You are on page 1of 23

© KROHNE 01/2006 7025552100

Supplementary
Installation and Operating
Instructions

IFC300 PROFIBUS
with
MBP Physical Interface and
PA Profile 3.0
(“Profibus PA Device”)

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

CONTENTS:

1
TU UT GENERAL
TU UT 3

2
TU UT ITEMS INCLUDED WITH SUPPLY
TU UT 3

3
TU UT SOFTWARE HISTORY
TU UT 3

4
TU UT PROFIBUS-PA DEVICE WITH MBP INTERFACE
TU UT 3
4.1
TU UT PROFILES
TU UT 4
4.2
TU UT GSD FILES
TU UT 4
4.2.1
TU UT Manufacturer specific GSD file: KR024501.GSD
TU UT 5
4.2.2
TU UT Manufacturer specific GSD file: YP024501.GSD
TU UT 6
4.2.3
TU UT Manufacturer specific GSD files “KROHF401.GSD”/“YP01F401.GSD” of an “IFC090PA”
TU UT 6
4.2.4
TU UT Profile specific GSD file: PA139740. GSD
TU UT 8
4.3
TU UT CYCLIC DATA EXCHANGE
TU UT 8
4.4
TU UT DATA STRUCTURE OF FUNCTION BLOCK OUTPUT VALUES
TU UT 8
4.4.1
TU UT Float Value
TU UT 8
4.4.2
TU UT Status Value
TU UT 8
4.5
TU UT DIAGNOSIS
TU UT 9
5
TU UT ELECTRICAL CONNECTION
TU UT 10
5.1
TU UT PROFIBUS-PA CONNECTION
TU UT 10
6
TU UT MENU SETTINGS
TU UT 11
6.1
TU UT USING THE DISPLAY MENU TO DISTINGUISH THE CURRENT REVISION OF THE DEVICE
TU UT 17
7
TU UT TECHNICAL DATA
TU UT 18

8
TU UT DEVICE DESCRIPTION FOR THE SIMATIC PROCESS DEVICE MANAGER (PDM)
TU UT 18
8.1
TU UT INSTALLATION
TU UT 18
8.2
TU UT OPERATING
TU UT 18
9
TU UT ATTACHMNET A
TU UT 19

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 2/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

1 General
These Instructions are supplementary to the “IFC 300 (OPTIFLUX) Handbook”. The details given there, in particular
the Safety Information are valid and should be adhered to. These Supplementary Instructions provide only additional
information for device operation and connection to a PROFIBUS fieldbus.

2 Items included with supply


In addition to the standard scope of supply, these Supplementary Instructions for the IFC300 PROFIBUS MBP
Interface will be included.

3 Software history
Configuration Tool
Issued Signal Converter User Program
(Add-On)
Month/ Hardware Firmware Hardware Software GSD GSD
Year
Model name adopted in the File name in the GSD
GSD compilation*:
01/06 IFC300 PROFIBUS MBP V2.0.0 / 060112 PC DTM > --/--
U U “IFC300 (MBP) Rev. 2” KR024501.GSD
Interface with PA Profile 3.0 V2.0.0 / 060126 ”YP0 IFC300 (MBP) Rev. 2” YP024501.GSD
Device Description (Ident No
& Dev.Rev. & DDRev.): “Flow with 1 AI, 1 TOT (PhyL 1)” PA139740.GSD
4501030002

PDM ≥ 6.0

* -> see detailed description depicted below (Chapter 4.4 GSD Files)

4 PROFIBUS-PA Device with MBP Interface


(MBP == Manchester Coded Bus Powered)
U U U U U U

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 3/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

The diagram above depicts a typical network configuration with PROFIBUS-PA devices with MBP interface in
hazardous and non-hazardous environment.
As a rule, the PROFIBUS-PA segment is connected to a coupler which, among other things, provides the conversion
to the PROFIBUS-DP bus line. It should be mentioned that the segment coupler is normally set to a fixed baud rate
on the DP side.
Additional information on the configuration and operation of PROFIBUS-PA networks is to be found in the KROHNE
brochure “Fundamentals PROFIBUS” which can be downloaded from the KROHNE homepage
http://www.krohne.com ( following the path: Service -> Download Center -> select “Brochures and Catalogues” ->
HTU UTH

choose “Fundamentals PROFIBUS”) or contact “KROHNE Marketing”.

4.1 Profiles
The IFC300 PROFIBUS MBP interface supports the PROFIBUS-PA Profile Version 3.0. Additionally, all relevant
parameters of the device are accessible via the PROFIBUS interface.
The IFC300 PROFIBUS MBP interface with PA Profile 3.0 supports the following blocks:
• One physical block.
This block contains the parameters defined in PA Profile 3.0.
• One transducer block for electromagnetic flow devices.
This block provides the parameters and functions defined in PA Profile 3.0.
• Five “Analog Input (AI)” function blocks: by default “Volume Flow”, “Mass Flow”, “Speed Flow”, “Coil
Temperature” and “Conductivity”.
• Three “Totalizer (TOT)” function blocks: by default the first two totalizers will integrate “Volume” and third one will
integrate “Mass”.

4.2 GSD Files


A “PROFIBUS GSD ZIP” file (e.g. GSD-31777813.zip) including both all KROHNE GSD files and additional data files
can be downloaded from the KROHNE homepage http://www.krohne.com ( following the path: Service -> Download
HTU UTH

Center -> select “Software” -> choose “PROFIBUS GSD”) or contact “KROHNE Marketing”. The GSD file contains
information that will be needed for project planning of the PROFIBUS-DP communication network. The relevant data
files (e.g. ifc300_n.bmp; ifc300_n.dib) must be loaded into the bus configuration system/master system before start-
up of the bus system.

