4 Preface 26 Selecting the right window actuators
27 How do actuators differ?
5 Introduction 27 What is an actuator and what is its purpose?
5 Why consider natural ventilation? 28 Wiring routes and concealment
29 Multi speed operation
6 Natural ventilation 29 Pressure safety function
6 So, what is natural ventilation? 29 Actuator position feedback
7 Indoor air quality indicators 29 Synchronised actuators
30 Opening areas
8 Natural ventilation advantages 31 Window orientation
8 The advantages in a nutshell 31 Compiling a specification to avoid common
10 Productivity and Health benefits complaints
13 Productivity and Health benefits – the practical
implications 32 Green certifications
14 Economic impact of natural- and hybrid
ventilation 33 Project examples
16 Improved use of space
17 What kind of buildings can benefit from using 51 Get in touch
natural ventilation?
51 References
18 Natural ventilation principles
19 Single-sided ventilation
19 Cross ventilation
19 Stack ventilation
2 3
← Back to index
Preface
Natural ventilation has always been at the heart of around energy, CO2 emissions and the efficient use of
WindowMaster. By making buildings breath and resources. These are all crucial for our life on this planet;
bringing fresh air into schools, workplaces and other yet they only compose three factors on the whole
buildings, WindowMaster has helped to focus attention spectrum of issues facing us in our pursuance for living
on what really matters: A sustainable and healthy good, viable lives.
climate – inside as well as outside.
A comfortable indoor climate with the optimum amount
By implementing natural ventilation to almost all types of fresh air is equally important for our health and
of buildings, we have created spaces of high quality well-being. And with our health and well-being making
and increased the well-being of occupants all whilst up essential parameters to the overall quality of our
increasing the room for design and actual usage by lives, it is of utmost importance that we make indoor
reducing the area needed for mechanical installations. environment part of the public discussion and raise it to
Today, we experience that WindowMaster’s products the same level as the questions pertaining to the human
and solutions are more pertinent to the market than impact on outdoor environment and sustainability.
ever before. Together with aesthetically designed
rooms, health and well-being constitute one of the With natural ventilation, indoor and outdoor
most important agendas of the future together with an environmental issues can be addressed concomitantly
increased focus on energy savings. while putting full focus on the architectural design of a
building.
In recent years, the public discourse on sustainable
architecture, and sustainability in general, has revolved
Introduction
Why consider natural ventilation?
Imagine you could reduce a building’s area used for With this e-book, we aim to share our knowledge
ventilation by 90%[1], what would be the impact on your on sustainable ventilation architecture by offering
design and final performance of that building? specific advice and documentation on the effects and
advantages of WindowMaster products. You will learn
This eBook has been written to address some of the how natural ventilation can be used to create beautiful,
issues and opportunities that Architects worldwide healthy buildings that are good for both the indoor
face when designing buildings that needs to be and outdoor climate. You will discover ways in which
ventilated and meet sustainable requirements. Chunky natural ventilation can be applied to new as well as old
ventilations taking up space that could have been used buildings, to make them more sustainable. And you will
for more aesthetically designed rooms, unnecessary learn how to use the principles of natural ventilation
energy consumption as a result of ventilation systems, architecture to make complete use of your space,
high maintenance costs and noisy mechanical fans. If reduce construction costs and increase your green
these issues sound familiar, this e-book is for you. energy rating.
WindowMaster project: Gentofte Hospital
Photo: Jesper Ludvigsen
4 5
← Back to index
6 7
230 / CNBOP-
120V CO2 230V WFI ETL
EN 12101
O2 $
400V PIB NV Embedded® NV Embedded®
3 in 1
ENTrueSpeed™
EN
EN
EN
MotorLink
®
← 12101-2 12101-10
compatible
Natural
ISO 21927-9 EN 12101 B300
As already stated in the beginning of this e-book, 2 Green profile Lower costs
MAX MAX MAX MAX MAX MAX natural ventilation comesBMS Bluetooth
with many advantages
BMS Globally, commercial buildings account for The need for fewer and less expensive
EN B 24V 230V 4 5
8
4.8A 8A 16A 48A 60A 64A ranging 12101
ventilation
from environmental benefits to improved
300 up to 40% of all energy consumption. 5 components and construction work makes
3NF
NV Embedded® NV Embedded® EN EN design and lastly an enhanced indoor air quality that Natural ventilation has a very low energy natural ventilation a cost-effective option
compatible in 1 TrueSpeed™
12101-2
MotorLink
12101-10
®
advantages
battles high levels of CO2, VOCs and humidity. In the consumption, and thus very limited carbon for achieving a better indoor climate.
3
BMS following sections, we will sum up some of the key emissions. Over a building’s life cycle, capital costs,
120V
NF reasons why every architect should not design a 5 120V 6
9
6 operating costs, and maintenance costs
4A
Bluetooth 4.8A 8A 16A 20A 40A 48A 60A 64A
ISO 21927-9 EN 12101 B300
new building or retrofit an old building without first 1 It is possible to achieve a 24-71% are 5 times lower with natural ventilation
NV Embedded® NV Embedded®
compatible 3 in 1 TrueSpeed™ MotorLink
considering implementing natural ventilation.
