SI-WX-0114

File In/With: None


New 1113

Equipments Affected: YR SmartView Chillers


Service Information Subject: Software Enhancements for YR SmartView
Chillers (V2.06)

General
Beginning Nov. 1, 2013, enhanced software is supplied in new production YR SmartView chillers
and replacement micro-board kits. New version number is RMSYR-00.V2.06. This software is upgraded
on the basis of V2.05. It is backward compatible to all previous versions.
P/N of Micro-board Kit: 371W05405-086
P/N of Micro-board: 025W42574-000

Changes
I. Reading Precision of Chilled Liquid Temperature Setpoint via Modbus
In previous software versions, in metric mode, sometimes, the reading of chilled water temperature
setpoint through Modbus is not accurate. In new version, related algorithm is revised to make the reading
more precise.
II. Writing Chilled Liquid Temperature Setpoint via Modbus
In previous versions, in metric mode, the chilled liquid temperature of brine ice storage unit cannot be
set as a minus via Modbus. In this version, the chilled liquid temperature can be set as a negative number
under ice storage working conditions.
III. History Data
Previously, in metric mode, the temperatures and pressures shown in history deviated from the
values displayed on the screens of control panel by 0.2~0.5℃ or 0.2~0.5 KPa. Now, the program is
amended to make the history data more accurate.
IV. New Current Limit Response
To prevent motor current from swinging and overshooting current limit setpoint, in new software
version, proportional slide valve loading/unloading is applied within a band around the Current Limit
Setpoint (Local or Remote). See figure 1.
When the motor current is lower than 93% of motor current limit setpoint, the slide valve loads
normally as per liquid temperature control logic.
When the motor current is in the band of 93%~99.5% of the motor current limit setpoint, the slide
valve can load, but load pulse will proportionally decrease as the motor current increases. Meanwhile, it
cannot exceed the load pulse time that is calculated according to liquid temperature demand. The longest
load pulse time is 2 seconds.
When the motor current is at 99.5%~100.5% of the motor current limit setpoint, the slide valve does
not load or unload.
When the motor current is in the band of 100.5%~104% of the motor current limit setpoint, the slide
valve unload proportionally. The unload pulse increases proportionally as the motor current increases.

YORK(Wuxi) Air Conditioning & Refrigeration Co., Ltd. 1


The longest unload pulse time is 2 seconds.
Above 104% of the motor current limit setpoint, the slide valve continuously unloads.

Continuous Unloading
104%
Percentage Motor Current Limit

Full Unload Pulse Width (2s)


Proportional
Unloading Min (Current Limit Pulse, Liquid Temp. Pulse)
100.5% Pulse)
Hold No Loading or Unloading
99.5%

Proportional
Loading
Full Load Pulse Width (2s)
93%
Normal
Loading

Time ->
Fig. 1 New Current Limit Control Logic
V. Low Pressure Protection
In previous software versions, when smart freeze protection is enabled and the leaving chilled liquid
temperature setpoint is less than 38°F, low pressure fault is not detected. In the new version, whether
the smart freeze protection is enabled or not, low pressure protection will work.
VI. Minimum Load Logic
In previous versions, within 3 minutes after start, the slide valve is held and does not load after oil
pressure differential is established. Only after 3 minutes elapses, is the minimum load logic executed. In
this version, in 15 ~180 seconds after start, if ice storage is activated (Both “Ice Storage” and “Brine” are
chosen. Leaving chilled liquid temperature setpoint is less than 32°F), the minimum load logic is
executed as soon as the oil pressure differential is achieved.
VII. nandFlash Drive Program Upgrade
Prior to this, the nandFlash drive program of Windows CE supported only K9F1208. Now, besides
K9F1208, it also can support K9F1G08.

YORK(Wuxi) Air Conditioning & Refrigeration Co., Ltd. 2