GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN

Member of the SHORT-CIRCUIT TESTING LIAISON (STL)

Test Document
Report No.: 20029Be Contents: 29 Sheets

Test object: Three-pole operated outdoor circuit-breaker


Designation: 3AP1FG - 145 kV - 3150 A - 40 kA - 50 Hz
Rated voltage: 145 kV Rated normal current: 3150 A Rated frequency: 50 Hz

Manufacturer: Siemens High Voltage Circuit Breaker Co., Ltd., Hangzhou


Tested for: Siemens High Voltage Circuit Breaker Co., Ltd., Hangzhou
Testing station: PEHLA Testing Laboratory Berlin
Date of test: February 11 - March 05, 2020

Applied test specifications:

IEC Publication 62271-1, Edition 2.0 (2017)


IEC Publication 62271-100, Edition 2.0 (2008) + Amd. 1 (2012) + Amd. 2 (2017)
Instructions of Siemens High Voltage Circuit Breaker Co., Ltd., Hangzhou test parameters based on
GB 1984-2014, GB/T 11022-2011, DL/T 402-2016, DL/T 593-2016

According to STL Objectives and Operating Principles PEHLA issues a Test Document following exclusively the above mentioned
standards and the STL Guides wherever applicable.

Tests performed:

Mechanical endurance test at ambient air temperature with 10 000 operating cycles

Test results:

The test object has passed the test stated above without any objection.

GESELLSCHAFT FÜR ELEKTRISCHE


HOCHLEISTUNGSPRÜFUNGEN

ݸ®·­¬·¿² Õ®«­½¸¿

Management Committee

Ó¿²º®»¼ ̸±³ Ó¿¬¬¸·¿­ Þ¿¸®

Mannheim, August 12, 2020 Technical Committee

The test results only relate to the items tested.


The original document only exists at the issuing test laboratory, which can verify the content of this
document and from whom an authentic hard copy, guaranteed by seal and ribbon, can be obtained. It is not
allowed to make reproduction in extracts of this document without a written permission of the issuing test
laboratory, except copying this cover sheet accompanied by sheet 2.

02PE2001
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 2

General Information
Accreditation
The PEHLA GbR, PEHLA Testing Laboratory Berlin has been approved by DAkkS, the Deutsche Akkreditierungsstelle
GmbH (German Accreditation Body), according to EN ISO/IEC 17025 for tests in the field of high-voltage switchgear
and controlgear and power engineering equipment (Registration No. D-PL-12072-04-00).
STL Member
PEHLA (DE, CH) is a founder member of the SHORT-CIRCUIT TESTING LIAISON (STL) which has been established
in 1969. The STL provides a forum for international collaboration between testing organisations. For further information,
please see www.stl-liaison.org.
PEHLA Documents
A STL Type Test Certificate
is issued for type tests which have successfully been carried out in full compliance with the relevant standards and STL
Guides valid at the time of the test. For these tests the test object must be clearly identified by technical description,
drawings and additional specifications.
A Test Document
is issued for parts of type tests which have successfully been carried out in full compliance with the relevant standards
and STL Guides valid at the time of test. For these tests the test object must be clearly identified by technical description,
drawings and additional specifications.
A Test Report
is issued for all other tests which have been carried out according to standards, specifications and/or additional
instructions. Similarly, this test report contains all test results, details of the conditions under which the tests have been
carried out, also details relating to the behaviour of the test object, and its condition after the tests.
A Test Confirmation
is issued immediately after the tests. It confirms that the tests have been conducted and is valid only until issuing the
detailed results in an entire document.
Uncertainty of the Measurement Systems
The PEHLA Testing Laboratories apply the STL Technical Report “Handling of Measurement Uncertainties in Testing
and Test Documents” for determining the uncertainties of measurement. As long as no explicit statements are made,
the uncertainties required by the relevant standards have been complied with.
Addresses
Office: PEHLA Office Client: Siemens Gas and Power GmbH & Co. KG
Hallenweg 40 GP TP SW R&D TF BD
68219 Mannheim-Rheinau Nonnendammallee 104
Germany 13629 Berlin
www.pehla.com as partner and contractor of PEHLA GbR

