Professional Documents
Culture Documents
An Overview of Boiler Drum and Its Level Measurement and Control-TATA - Submited
An Overview of Boiler Drum and Its Level Measurement and Control-TATA - Submited
COVER PAGE
AN OVERVIEW OF BOILER DRUM & ITS LEVEL
MEASUREMENT & CONTROL SHEET i OF i
Date: 02-02-2011
TCE Office Code: DK
TATA CONSULTING ENGINEERS LIMITED
CONTENT SHEET
AN OVERVIEW OF BOILER DRUM & ITS LEVEL
MEASUREMENT & CONTROL SHEET i OF i
1.0 INTRODUCTION 1
8.1 Measurement 22
8.2 Control 22
10.0 CONCLUSION 33
11.0 REFERENCES 33
TATA CONSULTING ENGINEERS LIMITED
1.0 INTRODUCTION
Boiler steam drum water level is one of the most important power plant parameters to
measure and control. If the level is too low, boiler tubes will be damaged by overheating.
If the level is too high, the super heater tubes and the turbine may be damaged by
moisture or water treatment chemical carryover. As boiler operating pressures and boiler
drum wall thickness have increased, many boiler steam drums have become smaller.
This reduced boiler drum volume demands even more accurate level control. A variety
of instruments is available and approved by the ASME for power boiler level indication.
However, simply specifying one or more of these instruments will not guarantee that the
boiler level will be indicated accurately. So it is required to thoroughly understand the
operating principles of each instrument, instrument installation requirements and the
boiler operating scheme. A difference in the water density between the level instrument
and the boiler is the major source of level error. The National Board of Boiler Inspectors
has repeatedly reported that low water conditions in boilers is the number one cause of
boiler related accidents.
The boiler water/steam drum, or steam drum, is an integral part of the boiler’s design.
This vessel has three specific purposes.
Provide a volume space to hold the boiling water in the boiler.
Provide enough water volume to allow for good thermal mixing of the
cooler bottom drum water with the hotter surface interface water.
Provide surface area and volume for the efficient release of the entrained
steam bubbles from the boiler water.
The steam drum (fig. 1) is a cylinder, located at the top of the boiler. It runs length wise
from the Left side to the Right side of the boiler front side. The steam drum provides a
space for the saturated steam generated in the tubes and for the separation of moisture
from the steam. (Saturated steam is steam that has not been heated above the
temperature of the water from which it was generated). The steam drum also serves as
a storage space for boiler water, which is distributed from the steam drum to the down-
comer tubes. During normal operation, the steam drum is kept about half full of water.
The steam drum either contains or is connected to many of the important controls and
fittings required for the operation of the boiler.
Made from high Carbon Steel with high tensile strength and its working involves
temperatures around 390oC and pressures well above 350 psi (2.4MPa). The separated
steam is drawn out from the top section of the drum and distributed for process. Further
heating of the saturated steam will make superheated steam normally used to drive a
steam turbine. Saturated steam is drawn off the top of the drum and re-enters the
furnace in through a super heater. The steam and water mixture enters the steam drum
through riser tubes; drum internals (fig. 2) consisting of demister separate the water
droplets from the steam producing dry steam. The saturated water at the bottom of the
TATA CONSULTING ENGINEERS LIMITED
steam drum flows down through the down-comer pipe, normally unheated, to headers
and water drum. Its accessories include a safety valve, water-level indicator and level
controller. Feed-water of boiler is also fed to the steam drum through a feed pipe
extending inside the drum, along the length of the steam drum.
A steam drum is used without or in the company of a mud-drum/feed water drum which
is located at a lower level. A boiler with both steam drum and mud/water drum is called a
bi-drum boiler and a boiler with only a steam drum is called a mono-drum boiler. The bi-
drum boiler construction is normally intended for low pressure-rating boiler while the
mono-drum is mostly designed for higher pressure-rating.
TATA CONSULTING ENGINEERS LIMITED
Low water levels affect the internal thermal recirculation of the boiler water resulting in
cold spots in the boiler water and steam collapse. This lack of circulation also reduces
the effectiveness of the chemical water treatment and can cause precipitation of the
chemicals as chemical salts or foams.