The IFC300 PROFIBUS MBP Interface is based on the PROFIBUS-PA Profile V 3.0. The device supports three
Ident-Nos.:

• Ident-No. “4501hex”: this Ident-No. belongs to the KR024501.GSD / YP024501.GSD and includes the
complete functionality of the electromagnetic flow meter.
U U

• Ident-No. “9740hex”: the application of the manufacturer independent Ident-No. “9740hex” (GSD file
“PA139740.GSD”) provides interchangeability of devices, i.e. an exchange of electromagnetic flow
meters of different vendors.

• Ident-No. “F401hex”: this Ident-No. supports a compatibility mode concerning the cyclic data transfer
(cyclic measurement values and diagnosis) if the “IFC300 with PROFIBUS MBP Interface” will be used for
replacement of an “IFC090PA”. It is not necessary to adapt the PLC configuration. Communication
U U

functions are restricted to those functions supported by IFC090 converters. Take care to set the “IFC300
PROFIBUS MBP interface” parameters in a way to get the same behavior as of “IFC090PA” concerning
calculation of measuring values and totalizers.

Please follow the instructions in the manual of the host supplier when installing the GSD File you need and the
additional files (IFC300_n.bmp and IFC300_n.dib) into the PLC. If separated by the bus configuration system the
device entry of the IFC300 PROFIBUS MBP Interface with PA Profile 3.0 will be located within the slave family
PROFIBUS-PA.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 4/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

4.2.1 Manufacturer specific GSD file: KR024501.GSD

This GSD file is for use with standard DP/PA segment coupler. KROHNE delivers the GSD files with the entire device
functionality which is listed below:

Block Number Standard-Configuration KR024501.GSD Default unit:


(function block output: value + status) Ident-No. 4501
1 Volume Flow AI-FB m3/h
2 Volume Totalizer Totalizer-FB m3
3 Volume Totalizer Totalizer-FB m3
4 Mass Totalizer Totalizer-FB kg
5 Mass Flow AI-FB kg/s
6 Speed Flow AI-FB m/s
7 Coil Temperature AI-FB K
8 Conductivity AI-FB S/m

AI = Analog Input Function Block


FB = Function Block

There will be two additional output values available by changing the function block channel parameters of the above
mentioned “Analog Input Function Blocks”:

X Temperature AI-FB °C
(electronic temperature)
X Supply AI-FB V
(the internal supply voltage for the
PROFIBUS Interface)

X == Block Number 1, 5, 6, 7 or 8 may be used

There are separate settings to select the units for local display and PROFIBUS. Modifications of the units of the
display will have no effect on the data transferred via PROFIBUS. A master class 2 tool is required to modify the
units for PROFIBUS transfer.

Important Notes:
U

During network configuration the user has to define which function block outputs of the “IFC300 PROFIBUS MBP
interface” should be transferred cyclically to the master. This is performed by a bus configuration tool (e.g. “HW-
Config” for PC-S7 from Siemens). This tool offers the functions described as follows:
1. It is possible to configure an “Empty” block (the code of an “Empty” block is defined as 0x00) on each block
number. This implies that no data are transmitted in the cyclic data telegram for this block.
2. There is NO “Totalizer (TOT)” function block allowed on block position 1, 5, 6, 7 and 8! On these positions, only
an “Analog Input (AI)” function block or an “Empty” block is allowed!

Note: All codes supported by “Analog Input (AI)” - and “Totalizer (TOT)” – function blocks will be found in the
corresponding GSD files.
3. There is NO “Analog Input (AI)” function block allowed on block position 2, 3 and 4! On these positions , onla a
“Totalizer (TOT)” function block or an “Empty” block is allowed!

4. There is a choice of 7 different totalizer functions, which can be allocated to the blocks 2, 3 and / or 4. The 7
functions are defined as follows:

“Total” cyclic transfer of the totalizer value with status to the master
“SetTot + Total” cyclic transfer of the totalizer value with status to the master + cyclic control data
from master to the device via the parameter SetTot
“ModeTot + Total” cyclic transfer of the totalizer value with status to the master + cyclic control data
from master to the device via the parameter ModeTot
“SetTot+ModeTot+Total” cyclic transfer of the totalizer value with status to the master + cyclic control data

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 5/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

from master to the device via the parameters SetTot and ModeTot (in the given
order)
“SetTot” cyclic control data from master to the device via the parameter SetTot
“ModeTot” cyclic control data from master to the device via the parameter ModeTot
“SetTot + ModeTot” cyclic control data from master to the device via the parameters SetTot and ModeTot
(in the given order)

Both, the Byte SetTot and ModeTot are cyclically sent from the Master to the device if these bytes are inserted
as output data via the PLC configurator. The meaning of these control bytes are as follows:

SetTot:
SetTot =0: Totalizer is totalizing.
SetTot =1: Totalizer will be reset to 0 and stays at 0 until SetTot is switched back again to 0. If the value of
SetTot changes from “1” to “0” the totalizer starts counting from 0.
SetTot =2: Totalizer is set to the value defined by PresetTot. PresetTot can be written via a acyclic master
(totalizer in block 2 = Slot 2 Index 32; totalizer in block 3 = Slot 3 Index 32; totalizer in block 4 =
Slot 4 Index 32). If the value of SetTot changes from “2” to “0” the totalizer starts counting from
the current value defined by PresetTot.
SetTot > 2: not allowed. Value is ignored; totalizer remains in its last valid setting.

ModeTot:
ModeTot = 0 totalizer totalizes positive and negative values.
ModeTot = 1 totalizes only positive values.
ModeTot = 2 totalizes only negative values.
ModeTot = 3 totalizer is stopped, no totalization will be done.
ModeTot = 248 totalizes all values as positive (negative values will be multiplied with “-1.0”)
ModeTot = 249 totalizes all values as negative (positive values will be multiplied with “-1.0”)

All other values of ModeTot not allowed. Value is ignored; totalizer remains in its last valid setting.
5. The standard block configuration may be changed by the customer but using the default settings is highly
recommended. If the standard block configuration should be changed by the customer an acyclic master tool
must be used to change the “channel parameter” value of the block which should be connected to another
transducer output value.