Testing station: PEHLA Testing Laboratory Berlin


Nonnendammallee 104
13629 Berlin
Germany

Manufacturer: Siemens High Voltage Circuit Breaker


Co., Ltd., Hangzhou
No. 128 of 18th Road (East) of Xiasha
Industrial Area
310018 Hangzhou
China

Tested for: Siemens High Voltage Circuit Breaker


Co., Ltd., Hangzhou
No. 128 of 18th Road (East) of Xiasha
Industrial Area
310018 Hangzhou
China

02PE2001
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 3

Table of Contents

Cover Sheet ...................................................................................................................................................1


General Information .......................................................................................................................................2
Table of Contents ..........................................................................................................................................3
List of Test Participants .................................................................................................................................4
Technical Data of Test Object .......................................................................................................................5
List of Documents for Verification ..................................................................................................................6
Drawing of Test Object ..................................................................................................................................8
Test Results - Mechanical Endurance Test...................................................................................................9
Test Results - Operating Times .................................................................................................................. 10
Test Results - Recharging Characteristics and Consumption of the Control Circuit.................................. 11
Test Results - Current of Releases and Command Duration ..................................................................... 12
Test Results - Main Circuit Resistance ...................................................................................................... 13
Test Results - Tightness Test ..................................................................................................................... 14
Results and Evaluation ............................................................................................................................... 15
Photos of Test Object ................................................................................................................................. 16
Characteristics of the Closing Operation before the Mechanical Endurance Test ..................................... 18
Characteristics of the Closing Operation after the Mechanical Endurance Test ........................................ 21
Characteristics of the Opening Operation before the Mechanical Endurance Test ................................... 24
Characteristics of the Opening Operation after the Mechanical Endurance Test ...................................... 27

14PE1710
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 4

List of Test Participants

Representatives of Technical Committee:

Mr. Höhne PEHLA Testing Laboratory Berlin


Dr. Wachholz PEHLA Testing Laboratory Berlin-Marzahn

Test Engineers:

Mr. Höhne PEHLA Testing Laboratory Berlin

Representatives of Manufacturer:

Further Participants:

51PE1710
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 5

Technical Data of Test Object


Circuit-breaker
Test object: Three-pole operated outdoor circuit-breaker
Designation: 3AP1FG - 145 kV - 3150 A - 40 kA - 50 Hz
Manufacturer: Siemens High Voltage Circuit Breaker Co., Ltd., Hangzhou
Serial No.: 19/K40042868
Year of manufacture: 2019
Serial No. of drive: 1982 7569 8
Drawing No.: 1HZ 427-44700-514
3HM 427-44102-501

Ratings assigned by the manufacturer:


Rated voltage [Ur] 145 kV
Rated normal current [Ir] 3150 A
Rated frequency [fr] 50 Hz
Rated lightning impulse withstand voltage [Up] 650 kV
Rated switching impulse withstand voltage [Us] - kV
Rated power-frequency withstand voltage [Ud] 275 kV
Rated peak withstand current [Ip] 108 kA
Rated short-time withstand current [Ik] 40 kA
Rated duration of short-circuit [tk] 4 s
Rated short-circuit breaking current [Isc] 40 kA
DC component of the rated short-circuit breaking current [pcs] 45 %
Rated short-circuit making current [Ima] 108 kA
Transient recovery voltage 249 kV
Rate of rise of transient recovery voltage 2.0 kV/µs
First-pole-to-clear factor [kpp] 1.3/1.5 p.u.
Rated operating sequence O - 0.3 s - CO - 3 min - CO
Arc extinguishing medium SF6
Rated filling pressure for interruption [prm] 0.70 MPa abs. at 20 °C
Minimum functional pressure for interruption [pmm] 0.60 MPa abs. at 20 °C
Insulating medium SF6
Rated filling pressure for insulation [pre] 0.70 MPa abs. at 20 °C
Minimum functional pressure for insulation [pme] 0.60 MPa abs. at 20 °C
Driving mechanism (type) spring drive
Number of poles 3
Number of units per pole 1
Rated opening time 30 ms
Rated closing time 61 ms
Rated supply voltage of opening device [Uop] 220 V d.c.
Rated supply voltage of closing device [Uop] 220 V d.c.
Rated supply voltage of auxiliary circuits [Ua] 220 V d.c.
Rated frequency of supply voltage - Hz
Rated supply voltage of heating 220/380 V a.c.
Rated frequency of supply voltage of heating 50 Hz
Rated line-charging breaking current [Il] 50 A
Rated cable-charging breaking current [Ic] 160 A
Rated single capacitor bank breaking current [Isb] 3150 A