®
reduction in carbon emissions by using compared to mechanical ventilation and
4 natural ventilation instead of mechanical 2.5 times lower with hybrid/mixed mode
O2 M
M CO2
VdS KNX
$
CO2 BACnet LON120V Modbus 6 ventilation.[5] 230- 7
10 ventilation.[7]
NV Embedded® NV Embedded®
3 in 1 TrueSpeed™
VdS MotorLink®
KNX CO2 BACnet 230-
400V 7
$ GLT LON Modbus
compatible
Bluetooth CTS SD 400V
2 High user satisfaction Our systems pay for themselves within less
BMS With a natural ventilation solution from than a year, resulting in an average ROI of
Bluetooth
EN EN
The advantages in a nutshell 5
1 WindowMaster, it’s easy to divide your at least 120% for natural ventilation and
NX CO2 BACnet LON Modbus EN B 24V 230- 230V 7 8
12101-2 12101-10 EN
12101 B
300 24V400V 230V building into different zones, for instance 8 mixed mode systems, thanks to energy,
12101 300
O2 CO2 $ 3 separate office spaces, in order to address health, and productivity gains.[8]
a range of different needs.
$ 120V
Beautiful architecture 6 Users always have the option to override Minimal maintenance
2
EN B 24V 230V No unsightly pipework or duct penetrations 8 the automatic control, ensuring high user 9 No filter replacement. No dirty ducts to be
1 9
?
12101 4A 300 4.8A 8A 16A 20A 40A 48A 60A 64A
4A 4.8A 8A and no bulky ventilation
16A 20A units. Ceiling
40A 48A 60A satisfaction.64A cleaned.
4
EN EN heights can be increased, as natural
12101-2 12101-10 ventilation does not require suspended In air conditioned buildings, only 50% of Better indoor climate
KNX CO2 BACnet LON Modbus 230- 7
$ 400V
ceilings. More daylight and transparency, 3 occupants are satisfied with the indoor Studies show that people who spend
9 10
8A 16A 20A 40A 48A 2
1 including
60A the
CTSuse of64A
atriums
GLT for naturalSD temperature at one time, whereas in 10 time in buildings equipped with natural
BMS CTS GLT SD
ventilation. 5 naturally ventilated buildings, 77% of ventilation have fewer building-related
occupants are satisfied.[6] symptoms, such as headaches, eye
EN B 24V 230V 1 Lower energy consumption 8 irritation, etc.[9]
0 $ 12101 300 4
3 Natural ventilation consumes less energy 10 Gentle refurbishment
CTS GLT SD 2
than a comparable mechanical ventilation
120V With natural ventilation, it’s possible to They also show productivity gains of
6
$ system. The use of mixed mode ventilation create a good indoor climate in historical 3-18% compared to mechanical ventilation
BMS 2 can potentially reduce energy consumption 9 buildings without the need to break and savings on health costs of 0.8-1.3%.[10]
08A 16A 20A 40A 48A 60Afurther. 64A 5
even through walls and ceilings to make way for Finally, SBS symptoms can be reduced by
4
?
3 ducts and large ventilation units. more than 65% with a natural ventilation
0
NX CO2 BACnet LON Modbus 100% use of space 400V
Natural ventilation enables full utilization of
230-
? 7 Natural ventilation is the obvious choice
when replacing old windows with new
solution.[11]
3 10
CTS GLT SD the building floor plate and floor 120V
to ceiling 6 ones simply by installing actuators to
5
4 height, as there’s no need to devote space control the ventilation process.
EN
12101
B
300
24V 230V? to large air handling units and equipment
rooms.
8
Fast renovations
Read more about designing
4 230- With natural ventilation, the renovations can
KNX CO2 BACnet LON Modbus 7 buildings with natural ventilation
120V A mechanical ventilation system400V
occupies be completed very quickly, thus causing
6
5
up to 6.5% of a building’s floor area minimal disruption to the lives of the
compared to only 0.2% 9
8A 16A 20A 40A 48A 60A 64A for a natural building occupants. Often it is also possible See examples of projects that
5 ventilation system.[4] to avoid having to relocate the occupants have benefitted from natural ventilation
8
?
EN B 24V 230V of a building during the renovation period.
