PIX

Metal-clad Switchgear up to 24kV

Product Catalog
Schneider Electric
Make the most of your energy SM

As a global specialist in energy management with operations in more than 100 countries, Schneider
Electric TM offers integrated solutions across multiple market segments, with leadership position
in energy and infrastructure, industrial process control, building automation, and data centers/
networks as well a large market share in residential applications segment. We are focused on
delivering safer, more reliable, and efficient energy for our customers. Schneider Electric employs
more than 140,000 people around the world and generated 24 billion in sales in 2012. Schneider
Electric helps you make the most of your energy!

Schneider Electric in China


Schneider Electric established its first joint-venture factory, Merlin Gerin, in Tianjin in 1987, and thus brought
circuit breaker technology to China, replacing the traditional fuse. This move greatly enhanced the safety of power
utilization for Chinese users and contributed tremendously to establishment of new standards for breakers in China.
In early 90s, Clipsal by Schneider Electric introduced switch panel to China, ending the age of using ropes to switch
on/off lights in China.

The substantial investment from Schneider Electric has provided strong support for the development of Chinese
economy and offered cutting-edge product support and superior technical services for Chinese customers. Medium/
low voltage appliances, converters, contactors and other industrial products from Schneider Electric are widely used
in China to drive its economic growth, greatly facilitating and advancing its industrial process.

Schneider Electric now has 53 offices, 28 factories, 7 distribution centers, one learning institute, 3 research and
development centers, one laboratory, 700 distributors and a nation-wide sales network in China.Schneider Electric
China employs approximately 28,000 employees. Collaborating with its partners and resellers, Schneider Electric
has helped create thousands of employment opportunities in China.

Schneider Electric Architecture


With an in-depth understanding of five key markets, excellent care services for clients and unparalleled experience
in energy management, Schneider Electric has grown into an integrated solution provider from a leading product
and equipment supplier. This year, by converging its technical strength and expertise in five key domains including
building, IT, security, electricity, industrial process and equipment, Schneider Electric brought its high-quality
products and solutions under a single system architecture, delivering an open, transparent, energy-saving and
efficient architecture for customers across various sectors on a standard interface. It enables
savings of up to 30% on capital and operating expenses for enterprise customers.

2
PIX Contents
Metal-clad Switchgear up to 24kV

General 2

PIX Design and Structure 5


PIX Design 5

PIX Product Structure 7

Product Data 8
Standards 8

Technical Characteristics 8

IP 9

Dimensions 10

Product Nameplate Illustration 11

Operating Conditions 11

HVX Vacuum Circuit Breaker 12

VAH Indoor High-Capacity Vacuum Circuit Breaker 15

CVX Vacuum Contactor -Fuse-combination Unit 16

ESW Earthing Switch 18

PIX Primary Scheme and Application Example 19


Primary Schematic Diagram of PIX-12 kV Switchgear 19

PIX-12kV Application example 29

Primary Schematic Diagram of PIX-24kV Switchgear 30

PIX-24kV Application example 35

Ordering Instructions 36

Layout and Installation 37


Primary scheme on plan layout of distribution room 37

Construction of installation base of switchgear 37


Installation of switchgear 39

1
PIX General
Metal-clad Switchgear up to 24kV

In the present market environment, a safe, reliable and simple configuration scheme is necessary for
power generation, power distribution and power customers. To comprehensively satisfy customers’
needs and special requirements, we develop the PIX products.

b The PIX switchgear belongs to the metal-clad and movable-type indoor AC metal-enclosed
type, with the improved PIX scheme, including the contactor cubicle (PIX-M) applicable to the
FC circuit and the generator circuit breaker cubicle (PIX-Gen) used for power distribution at the
generator circuit and industrial and mining enterprises, starting of high capacity motors, and other
occasions

b PIX-12kV data are as below:


v Rated voltage: 7.2kV, 12kV
v Rated current: 630A~4,000A, 5,000A/6,300A (generator circuit breaker cubicle)
v Rated short-circuit breaking current: 20kA~50kA, 63kA (generator circuit breaker cubicle)
v Rated short-circuit peak value withstand current: 125kA/150kA, 160kA (generator circuit breaker
cubicle)
v Cubicle width: PIX contactor cubicle: 325mm, 650mm; PIX circuit breaker cubicle: 550mm, PIX Indoor AIS Metal-clad Switchgear

650mm, 800m and 1,000mm; PIX generator circuit breaker cubicle: 1,200mm

b PIX-24kV data are as below:


v Rated voltage: 24kV
v Rated current: 630A~4,000A
v Rated short-circuit breaking current: 20kA~40kA
v Rated short-circuit peak value withstand current: 100kA at most
v Cubicle width: 800mm and 1,000mm

b The PIX switchgear gathers the technical achievements of Schneider Electric in the global
medium voltage field and satisfies the following application needs of customers:
v Personal safety and reliable operation
v Simple operation and easy maintenance
v Easy installation and less installation cost
v Flexible solutions
v Less maintenance reducing the operation cost

Personal Safety and Reliable Operation


v The improved and reliable five-prevention blocking device is equipped
v The protection class requirements are strictly executed
v The closure interlocking is equipped and the racking in-out operation of the truck shall be carried Contactor cubicle
out when the door of the truck compartment is closed
v The earthing switch adopts the quick closing mechanism which owns the short circuit making
capacity
v The earthing switch can be added with the latching electromagnet, to realize electric interlocking
between the grounding switch and the switchgear equipment
v For the power cable and control circuit opening, the rubber seal ring is used, so as to prevent the
dirt and small animals from invading and protect the insulation layer of the cable
v Inside the three high-voltage compartments of the cubicle, the reasonable pressure relief
channels are provided, to release the pressure generated during the inner arc fault

2
PIX General
Metal-clad Switchgear up to 24kV

b There are safe and reliable interlocking apparatus provided in the PIX switchgear, to fully
satisfy the five-prevention interlocking requirements
v Only when the circuit breaker truck is at the test or service position, closing operation can be
performed to the circuit breaker, and after the circuit breaker is closed, the truck cannot be
moved, so as to avoid pulling or pushing the circuit breaker under load by mistake
v Only when the earthing switch is at the opening position, the circuit breaker truck can move
from the test position to the service position. Only when the circuit breaker truck is at the test
position, the closing operation can be performed to the earthing switch. Therefore, closing
live earthing switch by mistake can be avoided, and closing circuit breaker when the earthing
switch is at the service position can be avoided
v When the earthing switch is at the opening position, cable compartment door, cannot be
opened, so as to avoid entering live compartments by mistake
v When the circuit breaker truck is at the disconnected or service position, and there is no
control voltage, the switch can only be opened manually, and cannot be closed
v When the circuit breaker truck is at the service position, the secondary plug is locked and
cannot be pulled out
v Each cubicle can be equipped with electric interlock Generator circuit breaker cubicle

Simple Operation and Convenient Maintenance


v The cubicle can be operated and maintained at the front
v The circuit breaker truck can be pushed by either the power-driven or manual way
v Circuit breaker trucks of the same specification are interchangeable without any adjustment
v As to the sheet-metal working, the TRUMPF NC machining tools with the high machining
precision, good technology and strong interchangeability are used
v The adopted compact design can effectively save the space
v The indoor medium-voltage vacuum circuit breaker and contactor-fuse composite apparatus
with corresponding data can be assembled
v The earthing switch can be operated manually or by the power-driven way

Easy Installation and Less Installation Cost


v Cubicle splicing is easy;
v Installation against a wall or back to back installation is available;
v The cable connection space is sufficient in the cable compartment and three pairs of cables
can be connected in parallel for each phase at most, easy to installment. Besides, according
to the needs, the voltage transformer, lightning arrester and other components can be added
in the cable compartment;

3
PIX General
Metal-clad Switchgear up to 24kV

The PIX switchgear can be used in the motor, transformer, capacitor and most distribution circuits and can provide
the reliable centralized control and protection function for these circuits.

The PIX switchgear passes the comprehensive type test verification and is widely recognized by customers.

Type test reports obtained in domestic authoritative labs

The PIX switchgear is constituted by the cubicle and withdrawable part. With the top entry incoming & outgoing,
cable incoming & outgoing and other functional schemes, it can become the power distribution unit in all scheme
forms after the arrangement and combination.

