREA CARRIED:
Wt. of Concrete = 23.6 KN/m³ Wt. of Concrete = 23.6 KN/m³
A = 1/2(5)(2.5)() Live Loads = 1.92 kPa for rooms A = 1/2(5)(2.5)() Live Loads = 1.92 kPa for rooms
= 6.25 sq. m. = 4.8 kPa for stairs, halls, etc. = 6.25 sq. m. = 4.8 kPa for stairs, halls, etc.
ρb = 0.85fc'β600 ρb = 0.85fc'β600
fy (600+ fy) fy (600+ fy)
= 0.85(17.3)(0.85)600 = 0.85(17.3)(0.85)600
149(600+ 149) 149(600+ 149)
= 0.06719967 = 0.0671996667
= 1.4 = 1.4
149 149
= 0.00939597 = 0.0093959732
w = ρfy w = ρfy
fc' fc'
= 0.34726302 = 0.3472630174
Mu = φ Ru bd² Mu = φ Ru bd²
bd² = Mu bd² = Mu
φRu φRu
Check for the minimum thickness in table 2-1: Check for the minimum thickness in table 2-1:
h = L/16 (0.4 + fy/700) h = L/16 (0.4 + fy/700)
= 5000/16 (0.4 + 149/700) = 5000/16 (0.4 + 149/700)
= 191.52 mm ( ok ) = 191.52 mm ( ok )
As = ρbd As = ρbd
As = 0.04032(120)(180) As = 0.04032(140)(210)
As = 870.91 mm² As = 1185.41 mm²
RB4 fs = 124.3 Mpa E = 200000 Mpa FB4 fs = 124.3 Mpa E = 200000 Mpa
a = 5m 5000 fy = 149 Mpa n = 10 a = 5m 5000 fy = 149 Mpa n = 10
b = 2.5 m fc' = 17.3 Mpa k = 0.386 b = 2.5 m fc' = 17.3 Mpa k = 0.386
h = 2.5 m fc = 7.8 Mpa j = 0.871 h = 2.5 m fc = 7.8 Mpa j = 0.871
t = 0.12 m fv = 110.5 Mpa R = 1.31 Mpa t = 0.12 m fv = 110.5 Mpa R = 1.31 Mpa
β = 0.85 β = 0.85
TOTAL FLOOR AREA CARRIED: TOTAL FLOOR AREA CARRIED:
Wt. of Concrete = 23.6 KN/m³ Wt. of Concrete = 23.6 KN/m³
A = 1/2(5)(2.5)(2) Live Loads = 1.92 kPa for rooms A = 1/2(5)(2.5)(2) Live Loads = 1.92 kPa for rooms
= 12.50 sq. m. = 4.8 kPa for stairs, halls, etc. = 12.50 sq. m. = 4.8 kPa for stairs, halls, etc.
ρb = 0.85fc'β600 ρb = 0.85fc'β600
fy (600+ fy) fy (600+ fy)
= 0.85(17.3)(0.85)600 = 0.85(17.3)(0.85)600
149(600+ 149) 149(600+ 149)
= 0.06719967 = 0.0671996667
= 1.4 = 1.4
149 149
= 0.00939597 = 0.0093959732
w = ρfy w = ρfy
fc' fc'
= 0.34726302 = 0.3472630174
STRUCTURAL DESIGN ANALYSIS, ULTIMATE STRENGTH DESIGN I ENGR. MARVIN TALAVERA ARAÑO
Ru = fc' w (1-0.59w) Ru = fc' w (1-0.59w)
Ru = 17.3(0.347263)(1-0.59(0.347263)) Ru = 17.3(0.347263)(1-0.59(0.347263))
Ru = 4.78 Mpa Ru = 4.78 Mpa
Mu = φ Ru bd² Mu = φ Ru bd²
bd² = Mu bd² = Mu
φRu φRu
Check for the minimum thickness in table 2-1: Check for the minimum thickness in table 2-1:
h = L/16 (0.4 + fy/700) h = L/16 (0.4 + fy/700)
= 5000/16 (0.4 + 149/700) = 5000/16 (0.4 + 149/700)
= 191.52 mm ( ok ) = 191.52 mm ( ok )
As = ρbd As = ρbd
As = 0.04032(150)(230) As = 0.04032(170)(240)
As = 1391.04 mm² As = 1645.05 mm²
STRUCTURAL DESIGN ANALYSIS, ULTIMATE STRENGTH DESIGN I ENGR. MARVIN TALAVERA ARAÑO
GROUND FLOOR TO ROOF BEAM COLUMN
COLUMN 2
tslab = 0.10 m
bbeam = 0.20 m
dbeam = 0.30 m
Lbeam = 4.00 m
Aslab = 22.50 m²
Wt. of Roof =
= 53.1 kN
Deadload = = roof+RB
= 58.77 kN
Liveload = (4.8)(22.5)
= 185.96 kN
N = 417.8
π/4(12)²
Spacing of ties:
a) 16 x db = 256 mm
a) 48 x tie Ø = 480 mm
a) least dimension = 300 mm
COLUMN 2
tslab = 0.12 m
bbeam = 0.14 m
dbeam = 0.275 m
Lbeam = 5m
Aslab = 12.25 m²
Deadload = 34.7+4.55
= 39.25 kN
Liveload = (4.8)(12.25)
= 58.8 kN
N = Ast
A22
N = 442.99
π/4(16)²
Spacing of ties:
COLUMN 3
tslab = 0.12 m
bbeam = 0.13 m