4.2.2 Manufacturer specific GSD file: YP024501.GSD

This GSD file is for use with the transparent DP/PA coupler SK2 of Pepperl&Fuchs (up to 12 MBaud on the DP
segment) and supports the same device functionality as listed above (Manufacturer specific GSD file:
KR024501.GSD ).

Note: This is true for all KROHNE PROFIBUS devices with MBP interface: there are always two types of GSD files in
our GSD compilation:
• One standard GSD file for a standard DP/PA segment coupler: file name: “KR….GSD”
• One special GSD file specific for the segment coupler SK2 of Pepperl&Fuchs file name: “YP….GSD”

4.2.3 Manufacturer specific GSD files “KROHF401.GSD”/“YP01F401.GSD” of an “IFC090PA”

The “IFC300 PROFIBUS MBP Interface” offers a compatibility mode ensuring operation when being connected to a
PLC with software parameters based on the “IFC090PA”. This option is important for those customers who do not
want to change the parameters in the PLC software after having replaced the “IFC090PA” by an “IFC300 with
PROFIBUS MBP Interface”. In this application, the compatibility mode has to be selected in the service menu of the
“IFC300 with PROFIBUS MBP Interface”; some other entries have to be performed in a next.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 6/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

The overall situation is described using the following example: Consider an “IFC090PA” standard configuration based
on IFS…FLUX* flow sensor and “IFC090PA” flow converter. Consider the following two options for replacements
(IFS….FLUX* = IFS sensor compliant with “IFC090PA”):
I. the “IFC090PA” flow converter will be replaced by an “IFC300 PROFIBUS MBP Interface” flow converter. The
IFS…FLUX flow sensor is kept

II. In addition to I, also the IFS…FLUX flow sensor will be replaced by an OPTIFLUX flow sensor

Integration into the PLC via PLC


Options for “IFC300 PROFIBUS
a) “IFC090PA” GSD or The PROFIBUS PA
Sensor Installation: MBP Interface” converter
b) “IFC300 (MBP)” GSD parameter set in the Ctrl
Device PROFIBUS PA Software of the PLC
- Option I: IFS…FLUX Software Software
a) does not need to be
- Option II: OPTIFLUX changed
b) has to be changed
For both replacements I and II, there are 2 options how to deal with the GSDs. In order to provide communication
between “IFC300 with PROFIBUS MBP Interface” and the PLC, you may - in principle – use the GSD of the
“IFC090PA” (”KROHF401.GSD” or ” YP01F401.GSD”) and –alternatively - the GSD of the “IFC300 with PROFIBUS
MBP Interface” (“KR024501.GSD” or “YP024501.GSD”). However, both GSDs, when applied, do not provide the U U

same level of functionality in the PLC. The available PROFIBUS functionality of the “IFC300 with PROFIBUS MBP
Interface” in the PLC as function of installed flow sensor and GSD used for integration into the PLC is as follows:

Integration
“IFC090PA” GSD “IFC300 with PROFIBUS MBP Interface”
into the PLC GSD
(KROHF401.GSD)
via
(KR024501.GSD)
Installed
Sensor
“IFC300 with PROFIBUS MBP Interface”
IFS…FLUX flow sensor “IFC090PA” profile 2 functionality functionality (Some “IFC300 with
(Option I) PROFIBUS MBP Interface” self-test
functions not available)

OPTIFLUX flow sensor “IFC090PA” profile 2 functionality “IFC300 with PROFIBUS MBP Interface”
(Option II) functionality

How to deal with the PA The “IFC090PA” Parameter Set for The “IFC090PA” Parameter Set for the
parameter set in the the PLC Ctrl Software can be used Ctrl. Software has to be adapted with
PLC Ctrl Software: as existing in the PLC reference to the interface of “IFC300 with
PROFIBUS MBP Interface”

• If the GSD of the “IFC090PA” (”KROHF401.GSD” or ” YP01F401.GSD”) is used….


- The “IFC090PA” parameter set for the PLC control software will be maintained, i.e. there is no adaptation
needed with reference to the replaced interface of the “IFC300 with PROFIBUS MBP Interface”.
- In this usage of the GSD the PA Profile 2.0 functionality is provided in the PLC for both replacements, i.e. it is
not possible to reset the PA totalizer via the PLC.
• If the GSD of “IFC300 with PROFIBUS MBP Interface” (KR024501.GSD or YP024501.GSD) is used….
- The “IFC090PA” Parameter set for the PLC control software has to be adapted with reference to the
IFC300 PROFIBUS MPB interface.
- In this usage of the GSD the PA Profile 3.0 functionality is provided and all diagnostic features of the “IFC300
with PROFIBUS MBP Interface” are being made available.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 7/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

4.2.4 Profile specific GSD file: PA139740. GSD

The functionality of the profile specific GSD file is limited. This GSD file includes only two blocks:
Volume Flow and Volume Totalizer.

Block Number Standard-Configuration PA139740. GSD Default unit:


(function block output value) Ident-No. 9740
1 Volume Flow AI-FB m3/h
2 Volume Totalizer Totalizer-FB m3

The device has to be switched from “full functionality” to “interchangeable basic configuration” by using a master
class 2 tool (IDENT_NUMBER_SELECTOR: Slot 0, Index 40 change byte value to 0). In the next step, the device
has to be configured using the PA139740.GSD file.

4.3 Cyclic data exchange


During network configuration the user has to define which function block outputs of the IFC300 PROFIBUS MBP
Interface should be transferred cyclically to the master. Network configuration will be done using one of the GSD files
described above. The order of transmission of the function blocks always remains the same even if a function block
is defined as an “Empty” block (if so no function block output data will be send to the master and all function block
outputs following the “Empty” block will move up one position).