The PIX switchgear can be equipped with the vacuum circuit breaker and vacuum contactor-fuse composite
apparatus, widely used in the MV fields as below:

Application Scope

v Data center
v Power grid
v Wind power
v Power plant
v WWW
v Oil & Gas
v Infrastructure
v Building
v Industry
v MMM Data center Wind power

Oil & Gas Infrastructure Building

4
PIX PIX Design and Structure
Metal-clad Switchgear up to 24kV

PIX Design
v Four entirely independent functional compartments are respectively the circuit breaker compartment, busbar compartment, cable
compartment and LV compartment, and the protection class of all the compartments reaches IP2X; except the LV compartment, the other
three compartments are respectively equipped with the pressure relief channel. With the top entry incoming & outgoing, cable incoming &
outgoing and other functional schemes, it can become the power distribution unit in all scheme forms after the arrangement and combination.

Circuit breaker Compartment


The rail is installed at the two sides of the compartment to enable the truck to slide
from the disconnected/test position to the service position in the cubicle. When the
truck moves from the disconnected position to the service position, the upper and
lower isolating shutters on the spout are automatically opened with the truck linkage;
during its reverse movement, the isolating shutters are automatically closed until
the truck retreats to a test position, and fully covers the fixed spout, thus forming an
effective isolation. Meanwhile, the linkage between the upper and lower isolating
shutters can lock the isolating shutter on the live side during the maintenance, so
as to ensure the maintenance personnel stay away from the live part. Through the
observation window on the upper door, the position of the truck in the compartment,
the indication of closing and opening and spring charge status can be observed. circuit breaker compartment

Busbar Compartment
The main busbar are joined by mutual connection of single sets, and fixed through
the branch busbar and fixed spout. The main busbar and interconnection busbar
are of arched section or rectangular section. Double busbars are used for the large
current load. The branch busbar is connected to the fixed spout and main busbar
through the bolts, requiring no other supports. The main busbar and branch busbar
are equipped with heat-shrinkable sleeve, and the flame retarded T-shaped insulating
cover is used at the junction, so as to ensure reliable compound insulation. The
busbars of the adjacent cubicles are fixed by the bushing.

Busbar compartment

Cable Compartment
Middle-rolling type is used for the switchgear, the CT is installed on the back wall
of the cable compartment, and the earthing switch is installed on the fixed plate of
the spout, so as to avoid distortion of operating shaft for earthing switch. The cable
compartment has large interior space, so multiple cables can be connected. Also, the
connection height of cables is high and the installation is convenient.

Cable compartment

LV Compartment
The protection relay, instrument, potential indicator and secondary equipment with
special requirements can be installed in the relay instrument compartment. The
control wiring is laid in the wiring tray with enough space and metal cover, making
the secondary wires separated from the high voltage compartment. The wiring tray
at the left side is reserved for controlling the incoming and outgoing of the thin wires,
and the thin wires in the switchgear are laid at the right side. If necessary, the busbar
crossing holes can be reserved on the roof of the relay instrument compartment for
the convenience of the construction. During the connection process, the top cover of
the instrument compartment can be turned for the convenience of the installation of LV Compartment
small busbar.

5
PIX PIX Design and Structure
Metal-clad Switchgear up to 24kV

Enclosure and Others


The enclosure of the switchgear mainly uses highly corrosion resistant Alu-zinc plates, which is formed through
the double-bending and assembly after CNC machining. The special design of the side plate not only can form a
4 mm air layer between two adjacent cubicles during splicing of cubicles to reduce the impact of internal arc fault
between cubicles, but also feature high precision and high rigidity. The assembled structure is used for the cubicle
and connected by rivet nuts, high-strength bolts and stainless steel blind rivets. No escape holes are required
between cubicles, thus making the installation easy, appearance aesthetic and reliability high.

Truck
v According to different purposes, the trucks can be divided into circuit breaker truck, voltage transformer truck,
metering truck and disconnector truck. 100% free interchangeability is available for the trucks with the same
specification. There are test position and service positions in the cubicle for the truck, each equipped with
positioning device to ensure the reliability of interlocking. The operation must be carried out according to the
operation procedure for operator error preventing interlock.
v The secondary wires for signal, protection and control between the switchgear and circuit breaker truck are
connected by multi-contact plugs.
v The power-driven raking in-out for the circuit breaker truck and disconnector truck can be realized.
v The door closing operation can be realized.

Pressure Relief Device


The pressure relief device is provided on the upper parts of the circuit breaker truck compartment, busbar
compartment and cable compartment. When the arc occurs due to the fault in the circuit breaker or busbar,
the air pressure inside the switchgear will rise. The special seal ring mounted on the door encloses the front of
the cubicle, and the pressure relief metal plate equipped on the top will be automatically opened to release the
pressure and exhaust the air, so as to ensure the safety of personnel and switchgear.

6
PIX PIX Design and Structure
Metal-clad Switchgear up to 24kV

Position Interlocking of Secondary Plug and Circuit Breaker Truck


The connection of secondary wires of the switchgear and circuit breaker truck is realized through the secondary
plug. The dynamic contact of the secondary plug is connected to the circuit breaker truck via one nylon extension
tube, and the secondary fixed contact socket is installed on the upper right of truck compartment in switchgear.
Only when the circuit breaker truck is at the disconnected position, the secondary plug can be inserted and
removed; when the circuit breaker truck is at the service position, the secondary plug will be locked due to the
mechanical interlocking effect, so it cannot be removed. Since the closing mechanism of the circuit breaker truck is
locked by the electromagnet, before the secondary plug is connected, the switch can only be opened and cannot
be closed.

CAP. Voltage indicator


If required by the customer, the option (i.e. CAP. Voltage indicator) can be provided to test the primary circuit
operation in the switchgear. This device is constituted by high-voltage transducer and potential indicator, and
integrated through outdoor cable connection. This device can not only indicate the live state of high voltage circuit,
but also coordinate with the electromagnetic lock to realize the forced lockout of switching handle, so as to prevent
earthing switch from closing under live conditions and from entering live compartments by mistake, thus improving
the error prevention performance of the supporting products.

PIX Product Structure

A: Circuit Breaker
Compartment
B: Relay Instrument
Compartment
C: Busbar Compartment
D: Cable Compartment

7
PIX Product Data
Metal-clad Switchgear up to 24kV

Standards
b PIX switchgear abides by the following standards:
v GB3906, IEC62271-200
v GB/T11022, IEC62271-1
v GB1984
v GB1985

PIX-12kV Technical Characteristics


No Name Unit PIX-12kV PIX-Gen
1 Rated voltage 12 12
Short time To the ground,
42 42
power frequency phase-to-phase
withstand
Isolating break 48 48
Rated insulation voltage (1 min) kV
2
level Lightning To the ground,
75 75
impulse phase-to-phase
withstand
voltage (peak) Isolating break 85 85

630 630
1250 1250 1250 1250
1600 1600 1600 1600
3 Rated current A 2000 2000 2000 2000
2500 2500 2500 2500
3150 3150 3150 3150 5000
4000* 4000* 4000* 4000* 6300*
4 Rated short time withstand current (4s) 25 31.5 40 50 63
kA
5 Rated peak value withstand current 63 80 100 125 150 160
6 Rated short-circuit breaking current kA 25 31.5 40 50 63
7 Rated short-circuit making current (peak value) kA 63 80 100 125 150 160
8 Rated frequency Hz 50
Rated short time power frequency withstand voltage
9 kV 2
of auxiliary circuit and control circuit (1 min)
Rated voltage of opening/closing devices and
10 V AC 110/220 DC 110/220
auxiliary circuit
≤150+CT**(≤630A)
≤100+CT**(≤1250A)
11 Resistance of main circuit μΩ ≤55
≤50+CT**(≤2000A)
≤45+CT**(≥2500A)

Note: All technical data are obtained strictly in accordance with the type test data rather than the theoretical calculating value. PIX-
Gen is the generator circuit breaker cubicle.
* Data corresponding to the forced air cooling.
** CT is the DC resistance of the current transformer.