High water levels raise steam exit velocities and result in priming or boiler water
carryover into the distribution system. Priming results in wet dirty steam while carry-over
can result in dangerous water hammer and pipe or equipment damage.
The internal fittings in the steam drum help distribute the water evenly throughout the
drum, separate the generated steam from the water and remove moisture from the
steam before it leaves the boiler (fig. 3).
a) Lower baffle plates or apron plates separate the incoming feed water and
generated steam and direct the steam to the separators.
d) Feed water leaves the economizer and enters the boiler through the
internal feed pipe and becomes "boiler water." Perforations along the side
of the feed pipe allow water to be distributed evenly throughout the steam
drum.
TATA CONSULTING ENGINEERS LIMITED
The requirements for power boiler drum level indication are clearly stated in the ASME
Boiler and Pressure Code Section I, Paragraph 60.1.1. In addition to the direct reading
gauge glass, remote liquid level indicators of various types are permitted under certain
design conditions. These guidelines give the minimum level of protection considered
suitable for safe equipment operation.
60.1.1 Each boiler, except forced-flow steam generators with no fixed steam and water
line, and high temperature water boilers of the forced circulation type that have no
steam and water line, shall have at least one water gauge glass. Except for electric
boilers of the electrode type, boilers operated at pressures over 400 psi shall be
provided with two water gauge glasses which may be connected to a single water
column or connected directly to the drum.
Two independent remote level indicators may be provided instead of one of the two
required gauge glasses for boiler drum water level indication in the case of power boilers
with all drum safety valves set at or above 900 psi. When both remote level indicators
are in reliable operation, the remaining gauge glass may be shut off, but shall be
maintained in serviceable condition.
When the direct reading of gauge glass water level is not readily visible to the operator
in the area where immediate control actions are initiated, two dependable indirect
indications shall be provided, either by transmission of the gauge glass image or by
remote level indicators. A gauge glass image transmitted to the operator’s working area
by means of a fibre optic cable, with no electrical modification of the optical signal is
considered to provide direct reading of the gauge glass water level.
The lowest visible part of the water gauge glass shall be at least 2” (50mm) above the
lowest permissible water level, as determined by the boiler manufacturer. When remote
level indication is provided for the operator in lieu of the gauge glass, the same
TATA CONSULTING ENGINEERS LIMITED
PG-60.2.1 The Water Column shall be so mounted that it will maintain its correct
position relative to the normal waterline under operating conditions.
PG-60.3 Connections
PG-60.3.1 Gauge Glasses that are required by PG-60.1 shall be connected directly to
the shell or drum of the boiler or to an intervening water column.
PG-60.3.2 The lower edge of the steam connection to a water column or gauge glass in
the boiler shall not be below the highest visible water level in the water gauge glass.
There shall be no sag or offset in the piping which will permit the accumulation of water.
PG-60.3.3 The upper edge of the water connection to a water column or gauge glass
and the boiler shall not be above the lowest visible water level in the gauge glass. No
part of this pipe connection shall be above the point of connection at the water column.
PG-60.3.4 Connections from the boiler to the water column shall be at least NPS 1.
Connections for gauge glasses connected directly to the boiler shall be at least NPS 1/2.
Connections from the boiler to the remote level indicator shall be at least NPS 3/4 and
including the isolation valve and from there to the remote level indicator at least 1/2 in.
O.D. tubing. These connections shall be completely independent of other connections
for any function other than water level indication.
TATA CONSULTING ENGINEERS LIMITED
Some typical specifications have been provided relating to various different boiler
pressures and types of trim equipment. Each of these specifications is followed with a
short list of issues relating to the system design or equipment selected (refer Table-1).
This section might be worth considering when choosing a specific design concept.
Table-1.