4.4 Data Structure of Function Block Output Values


The data structure of function block outputs consists of 5 bytes: a 4 byte float value (Float Format according IEEE U

Standard 754 Short Real Number) followed by a 1 byte status value. If all 8 function block outputs have been U

configured (see above), 40 byte will be transmitted.

4.4.1 Float Value

First an example of the float format:

Byte n Byte n+1 Byte n+2 Byte n+3


Bit7 Bit6 Bit7 Bit6 Bit7 Bit7
VZ 27 26 25 24 23 22 21 20 2-1 2-2 2-3 2-4 2-5 2-6
P P P P P P P P P P P P P P P P P P P P P P P P P P P P 2-7 2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15 2-16 2-17 2-18 2-19 2-20 2-21 2-22 2-23
P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P

Exponent Mantisse Mantisse Mantisse

Example: 40 F0 00 00 (hex) = 0100 0000 1111 0000 0000 0000 0000 0000 (binary)

Formula: Value = (-1)VZ * 2 (Exponent - 127) * (1 + Mantisse)


P P P P

Value = (-1)0 * 2 (129 - 127) * (1 + 2-1 + 2-2 + 2-3)


P P P P P P P P P P

Value = 1 * 4 * (1 + 0,5 + 0,25 + 0,125)


Value = 7,5

4.4.2 Status Value

You will find the meaning of the status byte (unsigned integer) by looking at the tables down below:

Quality Quality-Substatus Limits


Gr Gr QS QS QS QS Qu Qu
7 6 5 4 3 2 1 0
2P 2
P P P 2P 2
P 2 2 P P P P P P 2 2 P P P P

0 0 = bad
0 1 = uncertain
1 0 = good (Non Cascade)
1 1 = good (Cascade) - not supported

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 8/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

Status = bad
0 0 0 0 0 0 = non-specific
0 0 0 0 0 1 = configuration error
0 0 0 0 1 0 = not connected
0 0 0 0 1 1 = device failure
0 0 0 1 0 0 = sensor failure
0 0 0 1 0 1 = no communication (last usable value)
0 0 0 1 1 0 = no communication (no usable value)
0 0 0 1 1 1 = out of service

Status = uncertain
0 1 0 0 0 0 = non-specific
0 1 0 0 0 1 = last usable value
0 1 0 0 1 0 = substitute-set
0 1 0 0 1 1 = initial value
0 1 0 1 0 0 = sensor conversion not accurate
0 1 0 1 0 1 = engineering unit violation (unit not in the valid set)
0 1 0 1 1 0 = sub-normal
0 1 0 1 1 1 = configuration error
0 1 1 0 0 0 = simulated value
0 1 1 0 0 1 = sensor calibration

Status = good (Non-Cascade)


1 0 0 0 0 0 = ok
1 0 0 0 0 1 = update event
1 0 0 0 1 0 = active advisory alarm (priority < 8)
1 0 0 0 1 1 = active critical alarm (priority > 8)
1 0 0 1 0 0 = unacknowledged update event
1 0 0 1 0 1 = unacknowledged advisory alarm
1 0 0 1 1 0 = unacknowledged critical alarm
1 0 1 0 0 0 = initiate fail safe
1 0 1 0 0 1 = maintenance required

Status = Limits
0 0 = ok
0 1 = low limited
1 0 = high limited
1 1 = constant

Check the first two quality bits in order to get the quality information of the measurement value:

Good (non Cascade) function block output value is ok and can be used without restrictions
Good (Cascade) will not be supported, because it is not applicable for the device
Uncertain function block output value can be used but the accuracy can not be guaranteed (e.g. function
block outputs value has been frozen or A/D converter is saturated or out of range)
Bad function block output value is bad - don’t use it for process control!

The „Quality-Substatus“- and „Limit“-Bits will be used for further diagnostics or limit checking.

Attention: The status should be watched always because a number will be transmitted even if the status of the
measurement value is bad or uncertain. This is the only way to check the quality of the transmitted
measurement values.

4.5 Diagnosis
If the device internal diagnostic functions will detect an error some additional information will be sent to the Master
(for further information have a look at the UNIT_DIAG_BIT(i) definitions of the corresponding GSD-file)

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 9/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

5 Electrical Connection
For a detailed description please check the ”IFC 300 (OPTIFLUX) Handbook”. Refer also to the “PROFIBUS PA User
and Installation Guideline Version 2.2 February 2003 ” (PNO Order Number 2.092).

5.1 PROFIBUS-PA connection


The next figures explain the wiring options, based on four terminals with the following notations:

Note: The current linkage between the device and the PROFIBUS-PA bus cable is independent of polarity. This
implies the wiring shown below is also possible:

Note: The “IFC300 PROFIBUS MBP interface” will operate only if the additional power supply for the device is
connected / available.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 10/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

6 Menu Settings
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

For a detailed description please see ”IFC 300 (OPTIFLUX) Handbook”. Some special settings concerning the
PROFIBUS features are easily entered via the local display:

A -> QUICK SETUP


A3 -> Reset
A3.1 -> Reset Errors this menu function can be used to reset all errors that are not removed
automatically (power fail, counter overflow)
step 1: reset? no: exit the function
yes: resets the errors and exits the function.
Note:
The following reset menus for the counters (totalizer) are only available,
if the quick access has been activated in the menu setup > device >
quick setup. Each counter (totalizer) can be activated for quick access
independently.

A3.2 -> FB2 totalizer (for PROFIBUS Devices) the counter can be reset to zero in this menu
step 1: reset counter? no: exits the function without reset
yes: resets the counter and exits the function
A3.3 -> FB3 totalizer (for PROFIBUS Devices) the counter can be reset to zero in this menu
step 1: reset counter? no: exits the function without reset
yes: resets the counter and exits the function
A3.4 -> FB4 totalizer (for PROFIBUS Devices) the counter can be reset to zero in this menu
step 1: reset counter? no: exits the function without reset
yes: resets the counter and exits the function

A4 -> Station Address (only for PROFIBUS devices)


A4 -> Station Address selects the address of the device at the PROFIBUS DP interface.