Contactor Cubicle Technical Characteristics


No. Name Unit Value
1 Rated voltage kV 7.2 12
2 Rated frequency Hz 50 50
Power frequency withstand voltage Phase-to-
3 kV 32/34 42/48
phase/break (1 min)
Rated lightning impulse withstand voltage Phase-
4 kV 60/70 75/85
to-phase/break
5 Max main busbar current A 4000 4000
6 Rated current A 250 160
7 Rated short time withstand current (main busbar)/4s kA 50 50
8 Rated peak value withstand current (main busbar) kA 125/150 125/150
9 Rated prospective short-circuit breaking current kA 50 50
Rated prospective short-circuit making current (peak
10 kA 150 150
value)

8
PIX Product Data
Metal-clad Switchgear up to 24kV

PIX-24kV Technical Characteristics


No. Name Unit Value
1 Rated voltage 24

Short time To the ground,


65**
withstand phase-to-phase
current (1 min) Isolating break 79**
Rated insulation kV
2 Lightning To the ground,
level 125
impulse phase-to-phase
withstand
voltage (peak Isolating break 145
value)
630
1250 1250 1250
1600 1600 1600
3 Rated current A 2000 2000 2000
2500 2500 2500
3150 3150 3150
4000* 4000* 4000*
4 Rated short time withstand current (4s) 25 31.5 40
kA
5 Rated peak value withstand current 63 80 100
6 Rated short-circuit breaking current kA 25 31.5 40
7 Rated short-circuit making current (peak value) kA 63 80 100
8 Rated frequency Hz 50
Rated short time power frequency withstand voltage
9 kV 2
of auxiliary circuit and control circuit (1 min)
Rated voltage of opening/closing devices and
10 V DC110, 220 / AC110, 220
auxiliary circuit
≤150+CT***(≤630A)
≤100+CT***(≤1250A)
11 Resistance of main circuit μΩ
≤50+CT***(≤2000A)
≤45+CT***(≥2500A)

Note: All technical data are obtained strictly in accordance with the type test data rather than the theoretical calculating value. PIX-
Gen is the generator circuit breaker cubicle.
* Data corresponding to the forced air cooling.
** Values 65 and 79 are executed based on the DL404-2007 Standard.
** CT is the DC resistance of the current transformer.

IP
The protection class of switchgear enclosures is IP4X and that of compartments is IP2X; when the door of circuit
breaker compartments is opened, the protection class of switchgear is still IP2X.
v Please contact the manufacturer if there is any special requirement

9
PIX Product Data
Metal-clad Switchgear up to 24kV

Dimensions
PIX-12kV
Items and descriptions Unit Value
Height (h) mm 2250
The branch busbar rated currents are 550
1,250A and below, and the thermal stability mm 650
currents are 31.5kA and below 800(optional)
The branch busbar rated currents are
1,250A and below, and the thermal stability mm 800
Width (w) currents are 40kA and 50kA
The branch busbar rated current is 1,600A 800
mm
or 2,000A 1000(optional)
The branch busbar rated current are
mm 1000
2,500A and above
Depth (d) mm 1400/1600
Weight kg 800-1200

Remark: 1. For the scheme of which the rated current is 4,000A, the cubicle depth is 1,600 mm.
2. Except 4,000A, for other current ratings, another 200 mm shall be added based on 1,400 mm of the cubicle depth.

PIX-24kV

Items and descriptions Unit Value


Height (h) mm 2400
The branch busbar rated current are 800
mm
1,250A and below 1000(optional)
Width (w)
The branch busbar rated currents are
mm 1000
1,600A and above
Depth (d) mm 1860/2260
Weight kg 800-1200

Contactor Cubicle

Items and descriptions Unit Value

Height(h) mm 2250

Width (w) mm 325, 650

Depth (d) mm 1400

Weight kg 600(325 cubicle width), 800(650 cubicle width)

Generator circuit breaker cubicle

Items and descriptions Unit Value

Height(h) mm 2240

Width (w) mm 1200

Depth (d) mm 1960

Weight kg 1700

10
PIX Product Data
Metal-clad Switchgear up to 24kV

Product Nameplate Illustration

PIX- W T

Scheme No.
Recommended scheme
Cubicle width data (expressed in thousands
digit and hundreds digit)
Cubicle width type

Rated short-circuit breaking current


(expressed in tens digit and units digit)

Rated current (A) (expressed in thousands


digit and hundreds digit)

Circuit breaker type (Z: vacuum)


Rated voltage (kV) (expressed in tens digit
and units digit)

M; contactor cubicle Gen: Generator circuit


breaker cubicle, except these two cubicles,
others shall not be marked with the code

Basic model

Note: Use “0” to substitute the first one when there is no figure in the first place of the first two digits.
Examples: (1) PIX-12Z1231W06T001 represents the metal-clad movable-type indoor AC metal-enclosed switchgear 12 kV, 1,250A,
31.5 kA, 650 mm cubicle width (feeder cubicle).
(2) PIX-24Z1231W08T001 represents the metal-clad movable-type indoor AC metal-enclosed switchgear 24 kV, 1,250A,
31.5 kA, 800 mm cubicle width (feeder cubicle).

Operating Conditions
Normal Operating Conditions
a) Ambient temperature: -25ºC ~ +40ºC,the daily average temperature is no more than 35ºC.
b) Altitude: no higher than 1,000m.
c) The ambient air should not be obviously polluted by the dust, smoke, corrosive or combustible gas, vapor or salt
mist.
d) Humidity: daily average relative humidity ≤95%, monthly average relative humidity ≤90%.
e) Seismic intensity: No more than 8 Richter scale.
f) Amplitude of electromagnetic interference sensed in the secondary system: No more than 1.6 kV.

Measures for Condensation and Corrosion Protection


To protect against the danger caused by condensation generated in the climatic environment with a big change
in humidity, the heaters are provided respectively in the circuit breaker compartment and cable compartment, to
facilitate their use in the environment stated above and avoid corrosion.

Special Operating Conditions


In case that the operating conditions go beyond the normal environment conditions specified in GB/T 11022 and
these technical specifications, the customer should consult with the manufacturer.

11
PIX HVX Vacuum Circuit Breaker
Metal-clad Switchgear up to 24kV

Overview
HVX series vacuum circuit breaker has condensed hundreds of years of wisdom
crystallization of Schneider Electric in the field of medium voltage. As a new
generation of circuit breaker developed for the Chinese market based on global
manufacturing and design experiences, it is suitable for PIX switchgears and
other mainstream air insulated switchgears, and is widely used in the power grid,
petrochemical industry, public infrastructure, industrial and mining enterprises and
transportation, etc.

v Relying on the patent design of VG series vacuum arc-extinguishing chamber


and the thorough understanding of the technology of vacuum arc-extinguishing
chamber of Schneider Electric, make VG series vacuum arc-extinguishing
chamber strike a line for itself with high stability, large capacity, small volume and HVX Circuit Breaker
long life in the field of medium voltage vacuum
v The spring operating mechanism adopting modular design is simple and reliable,
and is equipped with three-phase independent cam output to provide the best
characteristics matching for the vacuum arc-extinguishing chamber. The first level
of output of the transmission mechanism and the unique bearing transmission
design simplify the mechanism while ensuring the stable operation of the
mechanism
v Meets the requirements of application in a variety of special occasions, and is
widely used in various fields

Applications

v Rated short-circuit breaking current and non-full-


load current
v Asymmetrical current breaking
v Auto reclosing
v Switching off and closing non-loaded cable and
non-loaded overhead lines
v Single or back-to-back capacitor bank breaking
current
v Out-of-phase breaking
v Switching off and closing non-loaded transformer Advanced one-time tube sealing and
exhausting technique
v Out-phase grounding fault current breaking
v Breaking short-circuit current with large starting
gradient of transient recovery voltage
v Opening and closing of the motor and the non-
loaded inductance

VG series vacuum arc-exhausting


chamber

12
PIX HVX Vacuum Circuit Breaker
Metal-clad Switchgear up to 24kV

HVX 12kV main Technical Characteristics

Items Unit Value

Rated voltage kV 3.6,7.2,12

Rated frequency Hz 50,60

Rated power frequency withstand voltage kV 42

Rated lightning impulse withstand voltage 75


kV
(peak)

630 630

1250 1250 1250 1250

1600 1600 1600 1600

Rated current A 2000 2000 2000 2000

2500 2500 2500 2500

3150 3150 3150 3150

4000* 4000* 4000* 4000*

Rated short-circuit breaking current kA 25 31.5 40 50

Rated short time withstand current (4S) kA 25 31.5 40 50

Rated short-circuit making current (peak) kA 63 80 100 125/150

Rated peak value withstand current (peak) kA 63 80 100 125/150

O-0.3s-CO-15s-CO
Rated switching sequence Auto reclosing
Switching cycles O-0.3s-CO-180s-CO

Rated switching sequence Non-auto reclosing O-180s-CO-180s-CO

Rated operating voltage V AC110/220 DC110/220

* When the rated current is 4000A, and forced air cooling shall be provided.