Sl. No. Drum PSI Indication & Tripping Concept
1. 250 2 gauge glasses + whistle alarms + Float switches
2. 1100 2 Magnetic level gauges for remote indication &
Alarms + 1 gauge glass
3. 1500 2 gauge glasses + probe type alarms
4. 1500 2 vertical probe columns with remote Indication &
Alarms + 1 gauge glass
5. 1500 2 horizontal probe columns with remote
Indication & alarms + 1 gauge glass
6. 3000 2 horizontal probe columns with remote
Indication & alarms + 1 gauge glass
7. As Reqd. 3 element control with triple redundancy D/P
Fig. 5.a & 5.b shows the details Instrument tapping point for measurement and control
of a typical single furnace Boiler Steam Drum dished taken from Left side and Right
side. The capacity of Steam Generator is 805T/Hr, Drum Pressure is 200 Kg/ Sq. Cm
(g), Super heater Stem Pressure and Temperature is 155 Kg/ Sq. Cm (g) and 540°C
respectively. Drum Internal Diameter is 1778mm. Drum Thickness is 135mm (min) &
170mm (max). The Normal Water Level (NWL) of Steam Drum is normally considered
250mm below the Centre Line of Drum.
INSTRUMENTATION DETAILS
Left Side Right Side Type of Instruments Measuring Range
P1-P1 P10-P10 D/P LEVEL TRANSMITTER (+)147mm, (-)622 mm of C.L.
P5-P5 P6-P6
P2-P2 P9-P9 DWLG (+)512mm, (-)771 mm of C.L.
P3-P3 P8-P8 EWLI
P4-P4 P7-P7 D/P LEVEL TRANSMITTER +512mm, -675 mm of C.L
TATA CONSULTING ENGINEERS LIMITED
Gauge glasses made from tubular glass or plastic are used for service up to 450 psig
and 400°F. If it is desired to measure the level of a vessel at higher temperatures and
pressures, a different type of gauge glass is used. The type of gauge glass utilized in
this instance has a body made of metal with a heavy glass or quartz section for visual
observation of the liquid level. The glass section is usually flat to provide strength and
safety. Fig. 6.b illustrates a typical transparent gauge glass.
Another type of gauge glass is the reflex gauge glass (Fig. 6.1.c). In this type, one side
of the glass section is prism-shaped. The glass is moulded such that one side has 90-
TATA CONSULTING ENGINEERS LIMITED
degree angles which run lengthwise. Light rays strike the outer surface of the glass at a
90-degree angle. The light rays travel through the glass striking the inner side of the
glass at a 45-degree angle. The presence or absence of liquid in the chamber
determines if the light rays are refracted into the chamber or reflected back to the outer
surface of the glass.
When the liquid is at an intermediate level in the gauge glass, the light rays encounter
an air-glass interface in one portion of the chamber and a water-glass interface in the
other portion of the chamber. Where an air-glass interface exists, the light rays are
reflected back to the outer surface of the glass since the critical angle for light to pass
from air to glass is 42 degrees. This causes the gauge glass to appear silvery-white. In
the portion of the chamber with the water-glass interface, the light is refracted into the
chamber by the prisms. Reflection of the light back to the outer surface of the gauge
glass does not occur because the critical angle for light to pass from glass to water is
62-degrees. This results in the glass appearing black, since it is possible to see through
the water to the walls of the chamber which are painted black.
A third type of gauge glass is the refraction type. This type is especially useful in areas
TATA CONSULTING ENGINEERS LIMITED
of reduced lighting; lights are usually attached to the gauge glass. Operation is based on
the principle that the bending of light, or refraction, will be different as light passes
through various media. Light is bent, or refracted, to a greater extent in water than in
steam. For the portion of the chamber that contains steam, the light rays travel relatively
straight, and the red lens is illuminated. For the portion of the chamber that contains
water, the light rays are bent, causing the green lens to be illuminated.
In the event of the non visibility of the gauge glass to the operator, or as a part of an
alternate design philosophy, remote level indicators can be used in place of the gauge
glass. It is important to consider the level of integrity such a device provides since it is
being used in place of a direct reading device. Indirect level monitors do not offer a
direct observation of the level, however they provide additional benefits such as control
contacts or analog signals that can be used in the alarm, tripping or control systems.