12101 300 230-
s 120V 7
6
400V
10
CTS GLT SD
120V 6
9
8A 16A 20A 40A 48A 60A 64A
Vs 230- 8
7
400V 8 9
s 230- 7
400V 10
← Back to index
KNX EN 12101
KNX
230 / CNBOP-
24V 120V 230V
400V
WFI ETL PIB Outside views
LON VdS NF
NV Embedded® NV Embedded®
TrueSpeed™ BACnet Modbus 3 in 1 TrueSpeed™ MotorLink®
LON VdS NF
NV Embedded®
3 in 1 MotorLink ®
BACnet Modbus
compatible
3 in 1 TrueSpeed™ MotorLink®
It follows that the productivity of staff, or anything Mental Function & Call Processing Hospital Stays
AX
that affects their ability to be productive, should be a
MAX concernMAX MAX MAX
9% Memory 10-25%
better
6-12% faster 8.5% shorter
major MAX An
for any organisation. MAX MAX
improvement MAX MAX MAX MAX
MAX MAXMAX MAX MAXcosts MAX
Rental MAX MAX
Bluetooth
Bluetooth
0A 20A 4x5Aor productivity
4A 4.8A 8A 16A 48A 60A 64A
ISO 21927-9 EN 12101 B300
strong incentives for improving employee health and Typical business operating costs[13]
productivity. There are numerous ways to improve 1
1
employee health, including exposure to daylight and
access to outside views. Several certification programs
CO2 CO2 $
such as LEED, BREEAM and DGBN exists (read more
Students achieve Workers are 18% 15-40% increase
$ about green certificates on page 32) to guide the $
5-14% higher test scores more productive in Retail Sales
design, construction and operation of high performance 2 2
and learn 20-26% faster 1 1
buildings. Points for excellence are distributed
across different categories, one of which is Indoor
CO2 CO2 EN EN $ $
Environmental Quality. CO2 CO
12101-2
2 12101-10
$ $
3 3
2 2
Systems
EN EN EN EN Productivity Increases by:
12101-2 12101-10 12101-2 12101-10
4 4
3 3
M
VdS KNX
EN
CO2VdS
12101
8 B
BACnet
300 KNX
24V
LONCO
2
230V
Modbus
BACnet LON Modbus
230-
400V
8
7 230- 7
400V
10 11
9 9
4A60A 4.8A
64A 8A EN16A B20A 24V
40A
EN 230V
48A
B 60A24V 64A230V 8 8
12101 300 12101 300
← Back to index
24%
20%
Increased productivity (%)
16%
12%
Average improvements 8.5%
8% $3,900 per employee
4%
3.2% 5.1% 7.5% 7.7% 9.75% 18%
0%
Sterling and Skov et Heschong Kroeling et Leaman Rowe
Sterling 1983 al. 1990 Mahone 2002 al. 1988 2001 2002
7% reduced 40% reduced increased 67% reduced perceived productivity perceived productivity
absenteeism SBS symptoms testscores SBS symptoms increase increase
12 13
← Back to index
230 / CNBOP-
24V 120V 230V WFI ETL
EN 12101 400V PIB NV Embedded®
compatible
NV Embedded®
3 in 1 True
KNX
LON BACnet Modbus VdS MAX MAX MAX NF
MAX MAX MAX MAX MAX MAX MAX Bluetooth
10A 20A 4x5A 4A 4.8A 8A 16A 48A 60A 64A
LON VdS NF
EN 12101 B300
BACnet Modbus
MAX MAX MAX MAX MAX MAX MAX MAX MAX MAX KNX Bluetooth
10A 20A 4x5A 4A 4.8A 8A 16A 48A 60A 64A
230 / CNBOP- Natural- and hybrid ventilation systems yield:
24V 120V 230V WFI ETL
400V PIB NV Embedded®
compatible
■
NV Embedded®
3 in 1per employee
Annual energy cost savings
TrueSpeed™ MotorLink®
: $110
EN 12101
EN 12101 B300
MAX MAX MAX MAX MAX MAX MAX MAX MAX MAX Bluetooth
EN EN
10A 20A 4x5A 4A 4.8A 8A 16A 48A 60A 64A 1 12101-2 12101-10
CO2 CO2 $
$ EN 12101 B300
14 EN
1210160A
B
300
24V 230V 9 15 8
4A 4.8A 8A 16A 20A 40A 48A 64A
EN B 24V 230V 8
12101 300
← Back to index
16 17
← Back to index
Single-sided ventilation
The illustration shows a typical situation in an office with single sided-
ventilation, i.e. a room with windows on only one side. The example shows
the room during the winter months. The surrounding air is often cold in
Temp./CO2
the winter, meaning that windows cannot be opened for longer periods. To
overcome this problem pulse ventilation is used. Windows are opened for
short periods of time ensuring that the air in the room is replaced quickly.
Because cold air creates draughts even at very low wind speeds, the
windows are quickly closed again after a set period of time. High wind
speeds and low outdoor temperatures further limit the amount of time that
the windows are open.
Cross ventilation
The illustration shows the cross-ventilation principle. Cross ventilation is
achieved using windows on both sides of the room, creating a current of air
Temp./CO2
across the room. If the windows on both sides of the room are open, the
overpressure on the side of the building facing the wind and/or low pressure
on the opposite sheltered side will create a current of air through the room/
rooms from the exposed side to the sheltered side. To ensure optimal airflow
with as few draughts as possible, the windows on the side of the building
that is facing the wind are not opened as much as the windows on the
sheltered side.
