You are on page 1of 35

– Mini VRF System Air Conditioner –

INSTALLATION INSTRUCTIONS for Refrigerant R410A EN


– Climatiseur Système Mini-VRF –
INSTRUCTIONS D’INSTALLATION pour réfrigérant R410A

– Mini VRF System-Klimaanlage – FR


EINBAUANLEITUNG für Kühlmittel R410A

– Condizionatore d’aria VRF Mini –


ISTRUZIONI PER L’INSTALLAZIONE per refrigerante R410A
DE
– Sistema de Ar Condicionado Mini VRF –
INSTRUÇÕES DE INSTALAÇÃO para Refrigerante R410A

– Κλιματιστικό σύστημα Mini VRF –


ΟΔΗΓΙΕΣ ΤΟΠΟΘΕΤΗΣΗΣ για το ψυκτικό R410A IT
– Acondicionador de aire del sistema Mini VRF –
INSTRUCCIONES DE INSTALACIÓN para refrigerante R410A

– Mini VRF Systeem Airconditioner – PT


INSTALLATIE-INSTRUCTIES voor koelmiddel R410A

– Климатик мини система VRF –


ИНСТРУКЦИИ ЗА МОНТАЖ за хладилен агент R410A
GR
– Кондиционер системы Mini VRF –
ИНСТРУКЦИИ ПО УСТАНОВКЕ для хладагента R410A

– Система кондиціювання повітря Mini VRF –


ВКАЗІВКИ ЩОДО ВСТАНОВЛЕННЯ для охолоджувача R410A ES

Outdoor Units
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8 NL
Unités extérieures
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8
Außeneinheiten
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8
Unità esterne BL
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8
Unidades exteriores
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8
Εξωτερικές Μονάδες
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8 RU
Unidades exteriores
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8
Buiteneenheden
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8
Външни модули UK
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8
Внешние блоки
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8
Ззовнішні агрегати
U-4LE1E5, U-5LE1E5, U-6LE1E5, U-4LE1E8, U-5LE1E8, U-6LE1E8

85464369493021 2011

Mini_VRF_Cover.indd 3 2011/09/06 9:29:22


INSTALLATION INSTRUCTIONS
– Mini VRF System Air Conditioner –
for Refrigerant R410A

■ R410A Models
Model No.
Outdoor Units
4 hp 5 hp 6 hp
U-4LE1E5 U-5LE1E5 U-6LE1E5
U-4LE1E8 U-5LE1E8 U-6LE1E8
* Refrigerant R410A is used in the outdoor units.
hp = horsepower
Indoor Units
Indoor Unit Type 22 28 36 45 56
D1 1-Way Cassette S-28MD1E5 S-36MD1E5 S-45MD1E5 S-56MD1E5
L1 2-Way Cassette S-22ML1E5 S-28ML1E5 S-36ML1E5 S-45ML1E5 S-56ML1E5
U1 4-Way Cassette S-22MU1E5 S-28MU1E5 S-36MU1E5 S-45MU1E5 S-56MU1E5
Y1 4-Way Cassette 60 × 60 S-22MY1E5 S-28MY1E5 S-36MY1E5 S-45MY1E5 S-56MY1E5
K1 Wall-Mounted S-22MK1E5 S-28MK1E5 S-36MK1E5 S-45MK1E5 S-56MK1E5
T1 Ceiling S-36MT1E5 S-45MT1E5 S-56MT1E5
F1 Low Silhouette Ducted S-22MF1E5 S-28MF1E5 S-36MF1E5 S-45MF1E5 S-56MF1E5
M1 Slim Low Static Ducted S-22MM1E5 S-28MM1E5 S-36MM1E5 S-45MM1E5 S-56MM1E5
E1 High Static Pressure Ducted
P1 Floor Standing S-22MP1E5 S-28MP1E5 S-36MP1E5 S-45MP1E5 S-56MP1E5
R1 Concealed Floor Standing S-22MR1E5 S-28MR1E5 S-36MR1E5 S-45MR1E5 S-56MR1E5

Indoor Unit Type 73 90 106 140 160


D1 1-Way Cassette S-73MD1E5
L1 2-Way Cassette S-73ML1E5
U1 4-Way Cassette S-73MU1E5 S-106MU1E5 S-140MU1E5 S-160MU1E5
Y1 4-Way Cassette 60 × 60
K1 Wall-Mounted S-73MK1E5 S-106MK1E5
T1 Ceiling S-73MT1E5 S-106MT1E5 S-140MT1E5
F1 Low Silhouette Ducted S-73MF1E5 S-90MF1E5 S-106MF1E5 S-140MF1E5 S-160MF1E5
M1 Slim Low Static Ducted
E1 High Static Pressure Ducted S-73ME1E5 S-106ME1E5 S-140ME1E5
P1 Floor Standing S-71MP1E5
R1 Concealed Floor Standing S-71MR1E5

Mini_VRF_eng.indd 1 2011/08/26 13:45:10


IMPORTANT!
SPECIAL PRECAUTIONS
Please Read Before Starting
This air conditioner must be installed by the sales dealer WARNING When Wiring
or installer.
This information is provided for use only by authorized ELECTRICAL SHOCK CAN CAUSE
persons. SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
For safe installation and trouble-free operation, you must:
ELECTRICIAN SHOULD ATTEMPT TO
● Carefully read this instruction booklet before beginning. WIRE THIS SYSTEM.
● Follow each installation or repair step exactly as shown. • Do not supply power to the unit until all wiring and tubing
● This air conditioner shall be installed in accordance with are completed or reconnected and checked.
National Wiring Regulations. • Highly dangerous electrical voltages are used in this
● This product is intended for professional use. system.
Permission from the power supplier is required when Carefully refer to the wiring diagram and these
installing the U-4LE1E8, U-5LE1E8, U-6LE1E8, instructions when wiring. Improper connections and
outdoor units that are connected to a 16 A distribution inadequate grounding can cause accidental injury or
network. death.
● This equipment complies with EN/IEC 61000-3-12 • Connect all wiring tightly. Loose wiring may cause
provided that the short-circuit power Ssc is greater overheating at connection points and a possible fire
than or equal to the following table at the interface point hazard.
between the user’s supply and the public system. • Provide a power outlet to be used exclusively for each
It is the responsibility of the installer or user of unit.
the equipment to ensure, by consultation with the
distribution network operator if necessary, that the • ELCB must be incorporated in the fixed wiring.
equipment is connected only to a supply with a short- Circuit breaker must be incorporated in the fixed wiring
circuit power Ssc greater than or equal to the value in in accordance with the wiring regulations.
the table. U-4LE1E5 U-5LE1E5 U-6LE1E5
U-4LE1E5 U-5LE1E5 U-6LE1E5 Circuit breaker 30 A 40 A 40 A
Ssc 350 kVA 400 kVA 550 kVA U-4LE1E8 U-5LE1E8 U-6LE1E8
● This equipment complies with EN/IEC 61000-3-11 Circuit breaker 20 A 20 A 20 A
provided that the system impedance Zmax is less than • Provide a power outlet exclusively for each unit, and
or equal to the values corresponding to each model as full disconnection means having a contact separation
shown in the table below at the interface point between in all poles must be incorporated in the fixed wiring in
the user’s supply and the public system. Consult with accordance with the wiring rules.
the supply authority for the system impedance Zmax.
• To prevent possible hazards from insulation failure,
U-4LE1E5 U-5LE1E5 U-6LE1E5 the unit must be grounded.
Zmax 0.298 Ω 0.298 Ω 0.298 Ω
When Transporting
● Pay close attention to all warning and caution notices
given in this manual. Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
This symbol refers to a hazard or unsafe when lifting to reduce strain on your back. Sharp edges
WARNING practice which can result in severe or thin aluminum fins on the air conditioner can cut your
personal injury or death. fingers.
This symbol refers to a hazard or unsafe
CAUTION practice which can result in personal injury
or product or property damage.

If Necessary, Get Help


These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.

In Case of Improper Installation


The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.