This device measures water level through conductivity probes installed in a water
column connected to the boiler (Fig. 6.2.a). Electronic Gauging System is designed as
an electronic alternative to water level gauges on boilers, giving a more reliable and
safer water level indication than conventional visual gauges. It uses the significant
difference in resistivity of water and steam in temperatures up to 370°C (698°F) to
determine the water level. A vertical row of electrodes is installed in the water level
column attached to boiler and typically aligned so that half the electrodes are above and
half below the normal water level The resistance measurement is made between the
insulated tip of each electrode and the wall of the column.
TATA CONSULTING ENGINEERS LIMITED
The manometer contains fluid with three different densities. Dd = Saturated water with
boiler water density. Dg = Water in the gauge with an unknown density, and Ds =
Saturated Steam density. A pressure balance at point “A” in this system produces the
following relationships and the actual Drum water level can be determined by the use of
these formulas
HdDd = HgDg + HsDs ---------------------equation 1.
Hs = Hd – Hg ---------------------equation 2
Hg = Hd (Dd - Ds) / (Dg – Ds) --------------equation 3.
Hd = Hg (Dg - Ds)/ (Dd – Ds) --------------equation 4.
7.2 The factors that determine the magnitude of the level error are the operating pressure,
TATA CONSULTING ENGINEERS LIMITED
the gauge sub-cooling, and the boiler drum level above the gauge return connection.
Fig. 7.2.a, b. shows the effect of operating pressure and gauge sub cooling on gauge
error. As pressure increases, the density of saturated liquid and saturated steam
converge (Fig. 7.2.a.).
Hd can be minimized by returning the water pipe from the gauge horizontally to the
drum, and by designing the drum water connection to be a minimum distance below the
lowest gauge view port.
A profile of this temperature gradient is shown in Figure 7.3.b. Many level gauges are
connected to the boiler with a “tie bar” or “water column” because the visibility of the
gauge may be adversely affected by excessive water flowing over the glass. The tie bar
short circuits the excess water from the steam supply piping. The only flow through the
gauge is from steam condensing in the gauge itself and the gauge piping. Gauges and
remote level indication devices will indicate incorrectly if boiler pressure decreases
suddenly. The temperature of the water in the gauge or reference column is normally
within a hundred degrees of the saturation temperature. If the boiler pressure decreases
rapidly, the water in the gauge will flash to steam. The steam bubbles will cause the
level in the glass to rise and will often obliterate the meniscus. Indication will return to
normal when thermal equilibrium is re-established. Systems utilizing a reference column
will indicate high as water in the reference leg flashes to steam. Indication will return to
normal very slowly as steam condenses to refill the reference leg. The reference leg can
also be manually filled to establish proper indication more quickly.
TATA CONSULTING ENGINEERS LIMITED
corrects the apparent differential for boiler water density to indicate the boiler level. Less
sophisticated devices are calibrated to read correctly at only one pressure, usually at the
normal operating pressure. They will indicate improperly when operated at pressures
above or below the calibration pressure.
Drum level control is complicated by the inverse response in level to a change in the
firing rate. This phenomenon is known as swell and shrink. When the firing rate
increases, vapour bubbles form at a faster rate and that causes the drum level to rise or
swell. A decrease in firing rate causes drum level to shrink. The problem associated with
the swell and shrink phenomenon is that a standard feedback control loop measuring
level cannot correct for load changes without wide swings in drum level. When drum
level swells, feedwater flow decreases in order to correct for level. However, feedwater
should be increased in order to match the higher steam demand. The level control loop
does not start to correct for the increase in steam flow until after drum level has fallen
below set point. The risk is that drum level can significantly drop before the control
system finally adjusts to the change in steam load.
There are three typical control strategies: single-element, two-element, and three-
element drum level control.
Single-element control measures drum level and regulate the feedwater
valve in order to maintain drum level.
Two-element control measures drum level and steam flow rate. This is a
feedforward control strategy. Feedwater flow tracks steam load while the
drum level control loop trims it.