Stack ventilation
The illustration shows the stack effect that arises as a consequence of
18 19
← Back to index KNX
KNX
KNX
KNX
KNX
EN 12101
EN 12101
EN 12101
EN 12101
EN 12101
400V
Embedded® NV Embedded®
PIB
CNBOP- 3 in 1 TrueSpeed™ MotorLink®
exceed 2.5 times the room height, and never more 24V 120V 230V 400V WFI ETL PIB
NVcompatible
Embedded®
NVcompatible
Embedded®
NV Embedded®
NV Embedded® 3 in 1 TrueSpeed™ MotorLink®
■ Cross ventilation
MAX MAX
– the room depth should
MAX not exceed
MAX MAX MAX MAX MAX MAX MAX
MAX
MAX MAX
MAX MAX
MAX MAX
MAX MAX
MAX MAX
MAX MAX
MAX MAX
MAX MAX
MAX MAX
MAX
Bluetooth
Bluetooth
5 times the room10A
MAX
10A
height. 20A
MAX
20A 4x5A
MAX 4A
MAX 4.8A
MAX 8A
MAX 16A
MAX 48A
MAX 60A
MAX 64A
MAX Bluetooth
MAX
10A MAX
20A 4x5A
MAX
4x5A 4A
MAX
4A 4.8A
MAX
4.8A 8A
MAX
8A 16A
MAX
16A 48A
MAX
48A 60A
MAX
60A 64A
MAX
64A
Bluetooth
■ Stack ventilation
10A– the distance
20A from the
4x5A facade to
4Athe 4.8A 8A 16A 48A 60A 64A
Bluetooth
Let our Cleantech Engineers
10A 20A 4x5A 4A
roof lights should not exceed 5 times the room height. 4.8A 8A 16A 48A 60A 64A
guide you
If in need for advice or assistance with evaluating
Window opening ISO 21927-9
ISO 21927-9
ISO 21927-9
~ 1.2m / 3.9ft
EN 12101
EN 12101
EN 12101
B300
B300
B300
Other natural ventilation guidelines your buildings’ potential for intelligent natural
■ ighly placed openings/windows in the facade –
H ISO 21927-9
~ 0.4
ISO 21927-9
EN 12101
EN 12101
B300
B300
■ ptimized natural night cooling.
O ventilation, we have a dedicated team of
preferably 2 m or more above floor level and with ■ Preferably include thermal mass for optimum professionals ready to share our knowledge and
sufficient clearance between the top of the vent and benefit of night cooling. know-how on this topic.
ceiling for inward opening vents so the achievable ≥ 2m / 6.5ft
■ User control e.g. timed override facility by local
opening area is not limited. keypads.
■ Bottom hung inward windows or top hung outward Automatic controlled Manually operated
■ Preference for cross ventilation, stack ventilation or Our services
openings in the facade. hybrid ventilation in high occupancy spaces e.g. in
1
■ Window height, facade: Approximately 400-600 mm. Floor classrooms. 11
1
■ A window width of approximately 1.2-1.4 m is often ■ Preferably a minimum 7m3 per person in e.g. 1 Ventilation proposals
optimal, since you often need two window actuators ifCO CO2 $ classrooms.
CO22 CO2 $
$
CO2 CO2 $
the width exceeds 1.2-1.4 m (subject to window profileCO2 CO2
$
■ Maximum$ air changes:
CO2 CO2 $
material and type, due to frame flex with single pull Winter:$
$Approximately 2.5-3 h-1 (average during 2
2
$ 2
point). occupied hours). 2 Air change calculations
2
■ Openings evenly distributed. Summer: Workstations: 4-6 h-1 can easily be
EN EN
EN
12101-2
EN
EN
12101-10
EN accepted.
12101-2
EN 12101-10
EN
12101-2
EN
12101-2
12101-10
EN
12101-10
Atriums and similar transient spaces where 3
12101-2 12101-10 people stay for shorter periods: 10-15 h-1 can be 3
3 CO2 level calculations
3
accepted. 3
120V 6
120V 6
120V 6
120V
120V
Read
6 more about our natural ventilation
6
calculation and how we can help
M
M 230- 7
M
M
VdS
VdS
KNX
KNX
CO2
CO2
BACnet
BACnet
LON
LON
Modbus
Modbus 230-
400V
230- 7
7
M VdS
VdS
VdS
KNX
KNX
KNX
CO2
CO2
CO2
BACnet
BACnet
BACnet
LON
LON
LON
Modbus
Modbus
Modbus
400V
230-
400V
230-
400V
7
7
400V
20 21
EN B 24V 230V 8
EN
12101
EN
B
300
B
24V
24V
230V
230V
8
8
12101
EN 300
B 24V 230V 8
12101
EN 300
B 24V 230V 8
12101 300
12101 300
CNBOP-
WFI ETL
← Back to index PIBNF NV Embedded®
compatible
NV Embedded®
3 in 1 TrueSpeed™ MotorLink®
48ANV Embedded®
60A 64A
3 in 1 TrueSpeed™ MotorLink®
eed™ MotorLink®
Acknowledging the importance of how a building solutions are based on BACnet, KNX, LON, and
is designed is first step in achieving an optimum MotorLink® technologies, making them easy to combine
indoor climate. However, the performance of a natural with other mechanical ventilation systems and integrate
ventilation system is not limited to the design of into any BMS system.
a building; how the system is controlled is equally
important. And if there are not enough openings in a Based on analyses and empirical data, we have
building to create ideal conditions for air change, you designed three control systems to meet 1 market needs
may even have to combine natural ventilation with and the varying requirements that different buildings
mechanical ventilation (called
$ hybrid- or mixed-mode ask for based on their size, location and purpose.