Mini_VRF_eng.indd 2 2011/08/26 13:45:10


When Installing… Handle liquid refrigerant carefully as it may cause
frostbite.
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location When Servicing
for easy maintenance.
• Turn the power OFF at the main power box
…In a Room (mains) before opening the unit to check or repair
Properly insulate any tubing run inside a room to prevent electrical parts and wiring.
“sweating” that can cause dripping and water damage to • Keep your fingers and clothing away from any moving
walls and floors. parts.
Keep the fire alarm and the air outlet at least • Clean up the site after you finish, remembering to
CAUTION
1.5 m away from the unit. check that no metal scraps or bits of wiring have been
…In Moist or Uneven Locations left inside the unit being serviced.
Use a raised concrete pad or concrete blocks to provide • Do not clean inside the indoor and
a solid, level foundation for the outdoor unit. This outdoor units by users. Engage
prevents water damage and abnormal vibration. WARNING authorized dealer or specialist for
…In an Area with High Winds cleaning.
Securely anchor the outdoor unit down with bolts and a • In case of malfunction of this
metal frame. Provide a suitable air baffle. appliance, do not repair by yourself.
…In a Snowy Area (for Heat Pump-type Systems) Contact the sales dealer or service
Install the outdoor unit on a raised platform that is higher dealer for repair.
than drifting snow. Provide snow vents. • Do not touch the air inlet or the
sharp aluminum fins of the
When Connecting Refrigerant Tubing CAUTION outdoor unit. You may get injured.
• When performing piping work do not • Ventilate any enclosed areas when
mix air except for specifIed refrigerant installing or testing the refrigeration
(R410A) in refrigeration cycle. It system. Escaped refrigerant gas, on
causes capacity down, and risk of contact with fire or heat, can produce
explosion and injury due to high dangerously toxic gas.
tension inside the refrigerant cycle. • Confirm after installation that no
WARNING
• Refrigerant gas leakage may cause refrigerant gas is leaking. If the gas
fire. comes in contact with a burning stove,
• Do not add or replace refrigerant gas water heater, electric room heater
or other heat source, it can cause the
other than specified type. It may
generation of poisonous gas.
cause product damage, burst and
injury, etc. Others
• Ventilate the room well, in the event that is refrigerant
• Do not touch the air inlet or
gas leaks during the installation. Be careful not to allow CAUTION the sharp aluminum fins of the
contact of the refrigerant gas with a flame as this will
outdoor unit. You may get injured.
cause the generation of poisonous gas.
• Do not sit or step on the unit,
• Keep all tubing runs as short as possible. you may fall down accidentally.
• Use the flare method for connecting tubing. • Do not stick any object into
• Apply refrigerant lubricant to the matching surfaces of the FAN CASE.
the flare and union tubes before connecting them, then You may be injured and the
tighten the nut with a torque wrench for a leak-free unit may be damaged.
connection.
• Check carefully for leaks before starting the test run. NOTICE
• Do not leak refrigerant while piping work for an The English text is the original instructions. Other
installation or re-installation, and while repairing languages are translations of the original instructions.
refrigeration parts.

Mini_VRF_eng.indd 3 2011/08/26 13:45:10


Check of Density Limit 2. The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
The room in which the air conditioner is to be installed
requires a design that in the event of refrigerant gas
leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air conditioner,
is safe, without the toxicity or combustibility of ammonia, and
is not restricted by laws imposed to protect the ozone layer.
However, since it contains more than air, it poses the risk of
(2) When there is an effective opening with the adjacent room
suffocation if its density should rise excessively. Suffocation
for ventilation of leaking refrigerant gas (opening without
from leakage of refrigerant is almost non-existent. With the
a door, or an opening 0.15% or larger than the respective
recent increase in the number of high density buildings,
floor spaces at the top or bottom of the door).
however, the installation of multi air conditioner systems is
on the increase because of the need for effective use of floor Outdoor unit
space, individual control, energy conservation by curtailing heat Refrigerant tubing
and carrying power, etc.
Most importantly, the multi air conditioner system is able Indoor unit
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of the
multi air conditioner system is to be installed in a small room,
select a suitable model and installation procedure so that if the
(3) If an indoor unit is installed in each partitioned room and
refrigerant accidentally leaks out, its density does not reach the
the refrigerant tubing is interconnected, the smallest room
limit (and in the event of an emergency, measures can be made
of course becomes the object. But when mechanical
before injury can occur).
ventilation is installed interlocked with a gas leakage
In a room where the density may exceed the limit, create an detector in the smallest room where the density limit is
opening with adjacent rooms, or install mechanical ventilation exceeded, the volume of the next smallest room becomes
combined with a gas leak detection device. The density is as the object.
given below. Refrigerant tubing
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
< Density limit (kg/m3) Outdoor unit
The density limit of refrigerant which is used in multi air Very
conditioners is 0.3 kg/m3 (ISO 5149). small
Indoor unit
room
Small Medium Large room
NOTE
room room
1. If there are 2 or more refrigerating systems in a single
refrigerating device, the amount of refrigerant should be as
charged in each independent device. Mechanical ventilation device – Gas leak detector
For the amount of charge in this example:
Outdoor unit 3. The minimum indoor floor space compared with the
e.g., charged
amount (10 kg) amount of refrigerant is roughly as follows: (When the
e.g., charged
amount (15 kg) ceiling is 2.7 m high)
m2 m3
125 337.5
120 324.0
Indoor unit 115 310.5
110 297.0
105 283.5
100 270.0
(when the ceiling is 2.7 m high)

95 256.0
Room A Room B Room C Room D Room E Room F 90 243.0
85 229.5 Range below the
density limit of
Min. indoor volume

The possible amount of leaked refrigerant gas in rooms A, 80 216.0


Min. indoor floor area

75 202.5 0.3 kg/m³


B and C is 10 kg. (Countermeasures
70 189.0 not needed)
The possible amount of leaked refrigerant gas in rooms D, 65 175.5
E and F is 15 kg. 60 162.0
55 148.5
50 135.0 Range above the
45 121.5 density limit of
0.3 kg/m³
40 108.0
(Countermeasures
35 94.5 needed)
30 81.0
25 67.5
20 54.0
15 40.5
10 27.0
5 13.5
0 0.0
0 10 20 30 40 50 60 70 80 90 100 kg
Total amount of refrigerant

Mini_VRF_eng.indd 4 2011/08/26 13:45:10


Precautions for Installation Using New R407C
tools
Refrigerant Item
New
compatible Remarks
tool?
with
1. Care regarding tubing
R410A?
1-1. Process tubing
Manifold Yes No Types of refrigerant,
● Material: Use C1220 phosphorous deoxidized copper gauge refrigerating machine oil,
specified in JIS H3300 “Copper and Copper Alloy Seamless and pressure gauge are
Pipes and Tubes”. different.
● Tubing size: Be sure to use the sizes indicated in the
Charge Yes No To resist higher pressure,
table below.
hose material must be changed.
● Use a tube cutter when cutting the tubing, and be sure to
remove any flash. This also applies to distribution joints Vacuum Yes Yes Use a conventional vacuum
(optional). pump pump if it is equipped with
a check valve. If it has no
● When bending tubing, use a bending radius that is 4 times check valve, purchase and
the outer diameter of the tubing or larger. attach a vacuum pump
adapter.
CAUTION
Leak Yes No Leak detectors for CFC
Use sufficient care in handling the tubing. Seal the tubing ends
detector and HCFC that react to
with caps or tape to prevent dirt, moisture, or other foreign
chlorine do not function
substances from entering. These substances can result in
because R410A contains
system malfunction.
no chlorine. Leak detectors
Unit: mm for HFC134a can be used
Material O for R410A.
Copper Outer diameter 6.35 9.52 12.7 15.88 19.05 Flaring oil Yes No For systems that use R22,
tube apply mineral oil (Suniso
Wall thickness 0.8 0.8 0.8 1.0 1.2
oil) to the flare nuts on the
tubing to prevent refrigerant
1-2. Prevent impurities including water, dust and oxide from leakage. For machines
entering the tubing. Impurities can cause R410A refrigerant that use R407C or R410A,
deterioration and compressor defects. Due to the features apply synthetic oil (ether
of the refrigerant and refrigerating machine oil, the oil) to the flare nuts.
prevention of water and other impurities becomes more * Using tools for R22 and R407C and new tools for R410A
important than ever. together can cause defects.
2. Be sure to recharge the refrigerant only in liquid form. Manifold gauge Vacuum pump

2-1. Since R410A is a non-azeotrope, recharging the refrigerant Outlet


in gas form can lower performance and cause defects of Inlet
the unit.
2-2. Since refrigerant composition changes and performance
decreases when gas leaks, collect the remaining
refrigerant and recharge the required total amount of new
refrigerant after fixing the leak.

3. Different tools required


3-1. Tool specifications have been changed due to the
characteristics of R410A. 3-2. Use R410A exclusive cylinder only.
Some tools for R22- and R407C-type refrigerant systems Single-outlet valve
cannot be used. (with siphon tube) Valve
Liquid refrigerant should be
recharged with the cylinder
standing on end as shown.