Three-element control measures drum level, steam flow, and feedwater
flow. It is a refinement over 2-element control that improves drum level
control and responds quicker to variations in feedwater flow rate.
TATA CONSULTING ENGINEERS LIMITED
8.1 Measurement
8.2 Control
Typically one of three control strategies is employed to control the boiler drum level.
Single-element control is the minimum feedwater control system and shall be used for
the following applications:
1) During start-up or at low-load operation, when flow measurements are generally not
accurate.
2) When steam flow rate of change is nominal and feedwater supply pressure is
essentially constant.
Pressure compensation: - If the instruments used to measure drum level are sensitive to
density variations, then density compensation technologies shall be employed.
TATA CONSULTING ENGINEERS LIMITED
SWELL
NWL
DRUM LEVEL SHRINK
100
% STEAM FLOW 75 *
STEAM
FLOW FEEDWATER FLOW
50
25
0
0 TIME
By adding integral / reset control effect the level will come back to set point. The swell
or shrink results in an increase in level on steam increase. Integral control must be
tuned to be slow so the initial rise effect is reduced.
Typically, steam load is measured as mass flow, T/Hr. A differential pressure transmitter
across an orifice plate or venturi meter can be used to measure mass flow if steam
density is taken into consideration. For a saturated steam boiler, density can be
determined from the steam pressure. In 2-element drum level control, steam mass flow
TATA CONSULTING ENGINEERS LIMITED
must be converted into percent (%) feedwater valve opening engineering units. The
conversion is performed using a characterizer function block. This permits scaling
between steam mass flow measurement and valve position. It also permits linearization
of the feedwater control valve.
Drum level trim is the controlled variable from the drum level PID function block. The
engineering units are % valve opening. Drum level trim is summed with the feedwater
flow in order to regulate feedwater control valve position. The PID function block
supports controlled variable scaling. Set the minimum scale at -100% and the maximum
scale at +100%. This will enable the trim control to reduce and increase the flow control
valve position.
TATA CONSULTING ENGINEERS LIMITED
FEEDWATER PRESSURE
SWELL DRUM LEVEL
NWL
SHRINK
100
% STEAM FLOW
75
STEAM
FLOW FEEDWATER FLOW
50
25
0
0 TIME
The PID feedback signal is important because it enables integral action. In 2-element
control, the feedback signal is the feedwater control valve position (the output of the A/M
function block) minus the equivalent steam flow valve position (feedwater valve
characterizer). When the controller is in manual mode, the drum level trim PID function
block is forced into tracking mode.
While the system shown will achieve all of the desired control objectives under the
conditions specified, it has a serious drawback if the feedwater control valve pressure
differential and thus the control valve flow characteristic are not always the same. This
figure demonstrates how the performance is seriously degraded by variations in
feedwater pressure. Such feedwater pressure variations change the relationship
between steam flow and feedwater flow.
TATA CONSULTING ENGINEERS LIMITED
Boiler drum level is then forced to develop an offset from set point in order to bring the
steam flow and feedwater flow into balance.
Typically, steam load is measured as mass flow, T/Hr. A differential pressure transmitter
across an orifice plate or venturi meter can be used to measure mass flow if steam
density is taken into consideration. For a saturated steam boiler, density can be
determined from the steam pressure. The analog input block is scaled for full mass flow
at a reference pressure. The upstream static pressure is used to measure steam
density. Referring to the steam tables, a characterizer function block is configured to
convert absolute pressure into density. The actual mass flow is the measured flow
multiplied by the measured density and divided by the reference density.
The PID function block requires the process variable and set point to be in the same
engineering units. In 3-element control, the set point for the feedwater control loop is the
sum of the steam flow and drum level trim. Fortunately, both steam mass flow and
feedwater flow are measured in the same units, T/Hr, and this eliminates any need for
flow conversions.
The PID feedback signal is important because it enables integral action. In 3-element
TATA CONSULTING ENGINEERS LIMITED
control, the feedback signal is the feedwater flow rate minus the steam mass flow rate.