Product Model

HVX 12 25 06 E
Withdrawable structure
Model
F
Fixed structure
Rated voltage (kV)
Rated current

Rated short-circuit
breaking current
(kA)

13
PIX HVX Vacuum Circuit Breaker
Metal-clad Switchgear up to 24kV

HVX 24kV main technical characteristic

Items Unit Value

Rated voltage kV 24

Rated frequency Hz 50,60

Rated power frequency withstand voltage kV 50,65*

Rated lightning impulse withstand voltage 125


kV
(peak)

630

1250 1250 1250

1600 1600 1600

Rated current A 2000 2000 2000

2500 2500 2500

3150 3150 3150

4000** 4000** 4000**

Rated short-circuit breaking current kA 25 31.5 40

Rated short time withstand current (4S) kA 25 31.5 40

Rated short-circuit making current (peak) kA 63 80 100

Rated peak value withstand current 63 80 100


kA
(peak)

O-0.3s-CO-15s-CO
Rated switching sequence Auto reclosing
O-0.3s-CO-180s-CO
Switching cycles
Rated switching sequence Non-auto O-0.3s-CO-180s-CO
reclosing

Rated operating voltage V AC110/220 DC110/220

Note: All technical parameters are got in strict accordance with the type test data, not the theoretical calculation values.
* Data 50kV is implemented according to IEC 62271-100: 2001 standard.
** When the rated current is 4000A, and forced air cooling shall be provided.

Product Model

HVX 24 25 06 E
Withdrawable structure
Model

Rated voltage (kV)


Rated current
Rated short-circuit
breaking current
(kA)

14
PIX VAH Indoor High-Capacity Vacuum
Metal-clad Switchgear up to 24kV
Circuit Breaker

Regardless of power plants, power stations, industry or consumer substations and OEM,
you need flexible and reliable circuit breakers to meet the high mechanical and electrical
breaking requirements.
Schneider Electric VAH vacuum circuit breaker is based on decades of experience in the
field of vacuum technology, and is specially developed for high-capacity requirements,
with rated current up to 6300A. It is applicable to PIX-Gen switchgear, and is also an ideal
selection for the heavy industry and the generators to protect high-capacity circuit breakers.

Especially suitable for modification and expansion


The rated voltage of circuit breaker is up to17.5kV, while the rated lightning impulse
withstand voltage (peak) is up to 95kV. The design is flexible and can be used for fixed
installation and withdrawable truck. It is especially applicable to the modernized and
extended installation system. Under 12kV rated voltage, 63kA rated short-circuit current
breaking can be made.
The pole adopts extremely strong support and open-type structure that can be cooled by
air, which is designed based on meeting the requirements of high mechanical and electric
breaking cycle, high insulation level and large rated current. Schneider Electric's VAH
circuit breaker conforms to all relevant IEC standards. It has been applied to the industrial
production departments all over the world.

The traditional solid circuit breaker pole structure


The design of VAH circuit breaker is based on the traditional circuit breaker pole structure
of Schneider Electric. The pole is supported on the same holder through the insulator. The
Users First
structure is compact. b Structural reliability
Through the strong support, the vacuum arc-extinguishing chamber is firmly installed in the b Rated current up to 6300A
pole section, so as to ensure that it won't suffer any outside interference. During the period b Professional service experience
of breaking and making, the forces generated by the arc only act on the contact parts of the b Provision of special solutions to
arc-extinguishing chamber. This kind of simple and flexible structure of circuit breaker can users
provide solutions for the special needs of different users.

VAH generator circuit breaker Technical Characteristics


Items Unit Value
Rated voltage kV 12 13.8 17.5
Rated frequency Hz 50/60
Rated power frequency
kV 28/42 38/42 38/42
withstand voltage
Rated lightning impulse
withstand voltage kV 75 95 95
(BIL)
Rated current Maximum of A 6300* 6300* 6300*
Maximum of
Rated short-circuit current(3s) 63 63 50
kA
Rated short-circuit breaking Maximum of
63 63 50
current kA
Rated short-circuit making Maximum of
160 160 125
current kA
Number of cycles of
mechanical operation of the 10000
driving mechanism
Number of cycles of rated
10000
current electric breaking

*Fan cooling.

15
PIX CVX Vacuum Contactor-Fuse-
Metal-clad Switchgear up to 24kV
combination Unit

CVX series of vacuum contactors with embedded poles are applicable in AC power distribution system, and are
especially suitable for frequent operation. They are products persistently developed and improved to meet the
demand of different schemes of medium voltage air insulated switchgear.

Basic Characteristics
CVX series of vacuum contactors with embedded poles are a new generation of products
researched and developed based on global manufacturing and design experience of Schneider
Electric, adopt new embedded poles technology, modular design, aiming at the Chinese market,
and are suitable for 650mm and 325mm wide PIX and KYN28 air insulated switchgear.
CVX series of vacuum contactors with embedded poles are used for multiple opening and closing
operations, and can meet the frequent operation demand of users.
Adopting high-efficient and reliable power supply and control to protect electronic module, CVX
series of vacuum contactors with embedded poles have the functions of wide voltage power
supply, closing drive, time-delay automatic current reducing keeping and so on. Standardized
connection interfaces can match with microcomputer control system.
CVX vacuum contactors (matching with
cubicle width of 650mm)

Applications
CVX series of vacuum contactors with embedded poles can be widely used in metallurgy, mining,
petrochemical, drilling platforms and factories and mines power distribution and other fields, and
can cooperate with and protect motors, transformers and capacitor banks, etc. with appropriate
fuse.
CVX series of vacuum contactors with embedded poles can bring valuable solutions to your
projects.

Standards
CVX series of vacuum contactor combinations with
embedded poles conform to the following standards:
v GB14808
v GB11022 CVX vacuum contactors (matching with
v IEC60470 cubicle width of 325mm)

v IEC62271-1

Environment and operating conditions


Normal operating condition range of CVX series of vacuum contactors with embedded poles is
in accordance with GB/T 11022; if there are requirements exceeding the normal use condition
range, please contact the manufacturer.

16
PIX CVX Vacuum Contactor-Fuse-
Metal-clad Switchgear up to 24kV
combination Unit

Model Selection Table


Serial No Name Unit CVX-7 CVX-12

1 Rated voltage 7.2 12

Lightning impulse phase-to-phase, opposite 60 75


withstand voltage (peak) Isolating break kV 60 75
2 Rated insulation level
Power frequency phase-to-phase, opposite 32 42
withstand voltage (1min) Isolating break 32 42
3 Rated frequency Hz 50
4 Rated operational current 250* 160*
5 Maximum rated breaking current A 3200
6 Rated making current 4000
7 Rated short time withstand current 4s A 4000
8 SCPD maximum short-circuit breaking current 50
kA
9 SCPD maximum short-circuit making current (peak) 130
10 Breaking operation frequency (rated breaking current) -
Times
11 Making operation frequency (rated making current) -
12 Utilization category / AC-4
13 Operation frequency Times/h 300
14 Electrical life 250000
Electric self-hold Times 1000000
15 Electrical life
Mechanical self-hold 300000
16 Closing time 100 ~ 250
Electric self-hold ms 80~200
17 Opening time
Mechanical self-hold 30~100
18 Main circuit resistance μΩ y350 y200
Closing / 110, 220 VAC/DC
19 Operating voltage Electricity retention / 110, 220 VAC/DC
Opening / 110VAC/DC 220VAC/DC

* Depending on the fuse capacity.