Further data:
Minimum and maximum ambient air temperature -30 … +55 °C
Classification C2, M2

Essential characteristics: -

Remarks: -

16SE1801
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 6

List of Documents for Verification

The manufacturer has guaranteed to the testing laboratory that the documents for verification listed in the
following table unambiguously describe the test object.

These documents for verification are kept


at the manufacturer.
at the testing laboratory.

The testing laboratory has checked that the documents for verification submitted, adequately represent
the test object, but is not responsible for the accuracy of the detailed information.

Additional
Document No. Rev.1) P/D/F Title
information
3HM 427-44102-501 D D Triple-pole circuit-breaker 145kV Sheet 1 2)
1HZ 427-44700-514 K D Circuit-breaker 3AP1 FG-1S 145kV Sheet 1-4
427-44700-514 0I P 3AP1 FG-1S-145kV BOM Sheet 1
1HG 427-44704-001 F D Interrupter unit 145 kV Sheet 1
1HG 427-44704-001 H P Interrupter unit 145 kV Sheet 1-4
592-01267-001 - D Base, top, cpl. Sheet 1
592-01267-001 0- P Base, top, cpl. Sheet 1
2HG 427-44880-001 F D Base, bottom, cpl. Sheet 1
2HG 427-44880-001 G P Base, bottom, cpl. Sheet 1-3
592-01265-001 - D Moving contact Sheet 1
592-01265-001 0- P Moving contact Sheet 1
1HG 427-44703-001, -002 I D Column Sheet 1
1HG 427-44703-001, -002 L P Column Sheet 1-3
2HG 427-08910-002 I D Operating rod, cpl. Sheet 2
2HG 427-08910-002 I P Operating rod, cpl. Sheet 1-3
2HG 427-44928-001 H D Cover, cpl. Sheet 1
2HG 427-44928-001 L P Cover, cpl. Sheet 1-3
1HG 427-44701-001 F1 D Breaker base Sheet 1
1HG 427-44701-001 I1 P Breaker base Sheet 1-3
1HG 427-44702-051 Q D Operating mechanism unit Sheet 1
1HG 427-44702-051 U P Operating mechanism unit Sheet 1-3
521-11509-490 - D SMART CHAMBER INSULATOR Sheet 1
145KV (31mm/kV)
522-11509-490 - D 145kV SMART SUPPORT Sheet 1
INSULATOR (31mm/kV)
4HT 412-10872-001 L D Compressing spring 2kNm Sheet 2
4HT 412 10873-004 k D Compression spring 1,1kNm Sheet 1
2HT 427-44720-001 M D Terminal Sheet 1
3FR 950-34812-000 B D contact lamination D124 Sheet 1
3HG 427-44905-001 C D Heating cylinder, cpl. Sheet 1
Legend: P: Parts list, D: Drawing, F: File

Remarks: 1) Revision of P/D/F


2) Included in this document

52PE1710
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 7

List of Documents for Verification

P/D/F/ Additional
Document No. Rev.1) Title
W information
3HG 427-44905-001 C P Heating cylinder, cpl. Sheet 1-2
2HT 427-44914-001 E D Heating cylinder Sheet 1
3HT 427-44907-001 F D Pipe Sheet 1
3HT 592-01263-001 - D Auxiliary nozzle Sheet 1
2HT 592-01264-001 E D Nozzle Sheet 1
3HG 592-01260-001 0- D Pin Sheet 1
2HT 427-44764-003 D D Contact cage Sheet 3
2HG 592-01261-001 0- D Tube contact Sheet 1
3HT 592-01259-001 - D Contact lamination Sheet 1
2HT 427-44923-001 H D Contact support Sheet 1-5
1HG 412-29303-041 V D Spring drive mechanism FA2 Sheet 1
SMART, cpl.
1HG 412-29303-041 X P Spring drive mechanism FA2 Sheet 1-3
SMART, cpl.
592-01071-603 0C D cabinet(smart FG-145) Sheet 1-4
2HD 427-44715 H D Bezugskennlinie Sheet 1-3
Reference mechanical travel
characteristic f. Typ 3AP1FG/FI-1S
145kV
CHN 458 00055 205 2 D W CIRCUIT DOCUMENTS Sheet 1-14
Legend: P: Parts list, D: Drawing, F: File, W: Wiring diagram