dbeam = 0.265 m
Lbeam = 4m
Aslab = 6.25 m²
Liveload = (4.8)(6.25)
= 30 kN
N = Ast
A12
N = 229.77
π/4(12)²
Spacing of ties:
a) 16 x db = 192 mm say 200 mm
a) 48 x tie Ø = 480 mm
a) least dimension = 200 mm
fv = 110.50 Mpa R
β = 0.85
03Ag)]
DESIGN CRITERIA
fs = 124.3 Mpa E
fy = 149 Mpa n
fc' = 17.3 Mpa k
fc = 7.8 Mpa j
fv = 110.5 Mpa R
β = 0.85
DESIGN CRITERIA
fs = 124.3 Mpa E
fy = 149 Mpa n
fc' = 17.3 Mpa k
fc = 7.8 Mpa j
fv = 110.5 Mpa R
β = 0.85
03Ag)]
ERIA
= 200,000.00 Mpa
= 10.00
= 0.39
= 0.87
= 1.31 Mpa
(ordinary soil)
= 200000 Mpa
= 10
= 0.386
= 0.871
= 1.31 Mpa
(ordinary soil)
= 200000 Mpa
= 10
= 0.386
= 0.871
= 1.31 Mpa
(ordinary soil)
GROUND FLOOR TO ROOF BEAM COLUMN
COLUMN 1
Deadload = 169.48+113.28+58.41+4.07
= 345.24 kN
Liveload = (4.8)(22.5)
= 108 kN
N = 1144.32
π/4(16)²
Spacing of ties:
a) 16 x db = 400 mm
a) 48 x tie Ø = 480 mm
a) least dimension = 300 mm
COLUMN 2
Deadload = 98.05+113.28+34.7+4.55
= 250.58 kN
Liveload = (4.8)(12.25)
= 58.8 kN
Pu = 1.4 D.L + 1.7 L.L
= 1.4 (250.58) + 1.7 (58.8)
= 450.78 kN
N = Ast
A25
N = 2578.11
π/4(25)²
Spacing of ties:
a) 16 x db = 400 mm
a) 48 x tie Ø = 480 mm
a) least dimension = 250 mm
COLUMN 3
Wt. of 2nd floor column1 = 50.96 kN
Wt. of wall = 88.74 kN
tslab = 0.12 m
bbeam = 0.13 m
dbeam = 0.265 m
Lbeam = 4m
Aslab = 6.25 m²
Deadload = 50.96+88.74+17.7+3.26
= 160.66 kN
Liveload = (4.8)(6.25)
= 30 kN
N = Ast
A16
N = 1986.43
π/4(16)²
N = 3.92645303 say 4 bars
Spacing of ties:
a) 16 x db = 256 mm
a) 48 x tie Ø = 480 mm
a) least dimension = 200 mm
fs = 124.3 Mpa E =
fy = 149 Mpa n =
fc' = 17.3 Mpa k =
fc = 7.8 Mpa j =
fv = 110.5 Mpa R =
β = 0.85
0.03Ag)]
DESIGN CRITERIA
fs = 124.3 Mpa E =
fy = 149 Mpa n =
fc' = 17.3 Mpa k =
fc = 7.8 Mpa j =
fv = 110.5 Mpa R =
β = 0.85
DESIGN CRITERIA
fs = 124.3 Mpa E =
fy = 149 Mpa n =
fc' = 17.3 Mpa k =
fc = 7.8 Mpa j =
fv = 110.5 Mpa R =
β = 0.85
0.03Ag)]
200000 Mpa
10
0.386
0.871
1.31 Mpa
200000 Mpa
10
0.386
0.871
1.31 Mpa
200000 Mpa
10
0.386
0.871
1.31 Mpa
DESIGN OF COLUMN FOOTING 2
Aftg = 115.52
85.65
Aftg = 1.35 m²
L² = 1.35 m²
L = 1.16 m
Footing dimension = 1.2 m x 1.2 m
Depth of footing:
qu = Factored load
Aftg
qu = 1.4(345.24)+1.7(108)
1.35
qu = 494.03 kPa
qu = 0.11 Mpa
Vu = qu Ashaded
= (0.10758)[2500(1100-d)]
= 268.95(1100-d)
Vc = 1/6√(𝑓𝑐′) bwd
Vc = 1/6 √17.3(2500)d
Vc = 1733.05 d N
Vu = φ Vc
268.95(1100-d) = 0.85(1733.05 d)
d = 169.83 mm
Vu = qu Ashaded
= (0.10758)[(2500)² - (300+ d)²]
Vc = 1/3√(𝑓𝑐′) bcd
bc = 4(300+d)
Vc = 1/3√17.3[4(300+d)] d
Vc = 5.546(300d +d²)
Vu = φ Vc
d = 300.00 mm
Mu = 107.58(0.95)(2.5)(1.1/2)
Mu = 299.93 kN-m
Mu = φRu bd²
ρ = 0.01
ρmin = 1.40
fy
ρmin = 1.40
149.00
ρmin = 0.01
use ρ = 0.01
As = ρbd
As = 0.009396(2500)(250)
As = 3,276.00 mm²
Development length:
Furnished ld = 1100 - 75
Furnished ld = 1,025.00 mm > 351.69 mm (ok)
Acol. = 0.09 m²
Aftg. = 1.35 m²
√((𝐴𝑓𝑡𝑔.)⁄ 8.33 use 2.00
(𝐴𝑐𝑜𝑙.)) =
Use 1.2m x 1.2m footing with an effective depth to top bars of 225mm
(total depth= 300mm), with 13-16mm Ø bars on each side of the footing,
and atleast two column bars (16 -mm as given) must be extended into
the footing.