Product Configuration

Electric retention Mechanical retention

Control module circuit board


Control module circuit board Mechanical retention device+Manual opening device
Opening coil
Closing coil
Auxiliary switch (6 normally opened, 6
normally closed)
Closing and opening position indicator
Standard elements
Operation counter
Fuse status position indicator
Chassis truck
Only applicable to the Locking mechanism for preventing
truck type maloperation of truck
Chassis truck operation/Isolated location's
auxiliary switches S8, S9

Optional elements Opening time delay 100ms -

Only applicable to the Electric chassis truck


truck type Closing interlocking

17
PIX ESW Earthing Switch
Metal-clad Switchgear up to 24kV

ESW Earthing Switch

Item Unit Value

Rated voltage kV 12 24

Rated frequency Hz 50

Rated power frequency withstand voltage


kV 42 50/65*
(1 min)

Rated lightning impulse withstand voltage kV 75 125

Rated short-time withstand current (4s) kA 31.5/50 40

Rated short circuit making current kA 80/125 100

Phase-to-phase distance mm 150/210/275 210/275

* The value 50 kV is based on the standard IEC 62271-100: 2001.

v The earthing switch adopts a fast


closing mechanism, and it can be closed
in case of a short circuit. The closing
and opening states of the switch are
available at the observation window

v The earthing switch features compact


structure, small size, etc. as a whole

v All cooper parts of the earthing


switch are made of low-resistance
materials, which guarantee the reliable
performance of the switch
ESW earthing switch

18
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Scheme number 001 002 003 004 005

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 2 2 2 2 2
Voltage transformer 2 2 3 3
Main elements

High-voltage fuse 3 3 3 3
Earthing switch (optional) 1 1 1 1 1
Lightning arrester
3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF IF
Remarks

Scheme number 006 007 008 009 010

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 3 3 3 3 3
Voltage transformer 2 2 3 3
Main elements

High-voltage fuse 3 3 3 3
Earthing switch (optional) 1 1 1 1 1
Lightning arrester 3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF IF
Remarks

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

19
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Scheme number 011 012 013 014 015

Single Line Diagrams

Rated current (A) 630~2000 630~2000 630~2000 630~2000 630~2000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 2 2 2 2 2
Voltage transformer 2 2 3 3
Main elements

High-voltage fuse 3 3 3 3
Earthing switch (optional) 1 1 1 1 1
Lightning arrester
3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF IF
Remarks

Scheme number 016 017 018 019 020

Single Line Diagrams

Rated current (A) 630~2000 630~2000 630~2000 630~2000 630~2000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 3 3 3 3 3
Voltage transformer 2 2 3 3
Main elements

High-voltage fuse 3 3 3 3
Earthing switch (optional) 1 1 1 1 1
Lightning arrester
3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF IF
Remarks

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

20
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Scheme number 021 022 023 024 025

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 2 2 2 2 2
Voltage transformer 2 2 3 3
Main elements

High-voltage fuse 3 3 3 3
Earthing switch (optional) 1 1 1 1 1
Lightning arrester
3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF IF
Remarks

Scheme number 026 027 028 029 030

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 3 3 3 3 3
Voltage transformer 2 2 3 3
Main elements

High-voltage fuse 3 3 3 3
Earthing switch (optional) 1 1 1 1 1
Lightning arrester 3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF IF
Remarks

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

21
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Scheme number 031 032 033 034 035

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 2 2 2 2 2
Voltage transformer 2 2 3
Main elements

High-voltage fuse 3 3 3
Earthing switch (optional) 1
Lightning arrester
3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose BT BT BT BT BT
Remarks

Scheme number 036 037 038 039 040

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 2 3 3 3 3
Voltage transformer 3 2 2
Main elements

High-voltage fuse 3 3 3
Earthing switch (optional) 1
Lightning arrester
3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose BT BT BT BT BT
Remarks

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

22
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Scheme number 041 042 043 044 045

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 3 3 2 2 2
Voltage transformer 3 3 2
Main elements

High-voltage fuse 3 3 3
Earthing switch (optional) 1
Lightning arrester
3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose BT BT IF IF IF
Remarks

Scheme number 046 047 048 049 050

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 2 2 2 3 3
Voltage transformer 2 3 3
Main elements

High-voltage fuse 3 3 3
Earthing switch (optional) 1
Lightning arrester
3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF IF
Remarks

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

23
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Scheme number 051 052 053 054 055

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~1250


Vacuum circuit breaker 1 1 1 1
Current transformer 3 3 3 3 2
Voltage transformer 2 2 3 3 2
Main elements

High-voltage fuse 3 3 3 3 3
Earthing switch (optional)
Lightning arrester
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF M
Remarks

Scheme number 056 057 058 059 060

Single Line Diagrams

Rated current (A) 630~1250 630~1250 630~1250 630~1250 630~1250


Vacuum circuit breaker
Current transformer 3 2 3 3 2
Voltage transformer 2 2 2 3 2
Main elements

High-voltage fuse 3 3 3 3 3
Earthing switch (optional)
Lightning arrester
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose M RM RM RM M
Remarks

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

24
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Scheme number 061 062 063 064 065

Single Line Diagrams

Rated current (A) 630~1250 630~1250 630~1250 630~1250


Vacuum circuit breaker
Current transformer 2 2 3 3
Voltage transformer 2 2 2 3 2
Main elements

High-voltage fuse 3 3 3 3 3
Earthing switch (optional)
Lightning arrester
3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose M RM RM RM PS
Remarks

Scheme number 066 067 068 069 070

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~1250


Vacuum circuit breaker
Current transformer
Voltage transformer 3 3 2 3 2
Main elements

High-voltage fuse 3 3 3 3 3
Earthing switch (optional)
Lightning arrester
3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose PS PS RP RP RP
Remarks Cubicle width: 650,800,1000

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

25
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Scheme number 071 072 073 074 075

Single Line Diagrams

Rated current (A) 630~1250 630~1250 630~1250 630~4000 630~1250


Vacuum circuit breaker
Current transformer
Voltage transformer 3 2 3 3 2
Main elements

High-voltage fuse 3 3 3 3 3
Earthing switch (optional)
Lightning arrester
3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose RP IFDM IFDM RM IFDM
Remarks Cubicle width: 650,800,1000

Scheme number 076 077 078 079 080

Single Line Diagrams

Rated current (A) 630~1250 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker
Current transformer
Voltage transformer 3
Main elements

High-voltage fuse 3
Earthing switch (optional)
Lightning arrester
3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IFDM IFD R IFD IFD
Remarks

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

26
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Scheme number 081 082 083

Single Line Diagrams

Rated current (A) 630~2000 630~4000 630~4000


Vacuum circuit breaker
Current transformer
Voltage transformer
Main elements

High-voltage fuse
Earthing switch (optional)
Lightning arrester
3 3
(optional)
As needed by the As needed by the As needed by the
Potential indicator
customer customer customer
Purpose IFD IFD R
Remarks

Scheme number 084 085 086 087 088

Single Line Diagrams

Rated current (A) 400~630 400~630 400~630 400~630 400~630


Vacuum circuit breaker 1 1 1 1
Current transformer
Voltage transformer Transformer: 30-100kVA Transformer: 30-100kVA Transformer: 30-100kVA
Main elements

High-voltage fuse
Earthing switch (optional) 1
Lightning arrester
3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose DF DF T T T
Remarks Cubicle width: 650,800,1000 Cubicle width: 650,800,1000 WxD: 1000x1600 WxD: 1000x1600 WxD: 1000x1600

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

27
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Scheme on connection of PIX-12 kV switchgear to Scheme on connection of PIX-12 kV switchgear to


vacuum contactor (PIX-M) generator circuit breaker (PIX-Gen)
Scheme number 089 090 Scheme number 091 092

Single Line Diagrams Single Line Diagrams

Rated current (A) 400 400 Rated current (A) 5000~6300 5000~6300
Vacuum circuit Vacuum circuit
1 1 1 1
breaker breaker
Current transformer 2 3 Current transformer 2 3
Voltage transformer Voltage transformer
Main elements

Main elements

High-voltage fuse High-voltage fuse


Earthing switch Earthing switch
1 1
(optional) (optional)
Lightning arrester Lightning arrester
3 3
(optional) (optional)
As needed by the As needed by the As needed by the As needed by the
Potential indicator Potential indicator
customer customer customer customer
Purpose F F Purpose I I
Remarks Cubicle width: 325,650 Cubicle width: 325,650 Remarks WxD: 1200x1960 WxD: 1200x1960

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

28
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-12 kV Switchgear

Application example

Incoming Metering PT lifting Feeder Feeder


cubicle cubicle cubicle cubicle cubicle
User distribution scheme

It is generally used on the user side, located in the downstream area of substations, and applicable to factories, residential quarters, etc.
Successful cases: Xiamen Tianma Micro-electronics Project, Shenyang New World International Convention & Exhibition Center Project,
Beijing Benz Project, etc.