Note:
The PROFIBUS address can also be changed using the PROFIBUS
service “set_slave_add”. The input range is 0...125 according to the
PROFIBUS specification. Address 126 is the default address and
cannot be set via the PROFIBUS service “set_slave_add” - use menu
instead to reset to default address.

B -> TEST
B3 -> Information
B3.5 -> PROFIBUS available if there is existing a PROFIBUS interface; displays the
information about the PROFIBUS interface mentioned below:
KROHNE Ident No.
Software Revision of the PROFIBUS software
Date of Production

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 11/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

C -> SETUP
C3 -> I/O counter
Using the menu functions mentioned below you will be able to control basically the three counters of this
PROFIBUS device (IFC300 with RS-485 and PROFIBUS-PA Profile 3.0). These three menus are
identical so they are grouped together and their functions are described simultaneously as follows.

C3.1 -> FB2 totalizer


C3.2 -> FB3 totalizer
C3.3 -> FB4 totalizer

C3.#. 1 -> function of totalizer (function select of this totalizer)

sum counter: totalizes positive and negative values


+ counter: totalizes only positive values
- counter: totalizes only negative values
hold counter: totalizer is stopped, no totalization will be done

all as positive: neg. input values will be multiplied with "-1.0"


all as negative: pos. input values will be multiplied with "-1.0"

C3.#.2 -> measurement (measurement selection for this totalizer)

volume flow
mass flow

C3.#.3 -> preset totalizer (predefines a “threshold” using the High Limit value and the Low Limit
value of the totalizer affected; the “THRESHOLD” bit will be set in the
long status information bytes of the PROFIBUS interface if the actual
value of the totalizer is outside these limits. This can be also used as a
status output choosing the function "preset counter X”

C3.#.4 -> reset totalizer (the current value of the totalizer can be set to zero)

step 1: reset totalizer? no: exits the function without reset


yes: resets the totalizer to zero and exits the
function; totalizer will restart counting at
once

C3.#.5 -> error behavior (defines the behavior of this function block in case of errors)

hold meas. value: totalization is continued based on the last


incoming value with good status before the
first occurrence of bad status
ignore error: totalization is continued using the input values
despite the bad status. The status is ignored
stop totalizer: totalization is stopped during occurrence of
bad status of incoming values

C3.#.6 -> information (the serial Number of the circuit board, the software version number and
the production date of the circuit board will be displayed)

Note: if you choose “#” = 1 all settings done will concern FB 2 (Totalizer 1)
if you choose “#” = 2 all settings done will concern FB 3 (Totalizer 2)
if you choose “#” = 3 all settings done will concern FB 4 (Totalizer 3)

C4 -> I/O PROFIBUS

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 12/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

This feature will be available for PROFIBUS devices only.

Using the menu functions mentioned below you will be able to control basically the five analogue input
blocks of this PROFIBUS device ((IFC300 with RS-485 and PROFIBUS-PA Profile 3.0). These five
menus are identical so they are grouped together and their functions are described simultaneously as
follows:

C4.1 -> FB1 analog inp.


C4.2 -> FB5 analog inp
C4.3 -> FB6 analog inp
C4.4 -> FB7 analog inp
C4.5 -> FB8 analog inp

C4.#. 1 -> measurement (selects the measurement (channel) for the analogue input block for the
PROFIBUS interface)

flow speed:
volume flow:
mass flow:
coil temperature:
conductivity:
temperature: this is the electronic temperature
supply: the internal supply voltage for the PROFIBUS
interface

C4.#. 2 -> time constant (time constant for this function block)

C4.#.3 -> error behavior (defines the behavior of this function block in case of errors)

hold value: last valid OUT value stored will be used as


OUT value
ignore error: OUT has the wrong calculated value and
status Bad as calculated
replace value: the “replacement value” will be used as OUT
value
C4.#.4 -> replacement value (available, if the error behavior "replace value" is selected. Defines
the value that replaces the measured value at this function block in
case of an error)

Note: if you choose “#” = 1 all settings done will concern FB 1 (Analog Inp.1)
if you choose “#” = 2 all settings done will concern FB 5 (Analog Inp.2)
if you choose “#” = 3 all settings done will concern FB 6 (Analog Inp.3)
if you choose “#” = 4 all settings done will concern FB 7 (Analog Inp.4)
if you choose “#” = 5 all settings done will concern FB 8 (Analog Inp.5)

C5 -> Device
In this menu all functions are grouped that have no effect on the measurement or any output directly.

C5.3 -> 1. meas. page

Here are all settings for the first measurement.

C5.3.1 -> function


two lines: display shows two lines of measurement on
this page

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 13/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

three lines: display shows three lines of measurement on


this page
one line: display shows one line of measurement on
this page

C5.3.2 -> measurement 1.line

flow speed:
volume flow:
mass flow:
coil temperature:
conductivity:
diagnosis value:

C5.3.8 -> measurement 2.line (only available if this line is activated)


bargraph: analogue display of the value selected for the
first line
flow speed:
volume flow:
mass flow:
coil temperature:
conductivity:
diagnosis value:

FB2 totalizer:
FB3 totalizer:
FB4 totalizer:

operating hours:

C5.3.10 measurement 3.line (only available if this line is activated)

flow speed:
volume flow:
mass flow:
coil temperature:
conductivity:
diagnosis value:

FB2 totalizer:
FB3 totalizer:
FB4 totalizer:

operating hours:

C5.4 -> 2. meas. page

In case of a PROFIBUS device the second measurement page is meant to check the output
values of the different function blocks. Only PROFIBUS values can be selected here. The
analogue inputs are shown with exactly the value, seen on the PROFIBUS.