Aftg = 391.37
93.12
Aftg = 4.21 m²
3W = 4.21 m²
W = 1.40 m say 150.00 mm
Footing dimension = L = 3.00mm X W = 1.50mm
Depth of footing:
qu = Factored load
Aftg
qu = 1.4(250.58)+1.7(58.8)
4.21
qu = 98.43 kPa
qu = 0.10 Mpa
Vu = qu Ashaded
= (0.09843)[2100(925-d)]
= 206.703(925-d)
Vc = 1/6√(𝑓𝑐′) bwd
Vc = 1/6 √17.3(2100)d
Vc = 1455.76 d N
Vu = φ Vc
206.703(925-d) = 0.85(1455.76 d)
d = 132.40 mm
Vu = qu Ashaded
= (0.09843)[(2100)² - (250+ d)²]
Vc = 1/3√(𝑓𝑐′) bcd
bc = 4(250+d)
Vc = 1/3√17.3[4(250+d)] d
Vc = 5.546(250d +d²)
Vu = φ Vc
d = 225.00 mm
Mu = 98.43(0.95)(2.1)(0.925/2)
Mu = 60.69 kN-m
Mu = φRu bd²
ρ = 0.01
ρmin = 1.40
fy
ρmin = 1.40
149.00
ρmin = 0.01
use ρ = 0.01
As = ρbd
As = 0.009396(2100)(200)
As = 2,967.00 mm²
Development length:
Furnished ld = 925 - 75
Furnished ld = 850.00 mm > 225.08 mm (ok)
351.70
Verify if dowels 0r column bars extension are necessary:
Acol. = 0.06 m²
Aftg. = 1.97 m²
√((𝐴𝑓𝑡𝑔.)⁄ 8.40 use 2.00
=
(𝐴𝑐𝑜𝑙.))
Use 3.0m x 1.5m COMBINED footing with an effective depth to top bars of 225mm
(total depth= 300.00mm), with 15-16mm Ø bars on LONG side of the footing AND ,
with 8-16mm Ø bars on SHORT side of the footingand atleast FOUR
column bars (16-mm as given) must be extended into the footing.
Aftg = 88.52
93.72
Aftg = 0.95 m²
L² = 0.95 m²
L = 0.97 m
Footing dimension = 1.0 m x 1.0m
Depth of footing:
qu = Factored load
Aftg
qu = 1.4(160.66)+1.7(30)
0.95
qu = 437.82 kPa
qu = 0.44 Mpa
Vu = qu Ashaded
= (0.16122)[1600(700-d)]
= 259.52(700-d)
Vc = 1/6√(𝑓𝑐′) bwd
Vc = 1/6 √17.3(1600)d
Vc = 1109.15d N
Vu = φ Vc
259.52(700-d) = 0.85(1109.59d)
d = 151.05 mm
Vc = 1/3√(𝑓𝑐′) bcd
bc = 4(200+d)
Vc = 1/3√17.3[4(200+d)] d
Vc = 5.546(200d +d²)
Vu = φ Vc
d = 210.00 mm
Mu = 161.22(1.225)(1.6)(0.7/2)
Mu = 182.97 kN-m
Mu = φRu bd²
ρ = 0.01
ρmin = 1.40
fy
ρmin = 1.40
149.00
ρmin = 0.01
use ρ = 0.00
As = ρbd
As = 0.01247(1000)(210)
As = 922.00 mm²
Development length:
Furnished ld = 700- 75
Furnished ld = 625.00 mm > 351.69 mm (ok)
Acol. = 0.04 m²
Aftg. = 0.95 m²
√((𝐴𝑓𝑡𝑔.)⁄ 8.00 use 2.00
=
(𝐴𝑐𝑜𝑙.))
Use 1.0m x 1.0m footing with an effective depth to top bars of 210mm
(total depth= 250mm), with 5-16mm Ø bars on each side of the footing,
and atleast two column bars (16-mm as given) must be extended into
the footing.