Liquid

Mini_VRF_eng.indd 5 2011/08/26 13:45:10


CONTENTS
Page Page

IMPORTANT! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 5. HOW TO PROCESS TUBING . . . . . . . . . . . . . . . . . . . . . 20


Please Read Before Starting 5-1. Connecting the Refrigerant Tubing
Check of Density Limit 5-2. Connecting Tubing Between Indoor and Outdoor
Precautions for Installation Using New Refrigerant Units
5-3. Insulating the Refrigerant Tubing
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 5-4. Taping the Tubes
1-1. Tools Required for Installation (not supplied)
5-5. Finishing the Installation
1-2. Accessories Supplied with Outdoor Unit
1-3. Type of Copper Tube and Insulation Material 6. AIR PURGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1-4. Additional Materials Required for Installation
■ Air Purging with a Vacuum Pump (for Test Run) Preparation
1-5. Tubing Size
1-6. Straight Equivalent Length of Joints 7. TEST RUN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1-7. Additional Refrigerant Charge 7-1. Preparing for Test Run
1-8. System Limitations 7-2. Test Run Procedure
1-9. Tubing Length 7-3. Outdoor Unit PCB Setting
1-10. Check of Limit Density 7-4. Auto Address Setting
1-11. Installing Distribution Joint 7-5. Caution for Pump Down
1-12. Optional Distribution Joint Kit 7-6. Meaning of Alarm Messages
1-13. Example of Tubing Size Selection and Refrigerant
Charge Amount 8. MARKINGS FOR DIRECTIVE 97/23/EC (PED) . . . . . . . . 33

2. SELECTING THE INSTALLATION SITE . . . . . . . . . . . . . 11


2-1. Outdoor Unit
2-2. Air-Discharge Chamber for Top Discharge
2-3. Installing the Unit in Heavy Snow Areas
2-4. Precautions for Installation in Heavy Snow Areas
2-5. Dimensions of Air-Discharge Chamber
2-6. Dimensions of Snow-Proof Vents

3. HOW TO INSTALL THE OUTDOOR UNIT . . . . . . . . . . . . 16


3-1. Installing the Outdoor Unit
3-2. Drainage Work
3-3. Routing the Tubing and Wiring

4. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4-1. General Precautions on Wiring
4-2. Recommended Wire Length and Wire Diameter for
Power Supply System
4-3. Wiring System Diagrams

Mini_VRF_eng.indd 6 2011/08/26 13:45:11


1. GENERAL 1-4. Additional Materials Required for Installation
This booklet briefly outlines where and how to install the 1. Refrigeration (armored) tape
air conditioning system. Please read over the entire set of 2. Insulated staples or clamps for connecting wire (See your
instructions for the indoor and outdoor units and make sure all local codes.)
accessory parts listed are with the system before beginning.
3. Putty
1-1. Tools Required for Installation (not supplied) 4. Refrigeration tubing lubricant
1. Flathead screwdriver 5. Clamps or saddles to secure refrigerant tubing
2. Phillips head screwdriver 6. Scale for weighing
3. Knife or wire stripper
1-5. Tubing Size
4. Tape measure
Table 1-2 Main Tubing Size (LA)
5. Carpenter’s level
4 hp 5 hp 6 hp
6. Sabre saw or key hole saw
System
7. Hacksaw 4 5 6
horsepower
8. Core bits Gas tubing (mm) ø15.88 ø19.05
9. Hammer
Liquid tubing (mm) ø9.52
10. Drill
Unit: mm, hp = horsepower
11. Tube cutter
Note : If the system consists of only one indoor unit with an
12. Tube flaring tool
outdoor 6HP, the main tube of the unit (LA) should be
13. Torque wrench ø19.05. Convert ø19.05 to ø15.88 using a reducer
14. Adjustable wrench (field supply) close to the indoor unit and then make the
15. Reamer (for deburring) connection.
16. Hexagonal wrench (4 mm and 5 mm)
Table 1-3 Main Tubing Size After Distribution (LB, LC...)
17. Pliers
Total 7.1 12.1 14.0 15.5
18. Cutting pliers Below kW
capacity after (2.5 hp) (4 hp) (5 hp) (6 hp)
distribution Over kW – 7.1(2.5 hp)
1-2. Accessories Supplied with Outdoor Unit
Table 1-1 (Outdoor Unit) Gas tubing
ø12.7 ø15.88 ø19.05
(mm)
Q’ty Tubing size
Liquid
Part ø9.52 ø9.52
Figure U-4LE1E5 U-5LE1E5 U-6LE1E5 tubing (mm)
name U-4LE1E8 U-5LE1E8 U-6LE1E8 Unit: mm, hp = horsepower
(4 hp) (5 hp) (6 hp)
Note : In case the total capacity of connected indoor units
exceeds the total capacity of the outdoor units, select the
main tubing size for the total capacity of the outdoor units.
Table 1-4 Indoor Unit Tubing Connection ( 1, 2... n–1)
Indoor unite type 22 28 36 45 56 73 90 106 140 160
Tube
Discharge 0 0 1 Gas tubing (mm) ø12.7 ø15.88
Assy Liquid tubing (mm) ø6.35 ø9.52
Unit: mm

1-6. Straight Equivalent Length of Joints


Design the tubing system by referring to the following table for
Plastic bar the straight equivalent length of joints.
2 2 2
(L=115 mm)
Table 1-5 Straight Equivalent Length of Joints
Instruction Gas tubing size (mm) 12.7 15.88 19.05
1 1 1
manual
paper 90° elbow 0.30 0.35 0.42
hp = horsepower
45° elbow 0.23 0.26 0.32
1-3. Type of Copper Tube and Insulation Material U-shape tube bend
0.90 1.05 1.26
If you wish to purchase these materials separately from a local (R60 − 100 mm)
source, you will need: Trap bend 2.30 2.80 3.20
1. Deoxidized annealed copper tube for refrigerant tubing.
Y-branch distribution Equivalent length conversion
2. Foamed polyethylene insulation for copper tubes as joint not needed.
required to precise length of tubing. Wall thickness of the
Equivalent length conversion
insulation should be not less than 8 mm. Ball value for service
not needed.
3. Use insulated copper wire for field wiring. Wire size varies
with the total length of wiring. Refer to 4. ELECTRICAL Table 1-6 Required Copper Tubing Dimensions Unit: mm
WIRING for details.
Material O
Outer
CAUTION diameter
6.35 9.52 12.7 15.88 19.05
Copper
Check local electrical codes and regulations before tubing Wall
obtaining wire. Also, check any specified instructions or 0.8 0.8 0.8 1.0 1.2
thickness
limitations. 7

Mini_VRF_eng.indd 7 2011/08/26 13:45:11


1-7. Additional Refrigerant Charge Table 1-10 Ranges that Apply to Refrigerant Tubing Lengths
and to Differences in Installation Heights
Additional refrigerant charge amount is calculated from the
liquid tubing total length as follows. Items Marks Contents Length (m)
Actual
Table 1-7 Amount of Refrigerant Charge Per Meter, ≤ 120
L1 Max. tubing length
According to Liquid Tubing Size length Equivalent
≤ 140
Liquid tubing size Amount of refrigerant length
charge/m (g/m) Difference between max.
ø6.35 26 Allowable ΔL (L2 – L3) length and min. length ≤ 40
ø9.52 56 tubing from the No.1 distribution
length joint
Required amount of charge , ... n Max. length of each
1 2 ≤ 30
distribution tube
= (Amount of refrigerant charge per meter of each size of liquid tube
× its tube length) + (...) + (...) Total max. tubing length
including length of each
, ... +L1 ≤ 150
1 2 n-1 distribution tube (only
narrow tubing)
* Always charge accurately using a scale for weighing.
When outdoor unit is
installed higher than ≤ 50
Table 1-8 Refrigerant Charge Amount at Shipment (for indoor unit
Allowable H1
outdoor unit) When outdoor unit is
elevation
4 hp 5 hp 6 hp installed lower than ≤ 40
difference
3.5 3.5 3.5 indoor unit
Max. difference between
Unit: kg, hp = horsepower
H2 ≤ 15
indoor units
L = Length, H = Height
1-8. System Limitations WARNING
Table 1-9 System Limitations
Always check the gas density limit for the room in which the
Outdoor units 4 hp 5 hp 6 hp unit is installed.
Number of max.
6 8 9
connectable indoor units 1-10. Check of Limit Density
Max. allowable indoor/ When installing an air conditioner in a room, it is necessary to
50 – 130%
outdoor capacity ratio
ensure that even if the refrigerant gas accidentally leaks out, its
hp = horsepower density does not exceed the limit level for that room.
If the density could exceed the limit level, it is necessary to
1-9. Tubing Length provide an opening between the unit and the adjacent room,
Select the installation location so that the length and size of or to install mechanical ventilation which is interlocked with the
refrigerant tubing are within the allowable range shown in the leak detector.
figure below. (Total refrigerant charged amount: kg)
(Min. indoor volume where indoor unit is installed: m3)
≤ Limit density 0.3 (kg/m3)
L1
LA L2 The limit density of refrigerant which is used in this unit is
LB LC LD n 0.3 kg/m3 (ISO 5149).
Less than
Main tube 400 mm The shipped outdoor unit comes charged with the amount of
of unit
For H1 refrigerant fixed for each type, so add it to the amount that
extension is charged at the field. (For the refrigerant charge amount at
1st branch shipment, refer to the unit’s nameplate.)
L3 1 2 3 n-1 H2

Unit distribution tube


Distribution joint (CZ-P160BK2)
Ball valve (field supply)

Note: Do not use commercially available T-joints for the liquid tubing.

* Be sure to use special R410A R410A distribution joint


distribution joints (CZ-P160BK2 : CZ-P160BK2 (for indoor unit)
purchased separately) for outdoor
unit connections and tubing
branches.