ventilation). All WindowMaster’s natural ventilation
$
1 2
EN EN
$ 12101-2 12101-10
1 2 3
22 23
WindowMaster project: Aller Domicile
9 10
← Back to index
24V
24V 120V
120V 230V
230V 400V
230 / WFI
WFI ETL
ETL
CNBOP-
PIB compatible 3 in 1
The efficiency of night cooling
TrueSpeed™
depends
MotorLink®
on theMotorLink wind and rain sensors that can detect when rain and
400V PIB NV Embedded® NV Embedded®
CNBOP- 3 in 1
400V
TrueSpeed™
24V 120V 230V WFI ETL PIB
®
NVcompatible
Embedded® NV Embedded®
NVcompatible
Embedded® NV Embedded® 3
3 in
in 1
1
TrueSpeed™ MotorLink ®
400V
TrueSpeed™ MotorLink ®
PIB compatible
NV Embedded®
thermal properties of the3building
NV Embedded®
and on the local wind speed limits are exceeded and then send a close
compatible in 1 TrueSpeed™ MotorLink ®
MAX MAX climate conditions, i.e. night-time wind speed and the signal to the windows to avoid potential water damage.
MAX MAX MAX MAX MAX MAX MAX MAX Bluetooth
MAX
MAX
10A MAX
MAX
20A MAX
MAX
4x5A MAX
MAX
4A MAX
MAX
4.8A MAX
MAX
8A MAX
MAX
16A MAX
MAX
48A MAX
MAX
60A MAX
MAX
64A temperature swing
Bluetooth of the ambient air.
MAX MAX MAX MAX MAX MAX MAX MAX MAX MAX Bluetooth
Bluetooth
10A
MAX
10A 20A
MAX
20A 4x5A
MAX
4x5A 4A
MAX
4A 4.8A
MAX
4.8A 8A
MAX
8A 16A
MAX
16A 48A
MAX
48A 60A
MAX
60A 64A
MAX
64A All in all, passive night purging is a safe way to ventilate
10A 20A 4x5A 4A 4.8A 8A 16A 48A 60A 64A Bluetooth
10A 20A 4x5A 4A 4.8A 8A 16A 48A 60A 64A It is particularly effective in climates that have cool and cool down a building for improved well-being of the
night time temperatures as there will be a greater occupants while reducing energy consumption and the
difference between internal and external temperatures. concomitant energy bill.
ISO 21927-9
ISO 21927-9
EN 12101
EN 12101
B300
B300
This is not to say that night purging cannot be effective
in warmer climates. Even when internal and external
ISO 21927-9 EN 12101 B300
ISO 21927-9 EN 12101 B300
In a typical new office building with normal heat loads Night purging using natural ventilation – 1
generated from people, lighting and computers etc., 11
cooling may be needed even at outdoor temperatures
how does it work? Key benefits of night purge 1 Reduces daytime use of mechanical cooling
1 systems
below 0 degree Celsius. This is an example of how the
CO 2 Natural
CO2 night ventilation is a passive cooling method, $
$
ventilation
CO CO $
new building regulations, lowered U-values and the CO 2
CO22 driven
CO
CO2
2
2 by the natural forces of the wind and/or $ $
CO CO $ $
continued focus on the heating usage in buildings have2 thermally (stack) generated pressures. The heat
2
$
$ 2
resulted in a decreased need for heating but increased absorbed by a building's exposed thermal mass during $ 2
2
2 Lowers energy bill
the need for cooling. the day is released to the indoor air at night, after which 2
EN external EN
it is purged by night ventilation. Meanwhile,
12101-2
EN
EN 12101-10
EN
EN
Passive cooling measures can play an important role fresh air cools down the thermal mass, 12101-2
which
EN then EN
12101-10
12101-2
EN
12101-2 12101-10
EN
12101-10 3
in improving the energy efficiency of a building by acts as a heat sink during the following12101-2
day. The night
12101-10 3 Enhances performance of the building
3
3
reducing or even eliminating the need for auxiliary flushing involves automatically operable windows or 3 envelope
cooling. One passive cooling technique, commonly louvres being opened for a pre-set period of time over
used in private, public and commercial buildings, is night night, allowing a natural air flow through the building.
purging ("night flushing"). It is the removal of heat from 4
4
4 Improves occupant health and comfort
a building by bringing in cool night time air without the 4
Why should night purging be 4
use of active HVAC cooling and ventilation. Night purge
ventilation is a critical component to enhancing the incorporated into your building?