C5.4.1 -> measurement 1.line

FB1 analog inp.:


FB2 totalizer 1:
FB3 totalizer 2:
FB4 totalizer 3:
FB5 analog inp.:
FB6 analog inp
FB7 analog inp.:

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 14/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

FB8 analog inp.:

C5.4.2 -> format 1.line (fixed number of digits after the decimal point or automatic, where the
number of digits is automatically adjusted to the available space)

C5.4.3 -> measurement 2.line

FB1 analog inp.:


FB2 totalizer 1:
FB3 totalizer 2:
FB4 totalizer 3:
FB5 analog inp.:
FB6 analog inp.:
FB7 analog inp.:
FB8 analog inp.:

C5.4.4 -> format 2.line (fixed number of digits after the decimal point or automatic, where the
number of digits is automatically adjusted to the available space)

C5.4.5 -> measurement 3.line

FB1 analog inp.:


FB2 totalizer 1:
FB3 totalizer 2:
FB4 totalizer 3:
FB5 analog inp.:
FB6 analog inp.:
FB7 analog inp.:
FB8 analog inp.:

C5.4.6 -> format 3.line (fixed number of digits after the decimal point or automatic, where the
number of digits is automatically adjusted according to the available
space)

C5.6 -> special functions

C5.6.1 -> reset errors (this menu function can be used to reset all errors, that are not removed
automatically (e.g. power fail))

step 1: reset: no: exit the function


yes: resets the errors and exits the function.

C5.6.2 -> save settings (in this menu all settings can be saved in different storage places)

step 1: save settings:


break (exit the menu without saving)
backup 1 (saves the settings in the backup 1
storage place)
backup 2 (saves the settings in the backup " storage
place)
step 2: go on with copy? (Note: There is no possibility to undo this
command!)
no: exit function without saving
yes: copy the actual settings to the selected storage
place and exits the function.

Note: PROFIBUS interface settings will not be saved.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 15/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

C5.6.3 -> load settings (in this menu all settings can be loaded from different storage places,
where settings have been saved before)

step 1: load settings:


break (exits the menu without loading)
factory settings (loads the settings from the delivery)
backup 1 (loads the settings from the backup 1
storage place)
backup 2 (loads the settings from the backup 2
storage place)
step 2: go on with copy? (Note: There is no possibility to undo this
command!)
no: (exit function without saving)
yes: (copy the actual settings to the selected
storage place and exits the function)

Note: PROFIBUS interface settings will not be loaded.

C5.8 -> physical block

This menu is only available, if a PROFIBUS interface is present.

C5.8.1 -> station address (selects the PROFIBUS station address of the device)

Note: The PROFIBUS address can also be changed using the


PROFIBUS service “set_slave_add”. The input range is 0...125
according to the PROFIBUS specification. Address 126 is the default
address and cannot be set via the PROFIBUS service “set_slave_add” -
use menu instead to reset to default address.

C5.9 -> quick setup

In this menu some settings in the Quick Setup can be activated. In the default configuration the
settings in the Quick Setup are activated.

C5.9.1 -> reset counter 1 (the reset can be activated in the Quick Setup to get a quick access of
the function)
yes: quick access activated
no: quick access not activated

C5.9.2 -> reset counter 2 (the reset can be activated in the Quick Setup to get a quick access of
the function)
yes: quick access activated
no: quick access not activated

C5.9.3 -> reset counter 3 8the reset can be activated in the Quick Setup to get a quick access of
the function)
yes: quick access activated
no: quick access not activated

D -> SERVICE
This menu is in any case only to be entered by a password. This password can also be entered, when a
password for setup or quick setup is asked for. Thus this password can also be used to change forgotten
passwords.

D2 -> service parameters


In this menu all functions related to different data sets can be found.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 16/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

D2.1 -> cold start (a reset of the IFC300 can be done here, all actual changes up to this
moment are automatically stored and no undo is possible any more, this
function is helpful to reset an F error)

step 1: reset? no: terminates the function


yes: performs the reset and leaves the programming
mode

D2.1 -> save factory data (copies the actual data into the factory setting, this overwrites the factory
settings done during calibration)

step 1: save settings


break: exits the menu without saving
factory settings: saves the settings as factory
settings
step 2: go on with copy? (there is no possibility to undo this command)
no: exit menu without saving
yes: copy the actual settings to the selected storage
place.

D2.9 -> Identification No. (sets a different device modes for the cyclic communication of the
PROFIBUS interface)

IFC090: compatibility mode for the IFC300 used for replacing


the IFC090
IFC300: the normal setting (all manufacturer specific
parameters supported)

Profile: uses only the profile defined functions - no extras


(profile specific parameters supported only)

D2.10 -> PB cold start (initiates a PROFIBUS cold start)

reset? no: terminates the function


yes: PROFIBUS cold start will be carried out at once;
the programming mode is terminated

Note: during a PROFIBUS cold start nearly all


parameter values of the whole device will be
set to their default values (the PROFIBUS
address will not be changed) without
disconnecting an already established
connection to a PROFIBUS Master system

6.1 Using the display menu to distinguish the current revision of the device

Use the display of the “IFC300 with PROFIBUS MBP Interface” to open the path:
“test\information\Profibus” ( == menu B3.5)

This menu will provide the following information:

KROHNE Ident No.