Mini_VRF_eng.indd 8 2011/08/26 13:45:11


Minimum indoor volume & floor area relative to the amount of
refrigerant are roughly as given in the following table. Types of vertical trap specifications
m2 m3
125 337.5
120 324.0 (When using ball valve (field supply))
115 310.5
110 297.0 Main tubing
105 283.5
100 270.0
95 256.0
(when the ceiling is 2.7 m high)

90 243.0 Ball valve Indoor unit (more than 2 units)


85 229.5 (BV: field supply) (If only 1 unit is connected, a ball
80 216.0 Range below the valve is also needed on this side.)
Min. indoor volume

density limit of 0.3 kg/m³


Min. indoor floor area

75 202.5
(Countermeasures not Indoor unit (1)
70 189.0
needed)
65 175.5
60 162.0
55 148.5 (When not using ball valve)
50 135.0 Range above the
45 121.5 density limit of 0.3 kg/m³ Main tubing
40 108.0 (Countermeasures needed) Horizontal (Each unit is
35 94.5 Indoor unit connected to
30 81.0 tubing that is either
Branch tubing is
level or is directed
25 67.5 directed upward.
downward.)
20 54.0
15 40.5 More than
20 cm
10 27.0
5 13.5
0 0.0 Indoor unit is directed downward
0 10 20 30 40 50 60 70 80 90 100 kg

1-12. Optional Distribution Joint Kit


Total amount of refrigerant
See the installation instructions packaged with the distribution
joint kit for the installation procedure.
CAUTION
Pay special attention to any location, such as a basement, Table 1-11
etc. where leaking refrigerant can accumlate, since Cooling capacity
refrigerant gas is heavier than air. Model name Remarks
after distribution
CZ-P160BK2 22.4 kW or less For indoor unit
1-11. Installing Distribution Joint
CZ-P160BK2
(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT” Use: For indoor unit (Capacity after distribution joint is 22.4 kW or less.)
enclosed with the optional distribution joint kit
(CZ-P160BK2). Example Gas tube Liquid tube
(2) In order to prevent accumulation of refrigerant oil in 110 110
stopped units, if the main tubing is horizontal then each 97 97
branch tubing length should be at an angle that is greater C
than horizontal. If the main tubing is vertical, provide a B D C C DE
A B A
raised starting portion for each branch. B
C
(3) If there are height differences between indoor units or if Distribution joint Distribution
72

72
joint
branch tubing that follows a distribution joint is connected
to only 1 unit, a trap or ball valve (field supply) must be C D
added to that distribution joint. (When adding the ball E
valve, locate it within 40 cm of the distribution joint.)
Insulation Insulation

If a trap or ball valve (field supply) is not added, do not


operate the system before repairs to a malfunctioning unit Table 1-12 Size of connection point on each part
are completed. (The refrigerant oil sent through the tubing to (shown are inside diameters of tubing)
the malfunctioning unit will accumulate and may damage the Size Part A Part B Part C Part D Part E
compressor.) mm ø19.05 ø15.88 ø12.7 ø9.52 ø6.35
Tube branching methods (horizontal use) Unit: mm


t o3
15

Horizontal A
B A line View as seen from
arrow

Arrow view

Mini_VRF_eng.indd 9 2011/08/26 13:45:12


1-13. Example of Tubing Size Selection and Example:
Refrigerant Charge Amount
Additional refrigerant charging
Based on the values in Tables 1-2, 1-3, 1-4 and 1-7, use the L1
liquid tubing size and length, and calculate the amount of LA L2
additional refrigerant charge using the formula below. LB LC LN n
Main tube
of unit
Required additional
= [56 × (a) + 26 × (b)] × 10 –3
refrigerant charge (kg) 1st branch
1 2 3 n–1 type
Unit distribution 56
(a): Liquid tubing Total length of ø9.52 (m) tube type type type type
(b): Liquid tubing Total length of ø6.35 (m) 22 28 36 45

● Charging procedure ● Example of each tubing length


Be sure to charge with R410A refrigerant in liquid form Main tubing Distribution joint tubing
LA = 40 m Indoor side
1. After performing a vacuum, charge with refrigerant from
the liquid tubing side. At this time, all valves must be in the LB = 5 m 1=5m 4=6m
“fully closed” position. LC = 5 m 2=5m 5=5m
LD = 15 m 3=2m
2. If it was not possible to charge the designated amount,
operate the system in Cooling mode while charging with ● Obtain charge amount for each tubing size
refrigerant from the gas tubing side. (This is performed at
Note that the charge amounts per 1 meter are different for
the time of the test run. For this, all valves must be in the
each liquid tubing size.
“fully open” position.)
Charge with R410A refrigerant in liquid form. ø9.52 → LA + LB + LC + LD : 65 m × 0.056 kg/m = 3.64 kg
With R410A refrigerant, charge while adjusting the ø6.35 → 1+ 2+ 3+ 4+ 5 : 23 m × 0.026 kg/m = 0.598 kg
amount being fed a little at a time in order to prevent liquid Total 4.238 kg
refrigerant from backing up. Additional refrigerant charge amount is 4.238 kg.
● After charging is completed, turn all valves to the “fully open”
position.
CAUTION
● Replace the tubing covers as they were before.
Be sure to check the limit density for the room in which the
indoor unit is installed.

Tightening torque for 4


valve stem cap:
19 – 21 N·m
Tightening torque: 3
34 – 42 N·m
2 Tightening torque for valve 1 Tightening torque:
stem cap: 28 – 32 N·m 68 – 82 N·m

CAUTION
1. R410A additional charging absolutely must be done
through liquid charging.
2. The R410A refrigerant cylinder has a gray base color,
and the top part is pink.
3. The R410A refrigerant cylinder includes a siphon tube.
Check that the siphon tube is present. (This is indicated
on the label at the top of the cylinder.)
4. Due to differences in the refrigerant, pressure, and
refrigerant oil involved in installation, it is not possible in
some cases to use the same tools for R22 and for R410A.

10

Mini_VRF_eng.indd 10 2011/08/26 13:45:13


Checking of limit density
Exhaust fan
Density limit is determined on the basis of the size of a room Hot air
using an indoor unit of minimum capacity. For instance, when
an indoor unit is used in a room (floor area 7.43 m2 × ceiling Heat source
height 2.7 m = room volume 20.06 m3), the minimum room Out-
volume should be 25.8 m3 (7.738 kg ÷ 0.3 kg/m3) for refrigerant door
of 7.738 kg (3.5 kg + 4.238 kg). Accordingly, openings such as unit
louvers are required for this room.

<Determination by calculation>
Overall refrigerant charge amount for the air conditioner: kg Fig. 2-1
(Minimum room volume for indoor unit: m3) Installation space for outdoor unit
4.238 (kg) + 3.5 (kg) Install the outdoor unit with a sufficient space around the
= = 0.39 (kg/m3) 0.3 (kg/m3)
20.06 (m3) outdoor unit for operation and maintenance.
(1) Obstructions on the left side, right side and rear side (Front
Therefore, openings such as louvers are required for this room. side and above the unit are opened). (Fig. 2-2)

m2 m3
125 337.5
120 324.0
115 310.5
110 297.0 A *B C
105 283.5 15 cm 25 cm 20 cm
100 270.0 or more or more or more
95 256.0 A
(when the ceiling is 2.7 m high)

90 243.0
*B
85 229.5
80 216.0 Range below the
Min. indoor volume

density limit of 0.3 kg/m³ Fig. 2-2


Min. indoor floor area

75 202.5
(Countermeasures not * The outdoor units require necessary space to unscrew on
70 189.0 needed)
65 175.5 the rear side for maintenance and if a sufficient maintenance
60 162.0 space is provided on the rear side (40 cm), the space of over
55 148.5 15 cm is enough at the right side.
50 135.0 Range above the
45 121.5 density limit of 0.3 kg/m³ (2) Obstructions on the front side and rear side (Left side, right
(Countermeasures needed) side and above the unit are opened). (Fig. 2-3)
40 108.0
35 94.5
30 81.0
25 67.5
20 54.0
15 40.5
10 27.0 *A B
5 13.5 50 cm 15 cm
0 0.0 or more or more
0 10 20 30 40 50 60 70 80 90 100 kg
B

Total amount of refrigerant *A

Fig. 2-3
2. SELECTING THE INSTALLATION SITE * For compressor replacement, 50 cm or more is required on
the front side even when using the air discharge chamber.
2-1. Outdoor Unit (3) Obstructions on the front side and above the unit (Left
side, right side and rear side are opened). (Fig. 2-4)
AVOID:
● heat sources, exhaust fans, etc. (Fig. 2-1)
B
● damp, humid or uneven locations
A B
● indoors (no-ventilation location)
50 cm 30 cm
DO: or more or more
● choose a place as cool as possible.
● choose a place that is well ventilated and outside air A
temperature does not exceed maximum 45°C constantly.
● allow enough room around the unit for air intake/ Fig. 2-4
exhaust and possible maintenance. (Figs. 2-2, 2-3, 2-4)
● use lug bolts or equal to bolt down unit, reducing vibration
and noise.