BMS
performance of any naturally ventilated building that Night purge ventilation
BMS
can help reduce the building 5 Low carbon method for building cooling
BMS 5
is used during the summer time and in need of cooling operating costs, withBMS
hot and stale air being replaced 5
BMS 5
even during winter. with fresh night time air. This reduces the need for the 5
24 25
120V 6
120V
120V 6
120V 6
6
120V 6
← Back to index
26 27
← Back to index
Wiring routes and concealment Multi speed operation Actuator position feedback
The actuator must provide two-way communication The actuator must provide two-way communication
The visibility of wiring routes for windows are rarely On high load applications, such as large roof lights with with the control panel to enable it to operate at a very with the control panel to enable feedback to the control
considered during the specification and tender process. pitched opening, spindle actuators are usually used. slow speed when in the automatic mode. Operating in software on the exact position, for precision of opening
Nevertheless, paying attention to this detail in the The solid spindle housing hangs down into the space slow speed reduces noise significantly to near silent and control (mm by mm) as well as a security indicator
specification and preparation for concealment can when closed, which many designers and clients find when opening/closing a window, meaning that the for open windows.
reduce cost and improve aesthetics in subsequent unsightly. High capacity WMU 888 chain actuators ventilation system will not cause disturbance to the
stages of the building process. from WindowMaster can address this issue and offer a building occupants. Two-way communication will
powerful and neater solution. also enable the motors to operate at a faster speed Synchronised actuators
Oftentimes, a window profile can be used as a conduit when activated by the manual keypads, for example,
for 24V actuator wiring. It may require some co- Most actuators used for natural ventilation are 24V DC, to provide an immediate visual response to the user. Where opening vents are about 1.200mm wide or more,
ordination during installation but the specification which gives higher torque capacity and makes them The motors will operate at full speed during smoke the window or curtain walling supplier shall check
erases the need for surface-mounted trunking that electrically safer when using the window profile for clearance in the event of fire. WindowMaster actuators whether two actuators are required. This should be
can potentially spoil the overall look of the window containment. There are 240V actuators on the market, are the only ones in the market with the ability to checked with the profile systems house as it is dictated
system. If vents are at a high level, simply preparing but these are generally designed for occasional use operate at three different speed levels. by frame flex and the capacity to achieve a seal at the
the mullions to allow cables to be pulled through will and are prone to overheating if used regularly, so are edges with a single pull point. If required, the actuators
enable cables to be hidden on top of the transom thus therefore normally avoided. must use MotorLink® to synchronise speed and time of
limiting their appearance on the face of the façade or Pressure safety function operation.
windows. Alternatively, a matching cover profile may be When addressing the wiring routes, the window or
considered. curtain walling fabricator should prepare the profiles The actuator must have the ability to monitor for The actuator must provide two-way communication
for these with grommets and draw wires, using the entrapment on specified windows by communication with the control panel to enable feedback to the control
In certain windows (i.e. VELFAC windows), the actuator frame as containment. If at high level, a route should be via the microprocessors installed within the actuator software on the window status and an early indication
can be hidden inside the profile. Other aluminium provided through the mullions without having to bridge and by monitoring in real-time the amount of electrical of any errors with the actuator operation or the wiring.
systems also allow for this solution but low profile the inside face of the profile. If this cannot be avoided, current being drawn and the precise position of the
systems usually offer little room to hide the actuators, consideration should be given to a matching cover window to an accuracy of less than a millimetre. The
which will therefore be surface mounted. Accordingly, profile. MotorLink® actuator will detect if an object becomes
actuator colour- and finish need to be considered trapped in the leading edge of the window and prevent
already in the specification. it from closing by monitoring the amount of current
being drawn and then reversing the actuator to release
the obstruction.
28 29
← Back to index
Opening areas
Actuators come with different standard chain lengths:
250, 400, 500, 600 and 1.000 mm. Using the smallest
actuator possible will keep the unit size and cost down.
The longer the chain, the bigger the links are needed
to maintain integrity and therefore also the bigger the
housing to hide it when it is withdrawn. To reduce the
size and cost and improve aesthetics, use a 250mm
chain where possible.
be included if it is a string of opening windows height. Avoiding side-hung windows removes the risk in doubt, consult WindowMaster or fabricators early on
opening areas (adjacent open vents effectively cancel out the of a scissor action at body height, which can present in the project.
triangles). a safety hazard. In addition, the lower element of the
■ alculate the geometric free area by using the
C opening can introduce cold air at body height.
rectangle or throat at the leading edge of the ■ any window suppliers, or WindowMaster, offer
M
opening sash first. If slightly bigger areas are support with these calculations.
required, then consider the triangles at the sides
if they are allowed to be included. For example,
a standard 250mm chain gives approximately
0.210m clear opening x 1m window width gives Compiling a specification to ■ ow noise during automation to minimise disruption
L
0.210m2 clear opening per opening window. Enhanced safety to help protect occupants in case of
avoid common complaints
■
entrapment
■ onsider any reveal or sill that might limit
C ■ The capability for accurate control to prevent draughts
the actual clear opening achieved (Building Most quality actuators look similar, but while and energy problems
Regulations, Approved Document B, 2007). High aesthetically important, this has no bearing on how the ■ Minimised visual impact of wiring/cables on the
level top-hung outward opening windows can actuator will deliver on its requirements. When creating windows
avoid the reveal or sill limiting the achievable the specification, any expectations you have for the ■ Synchronised motors for wider windows to help
opening areas. benefit of the project and client should be made explicit. protect the sash from distortion
Decide which of the following points are important for ■ A special colour requirement
the project and your client: ■ Real time indication to the building owner of faults.