Remarks: 1) Revision of P/D/F/W

52aSE1801
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 8

Drawing of Test Object

449SE1104
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 9

Test Results
Mechanical Endurance Test

Test performed: Mechanical endurance test at ambient air temperature


Date of test: February 18 - 27, 2020
Condition of test object: After temperature-rise test of the auxiliary and control equipment (see
test document 20031Be)
Gas pressure (abs. at 20 °C): 0.70 MPa
Ambient air temperature: 20 °C ± 2 °C

Additional specification: The test was performed without any intermediate lubrication,
mechanical adjustment, maintenance or any replacement of parts.
Diagrams: Diagrams for closing and opening operations, before and after 10 000
operating cycles at rated, minimum and maximum supply voltage are
shown on sheet 18 and the following.

Operating sequence Supply voltage Number of operating sequences


minimum 500
C - ta - O - ta rated 500
maximum 500
O - t - CO - ta - C - ta rated 250
minimum 500
C - ta - O - ta rated 500
maximum 500
O - t - CO - ta - C - ta rated 250
minimum 500
C - ta - O - ta rated 500
maximum 500
O - t - CO - ta - C - ta rated 250
minimum 500
C - ta - O - ta rated 500
maximum 500
O - t - CO - ta - C - ta rated 250
minimum 500
C - ta - O - ta rated 500
maximum 500
O - t - CO - ta - C - ta rated 250
Abbreviations: C = closing operation
O = opening operation
CO = closing operation followed immediately by an opening operation
ta = time between two operations (approximately 60 s)
t = 0.3 s for rapid auto-reclosing

Remarks: -

404SE1104
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 10

Test Results
Operating Times

Test performed: Mechanical endurance test at ambient air temperature


Date of test: February 18 - 27, 2020
Condition of test object: After temperature-rise test of the auxiliary and control equipment (see
test document 20031Be)
Gas pressure (abs. at 20 °C): 0.70 MPa
Ambient air temperature: 20 °C ± 2 °C

Operating times
Operating
O C
sequence

Supply level Min Rated Max Min Rated Max

Supply voltage 143 V d.c. 220 V d.c. 242 V d.c. 187 V d.c. 220 V d.c. 242 V d.c.

tO, ∆tO, tO, ∆tO, tO, ∆tO, tC, ∆tC, tC, ∆tC, tC, ∆tC,
Time
ms ms ms ms ms ms ms ms ms ms ms ms
Before mechanical
43.0 0.3 30.5 0.4 28.9 0.4 68.4 0.5 64.8 0.5 63.2 0.5
endurance test 1)
After 2 000
45.1 0.5 31.0 0.5 29.3 0.5 69.1 0.7 65.5 0.7 63.8 0.7
operations
After 4 000
45.3 0.7 31.0 0.8 29.2 0.8 69.1 0.7 65.6 0.7 63.9 0.7
operations
After 6 000
45.5 0.8 30.8 0.6 29.2 0.7 69.5 0.6 65.7 0.7 64.1 0.6
operations
After 8 000
45.0 0.8 30.8 0.7 29.2 0.8 69.6 0.8 66.0 0.8 64.2 0.8
operations
After 10 000
45.3 0.7 30.8 0.6 29.1 0.6 69.6 0.8 66.0 0.7 64.3 0.7
operations 1)
Abbreviations: tC = closing time
tO = opening time
∆tC, ∆tO = time spread between poles

Remarks: 1) Where multiple measurements are required the average value is noted.