Software Revision of the PROFIBUS software
Date of Production

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 17/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

7 Technical Data

Hardware Software

Physical IEC 61158-2; 31,25kbit/s; GSD GSD file can be downloaded from the KROHNE Homepage
voltage mode http://www.krohne.com
Connection independent of polarity Device profile PA Profile compact class B, V3.0
Base current 10,5 mA Address range 0...126; default 126

0 to 125 via “set_slave_add”


0 to 126 via “Local Display”
126 via “FACTORY_RESET = 2712”

FDE yes: separate fault disconnection Local control local display and operator interface at device.
electronics provided
Fault current 6 mA; (fault current = max. SAPs 2 MS1 SAPs - acyclic interface to PLC
continuous current – base current).
3 MS2 SAPs - the number of MS2 ServiceAccess Points is typically
equal to the maximum number of master class 2
tools
Starting current < 12mA Function Blocks 1 PB
1 TB
5 AI
“Ex“ approval EEx ia IIC or EEx ib IIC/IIB,
3 TOT
FISCO device
(details see “IFC 300 (OPTIFLUX)
Handbook”

8 Device Description for the SIMATIC Process Device Manager (PDM)

8.1 Installation
If the IFC 300 Device Description is not already installed on the PDM System a so called Device Install IFC 300
PROFIBUS-PA PDM is needed (available as download from KROHNE ‘Download Centre’ on the internet or on CD-
ROM / floppy disk from KROHNE).
For installing the DD on PDM V 5.2 refer to the “PDM Manual” section 11.2:”Device Install / Integrating Devices in
SIMATIC PDM with 'Device Install'".
For installing the DD on PDM V 6.0 refer to the “PDM Manual” section 13:”Integrating Devices”.
Please read also the “readme.txt”, which is also contained in the Device Install.

8.2 Operating
Refer to the IFC 300 Menu Tree PDM (Attachment A).
Due to PROFIBUS and PDM requirements and conventions the IFC 300 operation differs from operation via local
keypad and the following special features should be kept in mind:.

• The online help of those parameters which are accessible at the device's display menu contain the function
number as a reference to the menu position.
• If the device is operated via its local keypad no write operation can be performed via the PROFIBUS interface at
the same time.
• In order to find out whether the setting of the device is still the same as the parameter set stored in PDM
compare the ‘Static Revision No.’ of the respective PROFIBUS Block. (The current Static Revision No. is
displayed on the window ‘View / Device Status / <block name>’).

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 18/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

9 Attachmnet A

IFC 300 Menu Tree PDM


Menu Bar
1

File Device View Options Help

Measured Values
Display
coil temperature
volume flow • coil temperature electronics temperature
• volume flow • coil temperature status • electronics temperature
• volume flow status conductivity • electronics temp. status
mass flow • conductivity supply voltage
• mass flow • conductivity status • supply voltage
• mass flow status flow speed • supply voltage status
• flow speed
• flow speed status
-----------------------------------

Y t Diagram
Y t Diagram • volume flow
• mass flow

Overview Opt
• FB1: Output value • Quality • Simulation • Actual Mode
• ... ... ... ...
Function Block Outputs • FB8: Output value • Quality • Simulation • Actual Mode

FB8: AI- channel Opt FB4: TOT-channel Opt


FB7: AI- channel Opt FB3: TOT-channel Opt
FB6: AI- channel Opt
FB5: AI- channel Opt FB2: TOT-channel
FB1: AI-channel • Channel
• Channel
• Bargraph Output AI Output TOT
• Output Value
Output AI • Quality
• Output Value • Status
• Quality
• Status

Simulation
• Simulation
• Actual Mode
Overview Opt
Overview Opt • FB1: Current State Alarm Sum
Alarm States FB1: AI-channel • ...
FB2: TOT- channel • FB8: Current State Alarm Sum
Device Status FB3: TOT- channel Opt
3 FB4: TOT- channel Opt
Circuit Board Info
FB5: AI- channel Opt Lower Limit Alarm
-----------------------------------
Toolbar FB6: AI- channel Opt
Lower Limit Warning
Status Bar FB7: AI- channel Opt
----------------------------------- FB8: AI- channel Opt Upper Limit Warning
Update
Alarm Summary Upper Limit Alarm
• Current State Alarm Sum • Unacknowledged Alarms
Designations:
Opt Optional, dependent on device
• Unreported St. Al. Sum • Status
• Cause
implementation / configuration
Rd Read-only
• Upper Limit Alarm
Loc Local PDM, affects only PDM views
• Alarm Output Value

KROHNE IFC300 PA 45000002 (2/5)


02.06
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 19/23
Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

IFC 300 Menu Tree PDM


Menu Bar
1

File Device View Options Help

Display
General Details Details (Service) Opt
-----------------------------------
Y t Diagram
2 • Tag • C number Unm. Diagnosis Opt
Function Block Outputs
• Manufacturer • Firmware Ident Number • Manufacturer Ident No.
Alarm States
• Product Designation • Station Address Diagnosis
• Device Variant • Operating Time
• Device Serial Number • EEPROM Cycles
• Software Revision • PROFIBUS Interface IFC 090 Mode Opt
• Hardware Revision Revision
Device Status Unm. Diagnosis Opt
• Installation Date • GDC Interface Revision
• PROFIBUS Ident No. • Diagnosis Extension 1 • Manufacturer Ident No
• Parameter Protection • Diagnosis Extension 2 Diagnosis
• Diagnosis
Messages on Device’s GDC Long Status Opt
Display
• errors • LS0 Long Status • LS0 No. of New Values
• application • ... • ...
• out of specification • LS10 Long Status • LS10 No. of New Values
• checks
• information

Block Overview Opt


• PB: Tag • Static Rev. Counter • Actual Mode
• TB: Tag ... ...
• FB1: Tag • Channel • Simulation
• ... ... ...
• FB8: Tag • Channel • Static Rev. Counter • Actual Mode • Simulation

FB4: AI-channel Opt

FB2: AI-channel FB5: TOT-channel Opt


Transducer Block
FB1: AI-channel FB3: TOT-channel
Physical Block • Tag • Tag
• Tag • Static Revision No. • Static Revision No.
• Static Revision No. • Simulation • Actual Mode
• Actual Mode • Actual Mode