30 31
NF
NF
← Back to index
NF
NF
NF
dded®® NV Embedded®®
dded
ible
ible ®
dded
NV Embedded
NV Embedded®
3
3 in
in 1
1
TrueSpeed™
TrueSpeed™
MotorLink®®
MotorLink
dded ®
NV Embedded® 3
3 in 1 TrueSpeed™ MotorLink®®
3 in
in 1
ible ®
dded NV Embedded® TrueSpeed™ MotorLink®
ible
ible ®
dded NV Embedded® 1 TrueSpeed™ MotorLink
3 in 1 TrueSpeed™ MotorLink®
Green certifications
ible
Bluetooth
Bluetooth
Bluetooth
Bluetooth
Bluetooth
Bluetooth
11
WindowMaster's natural 1
1
educing the energy consumption and the
R
ventilation solutions can 1 total resulting CO2 emissions.
contribute
$
to:
$
$
$ 2
$ 2 aving a good thermal comfort during summer
H
2
Project
2
2 and winter.
3
3
3
3
Using free cooling by introducing night cooling. examples
3
120V
120V 6
120V 6 iving a precise and accurate control of the
G
120V
120V 6
6
120V 6 actuators by using MotorLink® technology.
230-
230- 7
400V
230- 7
400V
230-
230- 7
400V
230-
400V 7
400V
400V
7
8
8
8
8
8
BREEAM DGNB LEED – Leadership in Energy
WindowMaster’s indoor WindowMaster’s indoor and Environmental Design
climate solutions can climate solutions9
9can provide WindowMaster’s indoor
60A
60A 64A 9
influence
60A up to64A
42 BREEAM
64A up to 80 DGNB9 points. climate solutions can provide
60A
60A 64A
64A 9 WindowMaster project: UWE - Bristol Business School
60A points.
64A up to 22 LEED points. Photo: © Stride Treglown / Tom Bright
32 33
10
10
10
10
10
← Back to index
A healthy indoor
climate
By monitoring indoor CO2, humidity
and temperature, the automated
natural ventilation system can
manage air flow through the
building’s window openings and
the chimney and thereby create
an optimum indoor environment.
To accurately measure the airflow
through each individual opening
given wind direction and speed
a Computational Fluid Dynamics
simulation was carried out. The
building and its surroundings were
modelled by an advanced software
program, so that the airflow
through the individual openings
could be calculated precisely based
on the wind pressure coefficient for
different wind directions.
34 35
← Back to index
Doug Gensler
Managing Director | Gensler Boston
The Tower at PNC Plaza is a 800,000 square feet From its one-of-a-kind, breathable double skin to
headquarters for the PNC bank in Pittsburgh, its innovative workplace strategy, The Tower drives
Pennsylvania. performance to new levels. The building “breathes” with
a double-skin facade: a natural ventilation system that
Planned as a landmark building, both with regards to has a glass outer weather and air barrier and an inner
design and in terms of environmental friendly solutions, layer with automated air vents, a wood curtain wall, and
the 33-story tower has a construction budget of manually operated sliding doors. A series of automatic
approximately $240 million. Incorporating state-of-the- sensors on both layers open up the building for air when
art green technology, including a double-skin facade the weather permits.
and solar chimney, the building was designed to exceed
LEED Platinum certification and to be the greenest The main reason for choosing WindowMaster as a
office tower in the world. supplier for this project is the MotorLink® technology
that enables genuine synchronization of four actuators
The WindowMaster Solution on one parallel window and exact position control and
feedback via the BACnet BMS.
WindowMaster has delivered more than 6300
actuators to control 700 parallel windows in the outer
double skin façade and 1450 automated air vents in the
inner facade.
36 37
← Back to index
Platinum protected
Gold and fire-protected
Silver
The new home of the John and Frances Angelos Law aircondition is on and made available for the users to
Center at 192,000 sq. ft. unites classrooms, faculty open and close at will by the manual override switches,
offices, administrative space, and the law library under a when the aircondition is off.
single roof for the first time in the history of the school.
The building, located at the prominent intersection of Operable windows are provided in regularly occupied
Mount Royal Avenue and Charles Street, functionally spaces, allowing users to have direct control of their
and symbolically defines the Law School as an environment. Occupants have local control of operable
academic and social nexus, offering state-of-the-art windows in all office, teaching and library spaces,
teaching and learning facilities.[21] and are notified of favorable outdoor conditions by
means of a green indicator light that communicates
The WindowMaster solution appropriate times to open a window. Atrium operable
windows are fully controlled by the building automation
WindowMaster has provided more than 1000 system based on the quality of outdoor conditions.