Incoming PT Feeder Bus coupler Bus coupler Feeder PT Feeder


cubicle cubicle cubicle cubicle isolation cubicle cubicle cubicle cubicle
Substation scheme

It is applicable to primary power distribution of power grids of the State Grid and China Southern Power Grid, or used by power plants and
large industrial and mining enterprises.
Successful cases: Shandong Zouping 110 kV Chengnan Substation Project, Fujian Shenyuan Advanced Materials Project, China Unicom
Project, Zhuhai Power Plant Project, etc.

Incoming Feeder Feeder PT FC feeder FC feeder FC feeder FC feeder


cubicle cubicle cubicle cubicle cubicle cubicle cubicle cubicle
Nuclear power station scheme

The scheme is highly targeted, applicable to the single unit capacity of millions of kW. The requirements on safe application of the products
are high.
Successful case: Medium-voltage Project of No. 5 & No. 6 Units in Hongyanhe Nuclear Power Plant.

29
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-24 kV Switchgear

Scheme number 001 002 003 004 005

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 2 2 2 3 3
Voltage transformer 2 3 2
Main elements

High-voltage fuse 3 3 3
Earthing switch (optional) 1 1 1
Lightning arrester
3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF IF
Remarks

Scheme number 006 007 008 009 010

Single Line Diagrams

Rated current (A) 630~4000 630~2000 630~2000 630~2000 630~2000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 3 2 2 2 3
Voltage transformer 3 2 3
Main elements

High-voltage fuse 3 3 3
Earthing switch (optional) 1 1
Lightning arrester
3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF IF
Remarks

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

30
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-24 kV Switchgear

Scheme number 011 012 013 014 015

Single Line Diagrams

Rated current (A) 630~2000 630~2000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 3 3 2 2 3
Voltage transformer 2 3 2 3
Main elements

High-voltage fuse 3 3 3 3
Earthing switch (optional) 1
Lightning arrester
3 3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF IF IF
Remarks

Scheme number 016 017 018 019 020

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~4000 630~4000 630~4000


Vacuum circuit breaker 1 1 1 1 1
Current transformer 3 3 3 2 3
Voltage transformer 2 3
Main elements

High-voltage fuse 3 3
Earthing switch (optional) 1
Lightning arrester
3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF IF BT BT
Remarks

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

31
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-24 kV Switchgear

Scheme number 021 022 023 024 025

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~1250 630~1250 630~1250


Vacuum circuit breaker 1 1
Current transformer 2 3 2 2 2
Voltage transformer 2 3 2
Main elements

High-voltage fuse 3 3 3
Earthing switch (optional)
Lightning arrester
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IF IF RM RM RM
Remarks Cubicle width: 1000 Cubicle width: 800,1000 Cubicle width: 1000

Scheme number 026 027 028 029 030

Single Line Diagrams

Rated current (A) 630~1250 630~1250 630~1250 630~1250 630~1250


Vacuum circuit breaker
Current transformer 2 3 3 3 3
Voltage transformer 3 2 3 2 2
Main elements

High-voltage fuse 3 3 3 3 3
Earthing switch (optional)
Lightning arrester
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose RM RM RM RM RM
Remarks Cubicle width: 800,1000 Cubicle width: 1000 Cubicle width: 800,1000 Cubicle width: 1000 Cubicle width: 800,1000

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

32
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-24 kV Switchgear

Scheme number 031 032 033 034 035

Single Line Diagrams

Rated current (A) 630~4000 630~4000


Vacuum circuit breaker
Current transformer
Voltage transformer 2 3 3 2 3
Main elements

High-voltage fuse 3 3 3 3 3
Earthing switch (optional)
Lightning arrester
3 3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose PS PS P RP RP
Remarks Cubicle width: 1000 Cubicle width: 800,1000 Cubicle width: 800,1000 Cubicle width: 1000 Cubicle width: 800,1000

Scheme number 036 037 038 039 040

Single Line Diagrams

Rated current (A) 630~1250 630~1250 630~4000 630~4000


Vacuum circuit breaker 1 1
Current transformer
Voltage transformer 3 2 3
Main elements

High-voltage fuse 3 3 3
Earthing switch (optional)
Lightning arrester
3 3 3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose M IFDM IFDM IFD R
Remarks Cubicle width: 800,1000 Cubicle width: 1000 Cubicle width: 800,1000

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

33
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-24 kV Switchgear

Scheme number 041 042 043 044 045

Single Line Diagrams

Rated current (A) 630~4000 630~4000 630~2000 630~4000 630~4000


Vacuum circuit breaker 1 1 1
Current transformer
Voltage transformer
Main elements

High-voltage fuse
Earthing switch (optional)
Lightning arrester
3
(optional)
As needed by the As needed by the As needed by the As needed by the As needed by the
Potential indicator
customer customer customer customer customer
Purpose IFD IFD IFD R IFD
Remarks

Scheme number 046 047 048

Single Line Diagrams

Rated current (A) 400~630 400~630 400~630


Vacuum circuit breaker 1 1
Current transformer
Voltage transformer Transformer: 30kVA Transformer: 30kVA
Main elements

High-voltage fuse
Earthing switch (optional) 1
Lightning arrester
3
(optional)
As needed by the As needed by the As needed by the
Potential indicator
customer customer customer
Purpose DF T T
Remarks Cubicle width: 1000 WxD: 1000x2600 WxD: 1000x2600

Function codes in the primary connection scheme are as follows:


I-incoming cubicle F-Feeder cubicle D-Isolation cubicle B-Busbar sectioning cubicle R-Busbar lifting cubicle M-Dedicated metering cubicle P-Voltage measurement
cubicle T-Substation transformer cubicle S-Lightning arrester cubicl.

34
PIX Primary Schematic Diagram of
Metal-clad Switchgear up to 24kV
PIX-24 kV Switchgear

Application example

Incoming Metering PT lifting Feeder Feeder


cubicle cubicle cubicle cubicle cubicle
User distribution scheme

It is generally used on the user side, located in the downstream area of substations, and applicable to factories, residential quarters, etc.
Successful cases: Wharf (Wuxi) Real Estate Co, Ltd. (International Financial Center) Project, Foshan New City Poly Business Center
Project, etc.

Incoming PT Feeder Bus coupler Bus coupler Feeder PT Feeder


cubicle cubicle cubicle cubicle isolation cubicle cubicle cubicle cubicle
Substation scheme

It is applicable to primary power distribution of power grids of the State Grid and China Southern Power Grid, or used by power plants and
large industrial and mining enterprises.
Successful cases: Chongqing BOE 220 KV Transmission and Distribution Project, Zhuhai Hengqin Island Project, etc.

35
PIX Ordering Instructions
Metal-clad Switchgear up to 24kV

Ordering Instructions
b The following technical materials should be supplied upon ordering PIX switchgear:
v Primary connection scheme number, purpose and single wire system diagram, rated voltage, rated current,
rated short circuit breaking current, plan layout of distribution room, switchgear lineup drawing, etc.
v Specifications of incoming/outgoing cables
v Requirements on switchgear control, metering and protection functions, and requirements for other locking and Circuit breaker truck
racking-in crank
automatic devices
v Model, specification and quantity of main electrical elements of the switchgear (When bus ducts are needed
between cubicles or by the incoming cubicle, the rated current-carrying capacity, span and height from the
ground of the bus ducts shall be provided.)
v Other special requirements (when the switchgear is used in special circumstances)

Operating handle of
Accompanying documents, accessories and spare parts earthing switch

The accompanying documents generally include the following:


a. Certificate of conformity and delivery inspection report
b. Operating instructions
c. Secondary connection diagram and switchgear lineup drawing Manual charging lever of
d. Packing list circuit breaker

Accessories
v Circuit breaker truck racking-in crank
v Manual charging lever of circuit breaker
v Operating handle of earthing switch

Transfer truck
Spare parts
The cost of the transfer truck is different from that of the lifting truck, and both of them should be ordered from the
manufacturer.
Other spare parts should be directly ordered by the customer according to the order contract.

Special precautions
In many areas in China, the humidity is high, and the temperature fast varies in a large range. In such areas,
the switchgear is with the risk of condensation, so the heater should be used 48 hours before the switchgear is
Lifting truck
powered on. During operation, the user should guarantee that the heater works around the clock. However, the
heater may not be used when the load current is higher than 1,250A.
The sample is a composite one. For detailed information, please contact the manufacturer.