11

Mini_VRF_eng.indd 11 2011/08/26 13:45:14


In case of multiple installations 2-3. Installing the Unit in Heavy Snow Areas
● Provide a solid base (concrete block, 10 × 40 cm beams or In locations with strong wind, snow-proof ducting should be
equal), a minimum of 15 cm above ground level to reduce fitted and direct exposure to the wind should be avoided as
humidity and protect the unit against possible water damage much as possible.
and decreased service life. (Fig. 2-5)
● Use lug bolts or equal to bolt down unit, reducing vibration
■ Countermeasures against snow and wind
and noise.
In regions with snow and strong wind, the following problems
Air intake Air intake may occur when the outdoor unit is not provided with a platform
and snow-proof ducting:
a) The outdoor fan may not run and damage to the unit may
occur.
Air discharge b) There may be no air flow.
c) The tubing may freeze and burst.
d) The condenser pressure may drop because of strong wind,
Air discharge and the indoor unit may freeze.
Anchor bolts
(4 pieces)
2-4. Precautions for Installation in Heavy Snow Areas
Min. 15cm (1) The platform should be higher than the max. snow depth.
(Fig. 2-7)

Fig. 2-5

2-2. Air-Discharge Chamber for Top Discharge


Be sure to install an air-discharge chamber in the field when:
● it is difficult to keep a space of min. 50 cm between the air
discharge outlet and an obstacle.
● the air discharge outlet is facing a sidewalk and discharged
hot air may annoy passers-by. Refer to Fig. 2-6.

Air discharge
Without snow- With snow-
proof ducting proof ducting
(Low platform) (High platform)
Fig. 2-7
(2) The 2 anchoring feet of the outdoor unit should be used for
the platform, and the platform should be installed beneath
the air intake side of outdoor unit.
(3) The platform foundation must be firm and the unit must be
secured with anchor bolts.
(4) In case of installation on a roof subject to strong wind,
countermeasures must be taken to prevent the unit from
being blown over.

Fig. 2-6
Min. 100
Duct 308
In regions with significant snowfall, the outdoor unit
should be provided with a platform and snow-proof duct. Outdoor Unit

Outdoor
Unit Min. 100 166
Unit: mm

Duct Duct
Higher than the
maximum snow depth

Air intake

Air intake Platform (foundation)


About 1/2 of the unit height
Fig. 2-8

12

Mini_VRF_eng.indd 12 2011/08/26 13:45:14


2-5. Dimensions of Air-Discharge Chamber
Reference diagram for air-discharge chamber (field supply)
Unit: mm

10
20
Air Intake

340
380
Air Intake

20
20
170 660 (110) Installation anchoring holes (4-R6.5) / Anchor bolt M10

940 643
56 568 (316) (303) 340
217

89
Air

566
discharge
Air Intake
1330

32

555
Air
discharge

(88)

Required space around outdoor unit


If the air discharge chamber is used, the space shown below must be secured around the outdoor unit.
If the unit is used without the required space, a protective device may activate, preventing the unit from operating.

(1) Single-unit installation


Unit: mm The top and both sides must remain open.

CAUTION If there are obstacles to the front and rear of


the outdoor unit, the obstacle at either the
front or rear must be no taller than the height
Min. 150
or more

of the outdoor unit.


Min. 500
or more

(2) Multiple-unit installation


Installation in lateral rows Installation in front-rear rows
Installation with intakes facing
intakes or outlets facing outlets

Min. 300 or more


Min. 200
or more

Min. 1000 or more

Min. 250 Min. 250


or more or more

Not less than 150* or more

Unit: mm

NOTE Unit: mm

● The amount of space is required for removing the screws CAUTION The front and both sides must remain open.
on the rear of the unit. If in case the sufficient space for
maintenance is ensured on the rear of the outdoor unit,
installation is possible with the space of both sides of not less
than 150mm where marked with * mark.

CAUTION The front and top must remain open.


The obstacles must be no taller than the height
of the outdoor unit.
13

Mini_VRF_eng.indd 13 2011/08/26 13:45:15


2-6. Dimensions of Snow-Proof Vents
Reference diagram for snow-proof vents (field supply)
Air Intake Unit: mm

702 (295)

10
20
340
380
20
20
Air discharge
227 660 Mounting hole
997 (2-13 × 18 hole) 645
691 2 340 (303)

Air discharge

733
1209
1333

Air discharge

Air Intake
(124)

Required space around outdoor unit


[Obstacle to the rear of unit]

● Top is open:

(1) Single-unit installation (2) Obstacles on both sides Unit: mm


A B C D E F G
150 150 250* 200 250 150 200
or more
or more

Notes:
Min. D
Min. A

1. In cases 2 and 3 the height of the obstacle must be no taller


than the height of the outdoor unit.
Min. B
or more Min. C 2. The amount of space is required for removing the screw on the
or more rear of the unit. If in case the sufficient space for maintenance
is ensured on the rear of the outdoor unit, installation is
possible with the space of both sides of not less than 150mm
where marked with * mark.

(3) Multiple-unit installation (2 or more units)

● Top is blocked by an obstacle:


or more

Min. L
Min. G

or more

Min. E Min. E Min. E


or more

Unit: mm
Min. K

or more or more or more


Min. F K L
or more
500 150

14

Mini_VRF_eng.indd 14 2011/08/26 13:45:16


[Obstacle to the front of unit]

● Top is open: Unit: mm ● Top is blocked by an obstacle:


(1) Single-unit installation H I J
500 250* 1000
Unit: mm
M N

or more
Min. N
or more
500 300

Min. H
Min. M
or more

(2) Multiple-unit installation (2 or more units)

or more
Min. I Min. I Min. J
or more or more

Note: The amount of space is required for removing the screws


on the rear of the unit.
If in case the sufficient space for maintenance is ensured
on the rear of the outdoor unit, installation is possible
with the space of both sides of not less than 150mm
where marked with * mark.

[Obstacle to the front and rear of unit]

● The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller
than the height of the outdoor unit.
(1) Single-unit installation (2) Obstacles on both sides
Installation is possible with the maximum 3 outdoor units.
or more
Min. P

Unit: mm
Q

Min.1000

Min.300
or more

or more
or more
Min. O

Q
Unit: mm
Min. 250* Min. 250*
O P or more or more
500 150

Dimension Q Note:
If a snow protection duct is attached after the unit is The amount of space is required for removing the screws on the rear
installed, verify that dimension Q is 500 mm or more. of the unit. If in case the sufficient space for maintenance is ensured
on the rear of the outdoor unit, installation is possible with the space
of both sides of not less than 150mm where marked with * mark.

[Installation in front-rear rows]

● The top and both sides must remain open. Unit: mm


Either the obstacle to the front or the obstacle to Min. 300 or more
the rear must be no taller than the height of the Min. 1500 or more
outdoor unit.

15

Mini_VRF_eng.indd 15 2011/08/26 13:45:17


3. HOW TO INSTALL THE OUTDOOR UNIT 3-3. Routing the Tubing and Wiring
● The tubing and wiring can be extended out in 4 directions
3-1. Installing the Outdoor Unit (front, rear, right, and down):
● Use concrete or a similar material to create the base, and ● The service valves are housed inside the unit. To access
ensure good drainage. them, remove the inspection panel. (To remove the
inspection panel, remove the 3 screws, then slide the panel
● Ordinarily, ensure a base height of 5 cm or more. If a drain
downward and pull it toward you.)
pipe is used, or for use in cold-weather regions, ensure a
(1) If the routing direction is through the front, rear, or right,
height of 15 cm or more at the feet on both sides of the unit.
use a nipper or similar tool to cut out the knockout holes for
(In this case, leave clearance below the unit for the drain
the inter-unit control wiring outlet, power wiring outlet, and
pipe, and to prevent freezing of drainage water in cold-
tubing outlet from the appropriate covers A and B.
weather regions.)
When routing the wiring, be sure to attach each supplied
● Refer to Fig. 3-1 for the anchor bolt dimensions. plastic bar to the edges around the wiring outlet holes in
● Be sure to anchor the feet with anchor bolts (M10). In order to protect the wiring from scratches by the cutting
addition, use anchoring washers on the top side. (Use large burr.
square 32 × 32 SUS washers with JIS nominal diameter of (2) If the routing direction is down, use a nipper or similar tool
10.) (Field supply) to cut out the lower flange from cover A.
4- ø32
Inter-unit control wiring outlet*
Drain port (2 locations)
Inspection panel
170 660 110 Rear
105 219 7575 50
(10)

13 Air Intake 13
26

20 20

Cover B
Cover A
340

410
380
290

Right
Front

Power wiring outlet* Down Tubing outlet


18

20

13 Air discharge 13
4- ø13 Anchor bolt hole Fig. 3-2
940
N OT E
* When not using a conduit material or existing materials,
measure and cut the supplied plastic bar according to the size
of the wiring outlet hole. Then attach the plastic bar to the edges
around the hole. Use sealing putty to seal off the hole to prevent
the dust and insects from entering the wiring outlet holes.
1330