MotorLink® actuators integrating the intelligent facades Atrium smoke exhaust fans are activated at low
with the LONworks Buildings Management System. speed in natural ventilation mode to guarantee good Read more about The University
This enables full control of each motorized window. The cross ventilation through all spaces, and acoustically of Baltimore
windows will then be automatically closed when the
38 39
← Back to index
40 41
← Back to index
42%
savings from title 24
baseline
Passive ventilation
Natural ventilation /
Radiant Floor System
The University of San Francisco (USF) needed to control temperature. In line with the campus’ wind Active ventilation
replace its cramped 1966 Harney Hall, built when patterns, the building is designed to accommodate Type 1:
science enrollments were just half of today’s levels. natural ventilation. Piping systems embedded in the Intensive Lab Space
Construction of a new state-of-the-art science building concrete run water hot and cold, which helps control
100% Outside Air
(S.J. Center for Science and Innovation) located in the the building’s temperature.[23]
center of the USF main campus, immediately adjacent Type 2:
to two existing buildings. Classrooms include chemistry Overhead /
wet-labs with fume hoods, physics labs, lecture halls, Displacement
computer labs, and community spaces. The 61,610 sq.
ft.building had a budget of $43M and was designed Type 3:
following LEED Gold standards. Underfloor Air
42 43
← Back to index
Solar cells
Atrium ventilation
Highly insulating
and tight climate
LED screens
Hybrid ventilation
Green Lighthouse was Denmark's first certified great electricity consumers. Automatic window control Fresh air intake
sustainable building, having become the first building in (natural ventilation) has therefore been installed to
the country to achieve a LEED Gold rating. ensure fresh air in the building. Mechanical ventilation is
only in operation for a very limited part of the year. Night cooling Sun screening
Green Lighthouse, a faculty building for the Faculty of
Cast shadow
Science at the University of Copenhagen in Denmark, NV Advance® from WindowMaster ensures that the
Heating pump Solar heating WindowMaster
is designed to optimize the well-being of the people building is at all times using the most efficient form of container touch screen
working in the building as well as being CO2 neutral. energy. This is done by continuous measurement of
room temperature, CO2 and light levels and using the
The 10,000 sq. ft. (950 m2) was built as a demo building weather station records of outdoor temperature, wind
in connection with the UN Climate Conference, COP15, speed and direction, sunshine and rain. Based on all
held in Copenhagen in 2009, with a sharp focus on these data, NV Advance® determines which type of
energy consumption and renewable energy. ventilation is optimal and whether there is a need for
heating or additional electrical lighting.
The WindowMaster solution
For most of the year, ventilation is provided solely via
An important element in achieving CO2 neutrality is the automatic control of windows that are opened and
using technology that reduces the use of electricity. closed in each room/area depending on the need for
Traditional ventilation systems are usually one of the
44 45
← Back to index
Zurich’s 126 metre high 430,000 sq. ft. (40,000 m2) MotorLink® actuators are connected to MotorLink®
Prime Tower, the tallest building in Switzerland, has MotorControllers to provide power and control primarily
been designed by architects Annette Gigon and Mike for natural ventilation.
Guyer to be at the forefront of sustainable building
technologies. The windows in Prime Tower are large rectangular
parallel opening windows, which weigh approximately
The development houses offices, restaurants and 360kg. To safely operate under load each window is
bars, retail outlets and support facilities. As part of the equipped with four WindowMaster chain actuators and
sustainable construction of the building it features one special espagnolette/locking actuator.
natural ventilation controlled by the MotorLink®
Photography by Swiss Prime Site
automated window control system. The window actuators communicate with the
MotorController via digital MotorLink® technology.
The WindowMaster solution Exact feedback concerning position as well as accurate
synchronisation of the actuators is therefore ensured.
Schüco, in partnership with façade designers The chain actuators and other components were
Emmer Pfenninger Partner and façade manufacturer tested and approved according to strict performance Read more about Prime Tower
Dobler Metallbau, delivered an installation of 6,910 standards.
WindowMaster chain actuators for the automation
of 1,382 parallel opening windows including one
espagnolette locking motor for each window. These
46 47
← Back to index
43% reducement of
the building’s energy
use, compared with
state requirements
The facility has been awarded LEED Silver certification The WindowMaster solution
by the U.S. Green Building Council, making it the The natural ventilation occurs via high-level automated
district’s fourteenth LEED certified facility. Natural façade windows in the classroom. In the back of
ventilation and daylighting played a big part, while each classroom, there are high-level automated vents,
sustainable construction materials and high-efficiency which can lead the air into the common areas (hallway)
plumbing and mechanical systems also contributed to where the air is ventilated out through the high-level
the green qualifications. automated windows in the clerestory.
This $22.5-million school project consolidates programs Each teacher controls the classroom temperature
such as English as a second language and disability through a single switch on the wall that offers the
support into a bright and airy two-story learning center choice between natural and mechanical cooling. When
of 37,700 sq. ft. (3500 m2). Project engineers have the temperature falls within the comfort zone (as it
incorporated sustainable features such as natural does the majority of the year), the natural ventilation
ventilation and natural lighting to reduce the building’s system disengages the mechanical air conditioning and Read more about San Diego Continuing
energy use by 43% compared with state requirements. automatically opens the windows. Education Mesa College Campus
48 49
← Back to index
50 51
WindowMaster aspires to protect people and the environment by creating a healthy
and safe indoor climate, automatically ventilating spaces with fresh air through facade
and roof windows in buildings. We offer the construction industry foresighted, flexible
and intelligent window actuators and control systems for natural ventilation, mixed
mode ventilation, and smoke ventilation – of the highest quality.
©WindowMaster 2017, 2021 ®WindowMaster is a registered trademark used under license by WindowMaster International
industry meet its green obligations and achieve their architectural and technical
ambitions.
windowmaster.com