When the controller is in manual mode, both the feedwater and drum level trim PID
function blocks are forced into tracking mode.
TATA CONSULTING ENGINEERS LIMITED
The control loop configuration of fig. provides a feedwater controller wherein steam and
water flow measurement are not recognized if they are in an equilibrium condition
because the derivative action gives zero output if the difference between steam and
water flow remains constant. This condition is prevalent at start up and hence, the
controller provides an improved response in attaining drum level equal to drum level set
point. If water flow changes relative to steam flow then that will be taken into account.
This configuration implements level control by means of a fast level controller as
distinguished from the previous slow prior art level controller.
TATA CONSULTING ENGINEERS LIMITED
9.1 Impulse lines from the Drum Dish tapping points to the instruments and the mounting
fixtures should be designed in consideration with the downward & outward expansion of
the boiler drum as well as the boiler with respect to the fixed structure of the Boiler.
Typical 250MW PF boiler of M/s- BHEL make Boiler expansions are as follows:
Boiler Drum expansion: - Downward-16mm, Outward- 33mm.
W W Lower Front Header: - Downward 227mm, Outward- 25mm.
Density of the fluid whose level is to be measured can have a large effect on level
detection instrumentation. It primarily affects level sensing instruments which utilize a
wet reference leg. In these instruments, it is possible for the reference leg temperature
to be different from the temperature of the fluid whose level is to be measured. An
example of this is the level detection instrumentation for a boiler steam drum. The water
in the reference leg is at a lower temperature than the water in the steam drum.
Therefore, it is denser, and must be compensated for to ensure the indicated steam
drum level is accurately indicated. Ambient temperature variations will affect the
accuracy and reliability of level detection instrumentation. Variations in ambient
temperature can directly affect the resistance of components in the instrumentation
circuitry, and, therefore, affect the calibration of electric/electronic equipment. The
effects of temperature variations are reduced by the design of the circuitry and by
maintaining the level detection instrumentation in the proper environment. The presence
of humidity will also affect most electrical equipment, especially electronic equipment.
High humidity causes moisture to collect on the equipment. This moisture can cause
short circuits, grounds, and corrosion, which, in turn, may damage components. The
TATA CONSULTING ENGINEERS LIMITED
effects due to humidity are controlled by maintaining the equipment in the proper
environment.
10.0 CONCLUSION
The water level gauge glass has been used for many years to indicate boiler water level
and it is required as per the ASME Boiler and Pressure Vessel Code. A number of
supplementary indicators are available that provide convenient remote indication and
level control. All of these devices are subject to indication error because the water
measured is external to the drum and is not at the same density as the boiler drum
water. A number of techniques have been developed for each indicating device to
address this problem. The electronic dp indicator can be adjusted by an analog or digital
program. The mechanical dp indicator uses a temperature compensated reference
chamber with a pressure compensation device. The standard level gauge and the
electronic level gauge can be corrected by measuring or calculating the average gauge
water temperature and installing the gauge in the proper location. Testing confirms that
the gauge temperature is affected by a large number of conditions: steam supply and
return pipe size, length and configuration; insulation, ambient conditions and water level.
Maintaining the gauge water temperature very close to the saturation temperature will
have an adverse effect on indication if the pressure drops suddenly. However, if the
gauge temperature is significantly less than the boiler water temperature, the level error
will be significant at high pressure. The best compromise is to determine the average
gauge temperature and the gauge level error that will exist under certain boiler operating
conditions. Then, the gauge installation position can be corrected accordingly. For the
electronic level gauge, probes can be located individually to indicate properly. For the
visual level gauge, repositioning the unit can compensate for the density error. It is vital
that the gauge installation follow the manufacturer’s specifications. Only then will the
level device indicate accurately and perform as designed and tested.
11.0 REFERENCES
& Reliance.
d) Improving Boiler Room Efficiencies. Presented by David C Farthing.
e) BHEL 250MW Boiler Drum Dished Document.
f) Boiler Level Control System, US Patent. Jan. 6, 1981.
g) Control & Instrumentation, Vol-1., NTPC, Power Management Institution.