Circuit Board Info Display / IO1 Profibus module


----------------------------------- • ident no. • ident no.
Toolbar • index • index
Status Bar • hardware id • hardware id
----------------------------------- • software version • software version
Update • production date • production date
• calibration date • calibration date
Designations: • board serial no. • board serial no.
Opt Optional, dependent on device

implementation / configuration
Rd Read-only

Loc Local PDM, affects only PDM views

KROHNE IFC300 PA 45000002 (3/5)


02.06

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 20/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

IFC 300 Menu Tree PDM


Parameter Table

Identification Identification Calibration


• zero point offset Rd
Operation Unit Operation Unit
• size entry Opt
• Tag • size
Device
• Descriptor
• GK selection
----------------------------------- • Message
• GK
Mask Bits for Diagnosis Opt • GKL
Device • coil resistance Rsp
Mask Bits for IFC 090 • Manufacturer Rd • density
Diagnosis Opt • Product Designation Rd • target conductivity
• Device Serial Number Rd • number of electrodes
-----------------------------------
• Software Revision Rd • field frequency
Input • Hardware Revision Rd • select settling
• Profile Revision Rd • settling time Opt
Measuring Limits
• Static Revision Number Rd • line frequency
Calibration • PROFIBUS Ident Number
• Installation Date Filter Process Input
Filter Process Input
• Write Locking Rd • limitation min
Self Test • Parameter Protection Rd • limitation max
• Device Type Rd • flow direction
Information
• C number Rd • time constant
----------------------------------- • Firmware Ident Number Rd • pulse filter
• PROFIBUS Interface Rev. Rd • pulse width Opt
Output
• GDC Interface Rev. Rd • pulse limitation Opt
FB1: AI-channel • Warm Start Timeout Opt • noise filter
• Warm Start Timeout Max Opt • noise level Opt
FB2: TOT- channel
• noise suppression Opt
FB3: TOT- channel Opt • lfc threshold
Input • lfc hysteresis
FB4: TOT- channel Opt
5 • Tag
FB5: AI- channel Opt • Static Revision No. Rd Self Test
• Gain Compensation Factor Rd • empty pipe
FB6: AI- channel Opt
• Low Flow Cut Off • limit empty pipe Opt
FB7: AI- channel Opt • Low Flow Cut Off Hysteresis • full pipe Opt
• Sample Rate Rd • limit full pipe Opt
FB8: AI- channel Opt
• Mode • linearity
----------------------------------- • Flow Direction • gain
• coil current
Mechanical Construction Measuring Limits • flow profile
Process Connection volume flow • limit flow profile Opt
• Unit • electrode noise
-----------------------------------
• Lower Value Min Rd • limit electrode noise Opt
Human Interface • Upper Value Max Rd • settling of field
mass flow
Local Display Information
• ...
coil temperature • liner
• ... • electrode material
conductivity • serial no. sensor Rd
• ... • V no. sensor Rd
flow speed
• ...
electronics temperature
• ...
supply voltage
Designations: • ...
Opt
Optional, dependent on device density
implementation / configuration • ...
Rd Read-only
Loc
Local PDM, KROHNE IFC300 PA 45000002 (4/5)
affects only PDM views 02.06

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 21/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

IFC 300 Menu Tree PDM


Parameter Table

FB8: AI-channel Opt FB4: TOT-channel Opt


Identification FB7: AI-channel Opt FB3: TOT-channel Opt
Operation Unit 4 Opt
FB6: AI-channel FB2: TOT-channel
Device Opt
• Tag
FB5: AI-channel
• Static Revision No. Rd
-----------------------------------
FB1: AI-channel • Channel
Mask Bits for Diagnosis Opt • Tag • Unit
• Static Revision No. Rd • Strategy
Mask Bits for IFC 090
• Channel • Alert Key
Diagnosis Opt
• Unit
----------------------------------- • Out Unit Text Batch Information
• Filter Time Constant • Batch ID
Input • Batch Unit
• Strategy
Measuring Limits • Alert Key • Batch Operation
• Batch Phase
Calibration Batch Information
Filter Process Input 4 • Batch ID Totalizer Settings
• Batch Unit • Totalizer Value
Self Test • Batch Operation • Mode
Information • Batch Phase • Fail Safe Mode
• Preset Value
----------------------------------- Process Value Scale • History Control
Output • Lower Value
• Upper Value Output Limits
FB1: AI-channel • Lower Limit Alarm
FB2: TOT- channel Output Scale • Lower Limit Warning
• Lower Value • Upper Limit Warning
FB3: TOT- channel Opt • Upper Value • Upper Limit Alarm
FB4: TOT- channel Opt • Limit Hysteresis
Output Limits
FB5: AI- channel Opt • Lower Limit Alarm
FB6: AI- channel Opt • Lower Limit Warning
• Upper Limit Warning
FB7: AI- channel Opt • Upper Limit Alarm
FB8: AI- channel Opt • Limit Hysteresis

Fail Safe Mode


• Fail Safe Mode
• Fail Safe Default Value

Human Interface
• Decimal Point
-----------------------------------
Mechanical Construction Mechanical Construction Human Interface
Process Connection Process Connection • Overview Views Loc
• Nominal Size Rd • Check serial no. sensor Loc
-----------------------------------
• Write sensor parameters Loc
Human Interface 1. measurement page
Local Display • display 1. line Rd
• display 2. line Rd
• display 3. line Rd
2. measurement page
• display 1. line
Designations:
Opt • display 2. line
Optional, dependent on device
• display 3. line
implementation / configuration
Rd Read-only
Loc
Local PDM, KROHNE IFC300 PA 45000002 (5/5)
affects only PDM views 02.06

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 22/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de
Supplementary Installation and Operating Instructions
(IFC300 PROFIBUS MBP Interface with PA Profile 3.0)

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg 23/23


Tel.: 0203-301 0 ‚ Fax: 0203-301 389 · e-mail: krohne@krohne.de

You might also like