36
PIX Layout and Installation
Metal-clad Switchgear up to 24kV

Primary scheme on plan layout of distribution room


According to technical features of PIX switchgear, it is suggested that appropriate space should be reserved
between the back cover plate of the switchgear and the wall, and between both sides of the switchgear and the
wall as maintenance channels.
Figure 1 is a reference scheme of the plan layout of the distribution room. The scheme can be used as reference
for installation by means of cables are led in the distribution room via a cable trench or led in downward or upward
direction. In the figure, the switchgear cubicles are arranged in a single row. If the switchgear cubicles are to be
arranged in two rows opposite to each other, the distance between the two rows shall be larger than or equal to 2,500
mm.

Construction of installation base of switchgear


The construction of the installation base for the switchgear should conform to the regulations in relevant clauses
in the Code of Erection and Acceptance of Electric Power Construction. Whichever incoming/outgoing way is
adopted, pre-processed channel steel is recommended for the installation base of PIX switchgear.

Attached figure 1

1000
Electric cable trench

1400(1860)

PIX Switchgear

Control cable trench

1200 30 n*(325,550,650,800,1000) 30 1200


2500

Typical plane layout of PIX indoor AIS metal-clad switchgear

37
PIX Layout and Installation
Metal-clad Switchgear up to 24kV

During civil design, the reserved height for the base frame should be taken into consideration for the foundation
elevation of the switchgear (see attached figures 2-3), and margin should be remained. In addition, anchored steel
plates should be embedded along the longitudinal direction of the frame on the switchgear foundation, with an
interval of 1-1.5m.
The base frame is welded by channel steel. The requirements on basic dimensions of the frame and the layout of
the cable trench are shown in attached figures 4-5. There are no strict requirements on the height of the channel
steel. The extended distance of the channel steel on the base frame should be consistent with the dimension of
the switchgear frame. The total length of the frame should be determined based on the layout of the switchgear
cubicles and the number of switchgear cubicles in each row.
During embedding of the base frame, horizontal alignment should be conducted. The horizontal error and flatness
error should not exceed 1 mm per m and the total error should not exceed 2 mm. In addition, the top surface of the
base frame should be approximately 3-5 mm higher than the final floor of the distribution room.

Attached figure 2

1000 1400
2250

30 1340 30

The top surface of the base


frame is about 3-5 mm
higher than the floor
Base frame
240 170 280
±0.0m
0. 0m

380 -0.25m

Cover plate of control


cable trench
δ=5mm corrugated
steel plate

Control cable trench


250*250

800 350 650

Power cable trench


800*1000

Typical plan layout of PIX-12kV distribution room (A-A section view of attached figure 1)

38
PIX Layout and Installation
Metal-clad Switchgear up to 24kV

Attached figure 3

1000 1860

2400
30 1800 30

The top surface of the base


frame is about 3-5 mm
higher than the floor
Base frame
240 630 280
±0.0m

380 -0.25m
Cover plate of control
cable trench
δ=5mm corrugated steel
plate

Control cable trench


250*250

800 350 650


Power cable trench
800*1000

Typical plan layout of PIX-24kV distribution room (A-A section view of attached figure 1)

Installation of switchgear
PIX switchgear should be installed in the distribution room which is dry, clean, and ventilated. Prior to installation,
the base frame and floor should have been completed and passed the acceptance inspection, and the window
and door decoration and indoor lighting and ventilation works should have been basically completed. See the
Installation Manual for specific installation methods.