408SE1511
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 11

Test Results
Recharging Characteristics and Consumption of the Control Circuit

Test performed: Mechanical endurance test at ambient air temperature


Date of test: February 18 - 27, 2020
Condition of test object: After temperature-rise test of the auxiliary and control equipment (see
test document 20031Be)
Gas pressure (abs. at 20 °C): 0.70 MPa
Ambient air temperature: 20 °C ± 2 °C

Recharging characteristics of the operating device

Supply level Minimum Rated Maximum

Supply voltage 187 V d.c. 220 V d.c. 242 V d.c.

Recharging time t, s t, s t, s

Before mechanical
6.6 5.4 4.8
endurance test 1)
After 2 000
6.5 5.3 4.7
operations
After 4 000
6.5 5.3 4.7
operations
After 6 000
6.6 5.3 4.8
operations
After 8 000
6.6 5.3 4.7
operations
After 10 000
6.6 5.3 4.7
operations 1)

Consumption of the control circuit

Both springs charged Both springs discharged

Supply level Minimum Rated Maximum Minimum Rated Maximum

Supply voltage 143 V d.c. 220 V d.c. 242 V d.c. 187 V d.c. 220 V d.c. 242 V d.c.

Consumption I, mA I, mA I, mA I, mA I, mA I, mA

Before mechanical
3 8 10 7 9 11
endurance test
After 10 000
6 9 11 6 9 10
operations

Remarks: 1) Where multiple measurements are required the average value is noted.

410SE1105
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 12

Test Results
Current of Releases and Command Duration

Test performed: Mechanical endurance test at ambient air temperature


Date of test: February 18 - 27, 2020
Condition of test object: After temperature-rise test of the auxiliary and control equipment (see
test document 20031Be)
Gas pressure (abs. at 20 °C): 0.70 MPa
Ambient air temperature: 20 °C ± 2 °C

Current of releases

Operating sequence O C

Supply level Minimum Rated Maximum Minimum Rated Maximum

Supply voltage 143 V d.c. 220 V d.c. 242 V d.c. 187 V d.c. 220 V d.c. 242 V d.c.

Current of releases I, A I, A I, A I, A I, A I, A

Before mechanical
0.6 0.9 1.1 0.8 1.0 1.1
endurance test 1)
After 10 000
0.6 0.9 1.1 0.8 1.0 1.1
operations 1)

Duration of opening and closing command impulse

Operating sequence O C

Supply level Minimum Rated Maximum Minimum Rated Maximum

Supply voltage 143 V d.c. 220 V d.c. 242 V d.c. 187 V d.c. 220 V d.c. 242 V d.c.

Time t, ms t, ms t, ms t, ms t, ms t, ms

Before mechanical
39.8 27.2 25.7 51.6 48.7 47.1
endurance test 1)
After 10 000
42.6 28.3 26.9 53.3 49.4 48.0
operations 1)

Remarks: 1) Where multiple measurements are required the average value is noted.

422SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 13

Test Results
Main Circuit Resistance

Test performed: Mechanical endurance test at ambient air temperature


Date of test: February 18 - 27, 2020
Condition of test object: After temperature-rise test of the auxiliary and control equipment (see
test document 20031Be)
Gas pressure (abs. at 20 °C): 0.70 MPa
Ambient air temperature
before / after: 19.4 / 18.9 °C

Resistance

Pole A B C

Main circuit resistance R 1), 2), µ R 1), 2), µ R 1), 2), µ

Before mechanical endurance test 45.6 42.2 42.6

After 10 000 operations 49.6 47.2 46.1

Remarks: 1) Resistance measurement at a current of 100 A d.c.


Where multiple measurements are required the average value is noted.
2) The measurement of the resistance of the main circuit was made by measuring the
voltage drop between contact supports of the test object.

424SE1511
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 14

Test Results
Tightness Test

Test performed: Tightness test


Date of test: February 11 - 13 and February 27 - March 02, 2020
Condition of test object: After temperature-rise test of the auxiliary and control equipment (see
test document 20031Be) and after mechanical endurance test
Test arrangement: Three-pole operated outdoor circuit-breaker
Gas pressure (abs. at 20 °C): 0.70 MPa
Ambient air temperature: 20 °C ± 2 °C

Test conditions:
Before and after the mechanical endurance test a tightness test was performed to the test object, both in
open and closed position using an integral test method. The measurement device was calibrated with a
reference leak.