CAUTION
● Route the tubing so that it does not contact the
compressor, panel, or other parts inside the unit.
Increased noise will result if the tubing contacts these
parts.
● When routing the tubing, use a tube bender to bend the
tubes.
Anchor bolt (M10)
4. ELECTRICAL WIRING
Drain port
4-1. General Precautions on Wiring
Fig. 3-1
(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring closely
3-2. Drainage Work following the wiring diagram.
Follow the procedure below to ensure adequate draining for the (2) Provide a power outlet to be used exclusively for each
outdoor unit. unit and a power supply disconnect, circuit breaker and
● For the drain port dimensions, refer to Fig. 3-1. earth leakage breaker for overcurrent protection should be
provided in the exclusive line.
● Ensure a base height of 15 cm or more at the feet on both
sides of the unit. (3) To prevent possible hazards from insulation failure, the unit
must be grounded.
● When using a drain pipe, install the drain socket (field
supply) onto the drain port. Seal the other drain port with the (4) Each wiring connection must be done in accordance with
rubber cap supplied with the drain socket. the wiring system diagram. Wrong wiring may cause the
unit to disorder or become damaged.
● For details, refer to the instruction manual of the drain socket
(field supply). (5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
● After completing the installation work of the drain socket,
make sure that the water does not leak from any part of (6) Unauthorized changes in the internal wiring can be very
connection. dangerous. The manufacturer will accept no responsibility
for any damage or malfunction that occurs as a result of
such unauthorized changes.
(7) Regulations on wire diameters differ from locality to
locality. For field wiring rules, please refer to your LOCAL
ELECTRICAL CODES before beginning.
You must ensure that installation complies with all relevant
rules and regulations.
16

Mini_VRF_eng.indd 16 2011/08/26 13:45:18


(8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:
● The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.
● Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.
(9) If the power supply cord of this appliance is damaged, it must be replaced by a repair shop appointed by the manufacturer,
because special purpose tools are required.

4-2. Recommended Wire Length and Wire Diameter Indoor unit


for Power Supply System (B) Power supply Time delay fuse or
Type
2.5 mm2 circuit capacity
Outdoor unit (Single-phase)
K1 Max. 150 m 10 – 16 A
(A) Power supply Time delay capacity
D1, L1, U1, Y1, T1, F1, M1,
Circuit Max. 130 m 10 – 16 A
Wire size Max. length Fuse P1, R1
breaker
E1 (73, 106, 140) Max. 60 m 10 – 16 A
U-4LE1E5 4 mm2 21 m 25 A 30 A
U-5LE1E5 6 mm2 24 m 35 A 40 A Control wiring
U-6LE1E5 6 mm2 20 m 35 A 40 A
(C) Inter-unit
(between outdoor (D) Remote control (E) Control wiring for
Outdoor unit (3-phase) and indoor units) wiring group control
(A) Power supply Time delay capacity control wiring
Circuit 0.75 mm2 (AWG #18)
Wire size Max. length Fuse Use shielded 0.75 mm2 (AWG #18) 0.75 mm2 (AWG #18)
breaker
wiring*1
U-4LE1E8 2.5 mm2 58 m 20 A 20 A
Max. 1,000 m Max. 500 m Max. 200 m (Total)
U-5LE1E8 2.5 mm2 49 m 20 A 20 A
U-6LE1E8 2.5 mm2 41 m 20 A 20 A
N OT E

4-3. Wiring System Diagrams *1 With ring-type wire terminal.

Indoor unit
(No. 1) Outdoor unit : single-phase model
Power supply L L
220 – 240V ~50/60Hz N N
Power supply
220 – 240 V, single-phase, ~ 50 Hz
Ground C
B U1 U1
Remote Ground
U2 U2
controller D
WHT 1 1 R1
Ground
BLK 2 2 R2 In case of 3-phase power supply
Outdoor unit : 3-phase model
Ground L1 Power supply
C 1 L1
Indoor unit 2 L2 L2 380 – 415 V, 3-phase, ~ 50 Hz
L3
L3
(No. 2) N
Power supply L L Ground
220 – 240V ~50/60Hz N N
Ground
Ground B U1
Remote U2
controller D Outdoor unit : single-phase model Outdoor unit : 3-phase model
WHT 1 1 R1
BLK 2 2 R2 2P terminal board 4P terminal board
Ground
C
Indoor unit
Group control:
(No. 3)
L U1 U2 U1 U2
Power supply L
220 – 240V ~50/60Hz N N

Ground B
Ground
L N U1 U2 L1 L2 L3 N U1 U2
E U1
U2 Power supply Inter-unit Power supply Inter-unit
control wiring control wiring
R1
R2
Mini VRF System
Ground
C
N OT E
Indoor unit (1) Refer to Section 4-2. “Recommended Wire Length
(No. n) and Wire Diameter for Power Supply System” for the
Power supply L L
explanation of “A”, “B”, “C”, “D” and “E” in the above
220 – 240V ~50/60Hz N N
Ground diagrams.
Ground B U1 (2) The basic connection diagram of the indoor unit shows
Remote
controller D
U2 the 7P terminal board, so the terminal boards in your
WHT 1 1 R1 equipment may differ from the diagram.
BLK 2 2 R2
(3) Refrigerant Circuit (R.C.) address should be set before
turning the power on.
(4) Regarding the R.C. address setting, refer to Section 7-4.
“Auto Address Setting”. Address setting can be executed
by remote controller automatically.

17

Mini_VRF_eng.indd 17 2011/08/26 13:45:18


CAUTION
(1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (CN-TERMINAL, 2P Black,
location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units.
(When shipping: In shorted condition)
For a system without link (no connection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-1)

Outdoor unit Outdoor unit Outdoor unit


Prohibited

Prohibited

Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit

Fig. 4-1
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting.

Outdoor unit Indoor unit Indoor unit

NO Indoor unit Indoor unit

Branch point
Fig. 4-2
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 1 m are not included in the total branch number.) (Fig. 4-3)

Outdoor unit Outdoor unit Outdoor unit

Indoor unit Indoor unit Indoor unit Indoor unit

more than 1 m
Branch
Point
16 or fewer Indoor unit Indoor unit Indoor unit Indoor unit

more than 1 m

Indoor unit

less than 1 m

Indoor unit

Fig. 4-3

(5) Use shielded wires for inter-unit control wiring (c) and
WARNING
ground the shield on both side, otherwise malfunction
from noise may occur. (Fig. 4-4) Connect wiring as Loose wiring may cause the terminal to overheat or result
shown in Section “4-3. Wiring System Diagrams”. in unit malfunction. A fire hazard may also occur. Therefore,
ensure that all wiring is tightly connected.
Shielded wire When connecting each power wire to the terminal, follow the
instructions on “How to connect wiring to the terminal” and
Ground Ground fasten the wire securely with the fixing screw of the terminal
plate.
Fig. 4-4
(6) Use the standard power supply cables for Europe
(such as H05RN-F or H07RN-F which conform to
CENELEC (HAR) rating specifications) or use the
cables based on IEC standard. (code designation,
60245 IEC 57, 60245 IEC 66)

18

Mini_VRF_eng.indd 18 2011/08/26 13:45:18


How to connect wiring to the terminal ■ Wiring sample
■ For stranded wiring Outdoor unit : single-phase model
(1) Cut the wire end with cutting pliers, then strip the insulation
to expose the stranded wire about 10 mm and tightly twist Use this screw when
the wire ends. (Fig. 4-5) connecting to ground
for the inter-unit control
Stranded wire wiring.

Ring
pressure
Strip 10 mm terminal

U1 U2

Fig. 4-5
(2) Using a Phillips head screwdriver, remove the terminal
screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely clamp
each stripped wire end with a ring pressure terminal.
(4) Place the ring pressure terminal, and replace and tighten
the removed terminal screw using a screwdriver. (Fig. 4-6)
Screw
Special washer

Ring pressure Screw and


terminal Special washer

Wire Terminal plate


Ring Earth
pressure
terminal

Wire
Inter-unit Control Wiring Power Supply
Fig. 4-6

Outdoor unit : 3-phase model


■ Examples of shield wires
(1) Remove cable coat not to scratch braided shield. (Fig. 4-7)
Use this screw when
(2) Unbraid the braided shield carefully and twist the connecting to ground
unbraided shield wires tightly together. Insulate the shield for the inter-unit control
wires by covering them with an insulation tube or wrapping wiring.
insulation tape around them. (Fig. 4-8)
(3) Remove coat of signal wire. (Fig. 4-9)
(4) Attach ring pressure terminals to the signal wires and the
shield wires insulated in Step (2). (Fig. 4-10)
U1 U2