Attached figure 4

Power cable trench


800
110

230 300 350 440 640


30

37
50
240

165 360 400 550 750


12

35
M

5# channel
steel
650
1400

1340

1340

Primary control
cable hole

70 70 70 70 70
Base
210

Secondary frame
70

control 37
50

35
30

100
250

Control cable trench

325 550 650 800 1000

Typical layout of cable trenches of PIX-12kV and PIX-M distribution rooms

39
PIX Layout and Installation
Metal-clad Switchgear up to 24kV

Attached figure 5

800
Power cable trench

110
440 640
30

48

100
250

50
12
M

10# channel
steel
450

Primary control Primary control


cable hole cable hole

580 780
1860

Secondary control
150 cable hole
120 150

Base frame 48

100

50
30

100
250
Control cable trench

800 1000

Typical layout of cable trench of PIX-24 kV distribution room

Attached figure 6

700 250
37
35

5# channel steel
25

50

4-M12

5# channel steel
1960

1900

220 (760) 220


5# channel steel

5# channel steel

1145

80

Secondary control
210

cable hole
50
35
70

5# channel steel
37
35

700 250
1200

50 50

Manufacturing diagram of PIX-Gen base frame

40
Schneider Electric (China) SA

Schneider Electric(China) SA Schneider Electric Office Building, No. 6 Wangjing East Road, Chaoyang District, Beijing, Zip Code:100102 Tel: (010) 84346699 Fax:(010) 65037402
b Beijing SBMLV No.2, Liangshuihe No.2 Street, ETDZ, Beijing Zip Code:100176 Tel: (010) 65039999/9001 Fax:(010) 65039639/9295
b Shanghai Branch 6 -13/F, Changfeng International Office Building, No. 89 Yunling East Road, Putuo District, Zip Code:200062 Tel: (021) 60656699 Fax:(021) 60656688
Shanghai
b Zhangjiang Office Building No.9, No. 3000, Longdong Avenue, Pudong New Area, Shanghai Zip Code:201203 Tel: (021) 61598888
b Guangzhou Branch 25/F, Development Center, No. 3 Linjiang Avenue, Zhujiang New Town, Guangzhou, Guangdong Zip Code:510623 Tel: (020) 85185188 Fax:(020) 85185190
Province
b Wuhan Branch Building B11, No.77 Guanggu Avenue, East Lake New High-tech Area, Wuhan, Hubei Province Zip Code:430205 Tel: (027) 59373000 Fax:(027) 59373001
b Tianjin Office 5/F, Building No.2, Schneider Electric Industrial Park, No. 11 Haitaichuangxin No.6 Road, Huayuan Zip Code:300392 Tel: (022) 23748000 Fax:(022) 23748100
Industrial Zone(Outer Ring), Binghai New High-tech Area, Tianjing
b Tangshan Office Rm 207, High-tech HQ Building, No. 101 Jianshe North Road, New High-tech Development Zone, Zip Code:063000 Tel: (0315) 6710148 Fax:(0315) 6710146
Tangshan, Hebei Province
b Hohhot Office Rm, 6027, 6/F, Building C, Taiweifangheng Global Plaza, No. 85, Xinhua East Street, Xincheng Zip Code:010010 Tel: (0471) 6537509 Fax:(0471) 6537529
District, Hohhot, Inner Mongolia
b Jinan Office 31/F, QiLu Bank Building, No. 176, Shunhe Street, Jinan, Shandong Province Zip Code:250001 Tel: (0531) 8167 8100 Fax:(0531) 86121628
b Qingdao Office Rm 413/4, 4/F, No.2 Building, Qingdao International Exhibition Wealth Center, No. 18, Qingling Zip Code:266061 Tel: (0532) 85793001 Fax:(0532) 85793002
Road, Laoshan District, Qingdao, Shandong Province,
b Shijiazhuang Office Rm 1201, 12/F, World Trade Plaza Hotel Office building, No. 303 Zhongshan East Road, Zip Code:050011 Tel:(0311) 86698713 Fax:(0311) 86698723
Shijiazhuang, Hebei Province
b Shenyang Office Rm F9-412, No. 860-6 Shangshengou Village, Dongling District, Shenyang, Liaoning Province Zip Code:110016 Tel:(024) 23964339 Fax:(024) 23964296
b Harbin Office 21/F, Building J, Always Outlets, No. 15 Hongjun Street, Nangang District, Harbin, Heilongjiang Zip Code:150001 Tel:(0451) 53009797 Fax:(0451) 53009640
Province
b Changchun Office Rm1211-12 , China Everbright Bank Changchun Branch Building, No.2677Jiefang Avenue, Zip Code:130061 Tel:(0431) 88400302/03 Fax:(0431) 88400301
Changchun, Jilin Province
b Dalian Office Rm 201-I, Building No.17, No.267 Wuyi Road, Shahekou District, Dalian, Liaoning Province Zip Code:116023 Tel:(0411) 84769100 Fax:(0411) 84769511
b Xi'an Office 1-4/F , Building C, GLP-I Park, No. 211 Tiangu No.8 Road, New High-tech Area, Xi'an, Shaanxi Zip Code:710077 Tel:(029) 65692599 Fax:(029) 65692566
Province
b Taiyuan Office Rm 805, Zone B, Lihong Building, No. 268 Fuxi Road, Taiyuan, Shanxi Province Zip Code:030002 Tel:(0351) 4937186 Fax:(0351) 4937029
b Urumqi Office No. TUVW , 21st/F, Guanghuizhongtian Plaza, No.165 Xinhua North Road, Urumqi, Xinjiang Uygur Zip Code:830001 Tel:(0991) 6766838 Fax:(0991) 6766830
Autonomous Region
b Nanjing Office Rm Zip 2001-2005 , Huijie Plaza, No. 268 Zhongshan Road, Nanjing, Jiangsu Province Zip Code:210008 Tel:(025) 83198399 Fax:(025) 83198321
b Suzhou Office No. 118 Dongshenhu Road, Industrial Park, Suzhou, Jiangsu Province Zip Code:215123 Tel:(0512) 68622550 Fax:(0512) 68622620
b Wuxi Office No. 20 Hanjiang Road, New High-tech Development Zone, Wuxi, Jiangsu Province Zip Code:214028 Tel:(0510) 81009780 Fax:(0510) 81009760
b Nantong Office Rm 1103, Building A, Huachen Complex, No.111, Gongnong Road, Nantong, Jiangsu Province Zip Code:226000 Tel:(0513) 85228138 Fax:(0513) 85228134
b Changzhou Office Rm 5-1801, Changfa Mall building, No. 101-1, Taihe East Road, Xinbei District, Changzhou, Zip Code:213022 Tel:(0519) 85516601 Fax:(0519) 88130711
Jiangsu Province
b Hefei Office 6/F, Hilton Hotel, No. 198 Shengli Road, Hefei, Anhui Province Zip Code:230011 Tel:(0551) 64291993 Fax:(0551) 64279010
b Hangzhou Office 10th/F, Hengxin Building, No.588 Jiangnan Avenue, Binjiang District, Hangzhou, Zhejiang Province, Zip Code:310053 Tel:(0571) 89825800 Fax:(0571) 89825801
b Nanchang Office Rm 1001-1002, Zhonghang Plaza, No. 1 Ganjiang North Road, Honggutan New Area, Nanchang, Zip Code:330008 Tel:(0791) 82075750 Fax:(0791) 82075751
Jiangxi Province
b Fuzhou Office Rm 11, 13th/F, Building A2, Cangshan Wanda Plaza, No.272, Pushang Avenue, Cangshan District, Zip Code:350001 Tel:(0591) 38729998 Fax:(0591) 38729990
Fuzhou, Fujian Province
b Luoyang Office Rm 609, Huayang Plaza Hotel, No.88 Kaixuan West Road, Jianxi District, Luoyang , Henan Zip Code:471003 Tel:(0379) 65588678 Fax:(0379) 65588679
Province
b Xiamen Office No.455, Malong Road, Huoju New High-tech Industrial Development Area, Xiamen, Fujian Province Zip Code:361006 Tel:(0592) 2386700 Fax:(0592) 2386701
b Ningbo Office Rm 833 , Citic Ningbo International Hotel, No. 1 Jiangdong North Road, Ningbo, Zhejiang Province Zip Code:315040 Tel:(0574) 87706806 Fax:(0574) 87717043
b Wenzhou Office RM 902-2, 9/F, New Century Office Building, No. 198, Shangjiang Road, Longwan District, Zip Code:325000 Tel:(0577) 86072225 Fax:(0577) 86072228
Wenzhou, Zhejiang Province
b Chengdu Office 5/F, Building No.7, Zone D, Tianfu Software Park, No.599 Century Town South Road, New High- Zip Code:610041 Tel:(028) 66853777 Fax:(028) 66853778
tech Industrial Development Area, Chengdu, Sichuang Province
b Chongqing Office Suite. 5, 6, 7, 10/F, Office Building No.4, Corporate Avenue, No.56, Ruitian Road, Yuzhong District, Zip Code:400043 Tel:(023) 63839700 Fax:(023) 63839707
Chongqing
b Foshan Office Rm 2622-2623 , 26th/F, Baihua Plaza, No.33 Zumiao Road, Foshan, Guangdong Province Zip Code:528000 Tel:(0757) 83990312/0029 Fax:(0757) 83992619
b Kunming Office Suite 07-08 , 10/F, Building A, Brilliant Plaza, No. 6 Sanshi Street, Kunming, Yunnan Province Zip Code:650021 Tel:(0871) 63647550 Fax:(0871) 63647552
b Changsha Office No. 24, 10/F, Zone B, Huachen Century Plaza, No. 8, 2nd section Middle Wanjiali Road, Yuhua Zip Code:410007 Tel:(0731) 88968983 Fax:(0731) 88968986
District , Changsha ,Hunan
b Zhengzhou Office 2/F, West Wing of Building C, Zhongzhou Crowne Plaza Hotel, No.115, Jinshui Road, Zhengzhou, Zip Code:450003 Tel:(0371) 6593 9211 Fax:(0371) 6593 9213
Henan Province
b Zhongshan Office Rm 1103, Building No.3, Central Plaza, No.1 Xingzheng Road, East District, Zhongshan, Zip Code:528403 Tel:(0760) 88235979 Fax:(0760) 88235979
Guangdong Province
b Lanzhou Office Rm 2310-2311, Guofang Office Building, No. 4-6, South Square Road, Chengguan District, Zip Code:730030 Tel:(0931) 8795058 Fax:(0931) 8795055
Lanzhou, Gansu Province
b Yantai Office Rm1806, Kunlun Yantai Hotel, No.218 Changjiang Road, Development Area, Yantai, Shandong Zip Code:264006 Tel:(0535) 6381175 Fax:(0535) 6381275
Province
b Yangzhong Office Rm, 666, 4th/F, Dongyuan Hotel, No.1 East Ring Road, Yangzhong, Jiangsu Province Zip Code:212200 Tel:(0511) 88398528 Fax:(0511) 88398538
b Nanning Office 10/F,Trans-Century Hotel, No. 111 Minzu Avenue, Qingxiu District, Nanning, Guangxi Province Zip Code:530000 Tel:(0771) 5519761/62 Fax:(0771) 5519760
b Dongguan Office Rm B417, Hongxi Center, No.2 Tiyu Road, Nancheng District, Dongguan, Guangdong Province Zip Code:523009 Tel:(0769) 22413010 Fax:(0769) 22413160
b Shenzhen Office 20/F, CADRE Group Centre, No.168, Tongsha Road, Xili Town, Nanshan District, Shenzhen, Zip Code:518000 Tel:(0755) 36677988 Fax:(0755) 3667 7982
Guangdong Province
b Guiyang Office Suite 1204, 12/F, Guihang Building, No. 49 South Zhonghua Road, Guiyang, Guizhou Province Zip Code:550002 Tel:(0851) 5887006 Fax:(0851) 5887009
b Haikou Office Rm 607, 6/F, Hainan Weihua Haiyi Hotel, No.18 Wenhua Road, Haikou, Hannan Province Zip Code:570105 Tel:(0898) 68597287 Fax:(0898) 68597295
b Schneider Electric East Wing, 13/F, Warwick, Taikoo Place, No.979 King's Road,Quarry Bay, Hongkong, Tel:(00852) 25650621 Fax:(00852) 28111029
(Hongkong ) SA
b China Study & Schneider Electric Office Building, No.6 Wangjing East Road, Chaoyang District, Beijing Zip Code:100102 Tel:(010) 84346699 Fax:(010) 84501130
Development School of
Schneider Electric Energy
University

41
Schneider Electric Industries SAS - All rights reserved

Customer Care Center Hotline: 400 810 1315


Schneider Electric (China) Co.,Ltd. Schneider Electric Building, No. 6, As standards, specifications and designs change from time to time, please
East WangJing Rd., Chaoyang District ask for confirmation of the information given in this publication.
www.schneider-electric.cn
Beijing 100102 P.R.C.
Tel: (010) 8434 6699
Printed on ecological paper
Fax: (010) 8450 1130

SE-AVX-012-08-2015.11