A containment was placed around the mechanical linkage into the housing for gas accumulation. At the
beginning and at the end of the test period the tracer gas concentration was measured at the bottom of
this containment.

Gas filled in test object: SF6


Mass of gas filled in the test object: 6.5 kg
Inside volume of the accumulation containment: 0.33 m3

Tightness test

Relative Permissible 1) Accumulation time


Leakage rate leakage rate leakage rate in open / closed
Frel, % per year Fp, % per year position

Before mechanical
< 0.1 < 0.5 23 h / 24 h
endurance test

After mechanical
< 0.1 < 0.5 25 h / 69 h
endurance test

Test result:
The measured leakage rate is small compared to the permissible leakage rate.

Remarks: 1) According to IEC 62271-1 subcl. 6.16.3 and 7.8, table 15

434SE2001
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 15

Results and Evaluation

During the test the test object showed the following behaviour:

– it operated on all commands and did not operate without command


– after each operation the on/off-indicator and the auxiliary switch showed correctly the position of the
test object
– the auxiliary switch and the control equipment fulfilled their functions without any objection
– the mechanical characteristics measured before, during and after the test were within the tolerances
specified in IEC Publication 62271-100 subcl. 6.101.1.1
– the resistance of the main circuit showed no remarkable change
– the tightness of the mechanical linkage into the poles measured before and after the test showed no
undue values.

After the test the following observations were made during the visual inspection:

– all mechanical and contact parts did not show any undue wear nor any distortion
– a layer of silver coating remained on all silver-coated contact areas
– insulating parts did not show any change which could influence the insulating properties
– the capability of the auxiliary and control equipment was not impaired and its contacts did not show
any undue wear nor any distortion.

According to these results after the test the test object was obviously in such condition that it was capable
of operating normally. Its functionality in respect to carrying normal and short-circuit currents, making and
breaking short-circuit currents and withstanding dielectric stresses related to its rated insulation level was
not impaired.

Thus, the mechanical operation test has been passed.

439SE1711
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 16

Photos of Test Object

Test object before test

411SE1104
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 17

Test object after test

411SE1104
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 18

Characteristics of the Closing Operation


Before the Mechanical Endurance Test
At Rated Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0000004E_Un

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 19

Characteristics of the Closing Operation


Before the Mechanical Endurance Test
At Minimum Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0000024E_Umin

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 20

Characteristics of the Closing Operation


Before the Mechanical Endurance Test
At Maximum Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0000014E_Umax

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 21

Characteristics of the Closing Operation


After the Mechanical Endurance Test
At Rated Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0520302E_Un

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 22

Characteristics of the Closing Operation


After the Mechanical Endurance Test
At Minimum Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0520322E_Umin

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 23

Characteristics of the Closing Operation


After the Mechanical Endurance Test
At Maximum Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0520306E_Umax

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 24

Characteristics of the Opening Operation


Before the Mechanical Endurance Test
At Rated Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0000007A_Un

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 25

Characteristics of the Opening Operation


Before the Mechanical Endurance Test
At Minimum Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0000031A_Umin

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 26

Characteristics of the Opening Operation


Before the Mechanical Endurance Test
At Maximum Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0000019A_Umax

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 27

Characteristics of the Opening Operation


After the Mechanical Endurance Test
At Rated Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0520295A_Un

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 28

Characteristics of the Opening Operation


After the Mechanical Endurance Test
At Minimum Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0520319A_Umin

432SE1409
GESELLSCHAFT FÜR ELEKTRISCHE HOCHLEISTUNGSPRÜFUNGEN
Report No.: 20029Be Sheet: 29

Characteristics of the Opening Operation


After the Mechanical Endurance Test
At Maximum Supply Voltage

Release current
A
2

Main contact of interrupter unit pole A


V
30

20

10

Main contact of interrupter unit pole B


V
30

20

10

Main contact of interrupter unit pole C


V
30

20

10

Auxiliary NC contact
V
30

20

10

Auxiliary NO contact
V
30

20

10

Angle of rotation corner gear pole A


°

60
40
20
0

0 10 20 30 40 50 60 70 80 90 100 110 120


ms
File 20029BeME0520305A_Umax