Fig. 4-7

Insulation tape Shield mesh


Fig. 4-8
m
8m

Insulation tape Shield mesh


Fig. 4-9
Earth

Fig. 4-10

Inter-unit Control Wiring Power Supply

19

Mini_VRF_eng.indd 19 2011/08/26 13:45:19


5. HOW TO PROCESS TUBING Caution Before Connecting Tubes Tightly
Both the liquid tubing and the gas tubing sides are connected (1) Apply a sealing cap or water-proof tape to prevent dust or
by a flare nut. water from entering the tubes before they are used.
(2) Be sure to apply refrigerant lubricant to the matching
5-1. Connecting the Refrigerant Tubing surfaces of the flare and union before connecting them
together. This is effective for reducing gas leaks. (Fig. 5-4)
Use of the Flaring Method
Many of conventional split system air conditioners employ the
flaring method to connect refrigerant tubes which run between
indoor and outdoor units. In this method, the copper tubes are
flared at each end and connected with flare nuts.
Apply refrigerant lubricant.
Flaring Procedure with a Flare Tool
Fig. 5-4
(1) Cut the copper tube to the required length with a tube
cutter. It is recommended to cut approx. 30 – 50 cm longer
(3) For proper connection, align the union tube and flare tube
than the tubing length you estimate.
straight with each other, then screw in the flare nut lightly
(2) Remove burrs at the end of the copper tube with a tube at first to obtain a smooth match. (Fig. 5-5)
reamer or file. This process is important and should be
done carefully to make a good flare. (Fig. 5-1)

Deburring
Before After Copper
tubing Flare nut
Union
Fig. 5-5
Reamer
● Adjust the shape of the liquid tube using a tube bender at the
installation site and connect it to the liquid tubing side valve
using a flare.
Fig. 5-1 Fig. 5-2
Cautions During Brazing
NOTE
● Replace air inside the tube with nitrogen gas to prevent
When reaming, hold the tube end downward and be sure that copper oxide film from forming during the brazing
no copper scraps fall into the tube. (Fig. 5-2) process. (Oxygen, carbon dioxide and Freon are not
acceptable.)
● Do not allow the tubing to get too hot during brazing.
(3) Remove the flare nut from the unit and be sure to mount it
The nitrogen gas inside the tubing may overheat,
on the copper tube.
causing refrigerant system valves to become damaged.
(4) Make a flare at the end of the copper tube with a flare tool. Therefore allow the tubing to cool when brazing.
(Fig. 5-3)
● Use a reducing valve for the nitrogen cylinder.
Flare nut ● Do not use agents intended to prevent the formation
Copper of oxide film. These agents adversely affect the
tubing refrigerant and refrigerant oil, and may cause damage or
malfunctions.

Flare tool
Fig. 5-3
NOTE
A good flare should have the following characteristics:
● inside surface is glossy and smooth
● edge is smooth
● tapered sides are of uniform length

20

Mini_VRF_eng.indd 20 2011/08/26 13:45:20


5-2. Connecting Tubing Between Indoor and Outdoor 5-3. Insulating the Refrigerant Tubing
Units
Tubing Insulation
(1) Tightly connect the indoor-side refrigerant tubing extended
from the wall with the outdoor-side tubing. ● Standard Selection of Insulation Material
(2) To fasten the flare nuts, apply specified torque as shown in Under the environment of the high temperature and high
the table below. humidity, the surface of the insulation material is easy to
become condesation. This will result in leakage and dew
● When removing the flare nuts from the tubing connections, drop. Refer to the chart shown below when selecting the
or when tightening them after connecting the tubing, be sure insulation material. In case that the ambient temperature and
to use 2 adjustable wrenches or spanners. (Fig. 5-6) relative humidity are placed above the line of the insulation
If the flare nuts are over-tightened, the flare may be thickness, the condensation may occasionally make a dew
damaged, which could result refrigerant leakage and cause drop on the surface of the insulation material. In this case,
injury or asphyxiation to room occupants. select the better insulation efficiency.
* However, since the condition will be different due to
Torque wrench the sort of the insulaton material and the environmental
condition of the installation place, see the chart shown
Spanner below as a reference when making a selection.
Indoor unit
Standard Selection of Tubing Insulation
Outdoor unit
Fig. 5-6 Calculating condition

● For the flare nuts at tubing connections, be sure to use the Sort of insulation material
Polyethylene heat resisting
flare nuts that were supplied with the unit, or else flare nuts material
for R410A (type 2). The refrigerant tubing that is used must Thermal conductivity of
be of the correct wall thickness as shown in the table below. Based on JIS A9501
insulation material
Calculating formula used
Tightening torque Based on JIS A9501
Tube diameter Tube thickness when calculating thickness
(approximate)
14 – 18 N · m Refrigerant temperature 2°C
ø6.35 (1/4") 0.8 mm
(140 – 180 kgf · cm)
o6.35 o9.52
34 – 42 N · m 100 100
ø9.52 (3/8") 0.8 mm
(340 – 420 kgf · cm)
Ambient relative humidity [%]

Ambient relative humidity [%]


90 Thickness 90
30 mm Thickness
49 – 55 N · m 30 mm
ø12.7 (1/2") 0.8 mm 80 Thickness 80 Thickness
(490 – 550 kgf · cm) 20 mm
20 mm
70 70
68 – 82 N · m
ø15.88 (5/8") 1.0 mm Thickness
(680 – 820 kgf · cm) 60 10 mm 60 Thickness
10 mm
100 – 120 N · m 50 50
ø19.05 (3/4") 1.2 mm
(1000 – 1200 kgf · cm)
40 40
10 20 30 40 50 10 20 30 40 50
Because the pressure is approximately 1.6 times higher than Ambient temperature [°C] Ambient temperature [°C]
conventional refrigerant pressure, the use of ordinary flare nuts o12.7 o15.88
100 100
(type 1) or thin-walled tubes may result in tube rupture, injury, or
Ambient relative humidity [%]

Ambient relative humidity [%]

asphyxiation caused by refrigerant leakage. 90


Thickness
90
Thickness
30 mm
● In order to prevent damage to the flare caused by over- 80
Thickness
80 30 mm
Thickness
tightening of the flare nuts, use the table on this page as a 70 20 mm 70 20 mm
guide when tightening.
60 Thickness 60
Thickness
● When tightening the flare nut on the liquid tube, use an 10 mm 10 mm
50 50
adjustable wrench with a nominal handle length of 200 mm.
40 40
10 20 30 40 50 10 20 30 40 50
Ambient temperature [°C] Ambient temperature [°C]

100
o19.05
Two tubes arranged together
Ambient relative humidity [%]

90
Thickness
80 30 mm Liquid tubing Gas tubing
Thickness
70 20 mm

60
Thickness
50
10 mm
Insulation
40
10 20 30 40 50
Ambient temperature [°C]

Fig. 5-7

21

Mini_VRF_eng.indd 21 2011/08/26 13:45:20


If the exterior of the outdoor unit valves 5-5. Finishing the Installation Apply putty here
has been finished with a square duct
After finishing insulating and taping
CAUTION covering, make sure you allow sufficient
over the tubing, use sealing putty to
space to use the valves and to allow the
seal off the hole in the wall to prevent
panels to be attached and removed.
rain and draft from entering. (Fig. 5-11)
Taping the flare nuts
Tubing
Wind the white insulation tape around the flare nuts at the gas
tube connections. Then cover up the tubing connections with Fig. 5-11
the flare insulator, and fill the gap at the union with the supplied
black insulation tape. Finally, fasten the insulator at both ends 6. AIR PURGING Manifold gauge
with the supplied vinyl clamps. (Fig. 5-8)
Air and moisture in the refrigerant
Sealer (supplied) Insulation tape (white) system may have undesirable effects
(supplied)
Flare insulator (supplied) as indicated below.
Tube insulator ● pressure in the system rises
Unit side (not supplied)
insulator Heat resistant ● operating current rises
120°C or above ● cooling (or heating) efficiency drops
Flare nut
Vinyl clamps (supplied) Fig. 5-8 ● moisture in the refrigerant circuit may
Fig. 6-1
freeze and block capillary tubing
Insulation material Vacuum pump
● water may lead to corrosion of parts
The material used for insulation must have good insulation in the refrigerant system Outlet
characteristics, be easy to use, be age resistant, and must not Therefore, the indoor unit and tubing Inlet
easily absorb moisture. between the indoor and outdoor unit
After a tube has been insulated, never try must be leak tested and evacuated
to bend it into a narrow curve because it to remove any noncondensables and
CAUTION moisture from the system.
can cause the tube to break or crack.
(Figs. 6-1 and 6-2)
Refrigerant tubing and insulator (not supplied)
Fig. 6-2
Drain pipe and insulator (not supplied)
Drain insulator ■ Air Purging with a Vacuum Pump (for Test Run)
and clamp. Large Preparation
(supplied) Check that each tube (both liquid and gas tubes) between the
Packing clamp. Insulation tape indoor and outdoor units has been properly connected and all
Small hose band wiring for the test run has been completed. Remove the valve
(supplied) Vinyl clamp caps from both the gas tube and liquid tube service valves on
Flare insulator the outdoor unit. Note that both liquid and gas tube service
Seal valves on the outdoor unit are kept closed at this stage.
The procedure used for
installing the insulator (Fig. 6-3)
for both gas and liquid
tubes is the same. Manifold valve
Fig. 5-9
Never grasp the drain or refrigerant connecting outlets
when moving the unit.
Pressure
Lo Hi
gauge
5-4. Taping the Tubes
(1) At this time, the refrigerant tubes (and electrical wiring Charge hose
if local codes permit) should be taped together with
armoring tape in 1 bundle. To prevent condensation from Cylinder
overflowing the drain pan, keep the drain hose separate valve
from the refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the outdoor Nitrogen gas cylinder
(In vertical standing
unit to the top of the tubing where it enters the wall. As you position)
wrap the tubing, overlap half of each previous tape turn.
Service port ø7.94 mm
(3) Clamp the tubing bundle to the wall, using 1 clamp approx.
each meter. (Fig. 5-10)

Open

Gas tube
Close Outdoor unit
Clamp
Insulated tubes Drain hose Open

Liquid tube
Close

Fig. 5-10 Fig. 6-3


NOTE
Do not wind the armoring tape too tightly since this will
decrease the heat insulation effect. Also ensure that the
condensation drain hose splits away from the bundle and drips
clear of the unit and the tubing. 22

Mini_VRF_eng.indd 22 2011/08/26 13:45:20


Leak test Manifold valve
(1) Attach a manifold valve (with pressure gauges) and dry
nitrogen gas cylinder to this service port with charge
hoses.
Lo Hi
CAUTION Pressure
gauge
Use a manifold valve for air purging. If it is not available,
use a stop valve for this purpose. The “Hi” knob of the
manifold valve must always be kept closed.
(2) Pressurize the system to no more than 3.80 MPa with dry
nitrogen gas and close the cylinder valve when the gauge
reading reaches 3.80 MPa. Then, test for leaks with liquid
soap.

CAUTION
Vacuum pump
To avoid nitrogen entering the refrigerant system in a
liquid state, the top of the cylinder must be higher than Service port ø7.94 mm
the bottom when you pressurize the system. Usually, the
cylinder is used in a vertical standing position.
(3) Do a leak test of all joints of the tubing (both indoor and
Open
outdoor) and both gas tube and liquid tube service valves.
Bubbles indicate a leak. Wipe off the soap with a clean
cloth after the leak test. Gas tube
Close Outdoor unit
(4) After the system is found to be free of leaks, relieve the
nitrogen pressure by loosening the charge hose connector
at the nitrogen cylinder. When the system pressure is Open
reduced to normal, disconnect the hose from the cylinder. Liquid tube
Close

Evacuation Fig. 6-4


(1) Attach the charge hose end described in the preceding
steps to the vacuum pump to evacuate the tubing and
indoor unit. Confirm that the “Lo” knob of the manifold
valve is open. Then, run the vacuum pump. The operation
time for evacuation varies with the tubing length and CAUTION
capacity of the pump. The following table shows the
Use a cylinder designed for use with R410A respectively.
amount of time for evacuation:
Required time for evacuation Charging additional refrigerant
when 30 gal/h vacuum pump is used
● Charging additional refrigerant (calculated from the liquid
If tubing length is If tubing length is
less than 15 m longer than 15 m tube length as shown in Section 1-7 “Additional Refrigerant
45 min. or more 90 min. or more Charge”) using the liquid tube service valve. (Fig. 6-5)
● Use a balance to measure the refrigerant accurately.
NOTE ● If the additional refrigerant charge amount cannot be
The required time in the above table is calculated based on the charged at once, charge the remaining refrigerant in liquid
assumption that the ideal (or target) vacuum condition is less form by using the gas tube service valve with the system in
than –101 kPa (–755 mmHg, 5 Torr). cooling operation mode at the time of test run. (Fig. 6-6)
(2) When the desired vacuum is reached, close the “Lo”
knob of the manifold valve and turn off the vacuum pump.
Confirm that the gauge pressure is under –101 kPa
(–755 mmHg, 5 Torr) after 4 to 5 minutes of vacuum pump
operation. (Fig. 6-4)

23

Mini_VRF_eng.indd 23 2011/08/26 13:45:21


Manifold valve
7. TEST RUN
7-1. Preparing for Test Run
● Before attempting to start the air conditioner, check the
Lo Hi
following points.
Pressure (1) All loose matter is removed from the cabinet especially
gauge
steel filings, bits of wire, and clips.
Valve
(2) The control wiring is correctly connected and all electrical
connections are tight.
(3) The transportation pads for the indoor fan have been
removed. If not, remove them now.
(4) The power has been supplied to the unit for at least 5
hours before starting the compressor. The bottom of
Liquid the compressor should be warm to the touch and the
crankcase heater around the feet of the compressor should
be hot to the touch. (Fig. 7-1)
R410A
Close
ON
Gas tube
(Power must be turned ON at least
Close Outdoor unit 5 hours before attempting test run)

Open
Liquid tube
Power mains switch
Close Fig. 7-1
Fig. 6-5
(5) Both the gas and liquid tube service valves are open.
If not, open them now. (Fig. 7-2)

Open

Gas tube
Open Liquid tube service cap
Outdoor unit Gas tube service cap
Close
Fig. 7-2
Liquid tube
(6) Request that the customer be present for the test run.
Open Explain the contents of the instruction manual, and then
have the customer actually operate the system.
Fig. 6-6 (7) Be sure to give the instruction manual and warranty
certificate to the customer.
Finishing the job (8) When replacing the control PCB, be sure to make all the
(1) With a hex wrench, turn the liquid tube service valve stem same settings on the new PCB as were in use before
counterclockwise to fully open the valve. replacement.
The existing EEPROM is not changed, and is connected to
(2) Turn the gas tube service valve stem counterclockwise to
the new control PCB.
fully open the valve.

CAUTION
To avoid gas from leaking when removing the charge hose,
make sure the stem of the gas tube is turned all the way
out.
(3) Loosen the charge hose connected to the gas tube service
port (for ø 7.94 mm tube) slightly to release the pressure,
then remove the hose.
(4) Replace the service port cap on the gas tube service port
and fasten the cap securely with an adjustable wrench or
box wrench. This process is very important to prevent gas
from leaking from the system.
(5) Replace the valve caps at both gas tube and liquid tube
service valves and fasten them securely.
This completes air purging with a vacuum pump. The air
conditioner is now ready for a test run. Refer to Section
“7. TEST RUN”.

24

Mini_VRF_eng.indd 24 2011/08/26 13:45:22


7-2. Test Run Procedure
Items to Check Before the Test Run
1. Turn the remote power switch on at least 5 hours before the test, in order to energize the crankcase heater.
2. Turn the outdoor service valves (2 locations) to the full-open positions.
● Use caution when making the settings.
If there are duplicated system addresses, or if the settings for the Nos. of the indoor units are not consistent, an alarm will occur
and the system will not start.
● These settings are not made on the indoor unit PCB.

Recheck the items to check before the test run.

<Outdoor unit control PCB>


Unit No. setting switch Set the No. of indoor units.
(S004)

(Check the link wiring.)


Are the inter-unit control wires NO CASE 1
connected to more than 1 refrigerant
system?

<Outdoor unit control PCB>


YES
Unit No. setting switch Set the system address.
(S002 and S003) Each system to be a unique number.

When multiple outdoor units exist, disconnect the terminals extended


Refer to Figs. 7-4, -5 from the shorted plugs (CN-TERMINAL) at all outdoor main unit PCBs
except for 1. Alternatively, move the sockets to the OPEN side.

Is it possible to turn ON the power only YES CASE 2


for the 1 refrigerant system where the
test run will be performed?
Turn ON the indoor and
outdoor unit power for that
NO refrigerant system only.

Will automatic address setting be performed Make necessary corrections. Short-circuit the automatic address pin
NO in Heating mode? (CN-A.ADD) on the outdoor unit PCB
for 1 second or longer, then release it.
YES Turn OFF the indoor and
CASE 3B CASE 3A outdoor unit power.
LED 1 and 2 blink alternately
Is it OK to start the compressors? Is it OK to start the compressors? (about 2 or 3 minutes).
Check the alarm contents.

Turn ON the indoor and Turn ON the indoor and


outdoor unit power. outdoor unit power. NO Are LEDs 1 and 2 on the
*2 *2 Make necessary
corrections Refer to “Table of outdoor unit PCB OFF?
Short-circuit the cooling side of the
mode change 3P pin (CN-MODE) on Short-circuit the automatic Self-Diagnostic Functions
the outdoor main unit PCB. At the address pin (CN-A.ADD) on the and Description of Alarm
outdoor unit PCB for 1 second Turn OFF the indoor Displays.” YES
same time, short-circuit the automatic
address pin (CN-A.ADD) for 1 second or longer, then release it. *1 and outdoor unit
or longer, then pull it out. *1
*3 *3
Start indoor and outdoor unit Start indoor and outdoor unit
Check the alarm
cooling operation. LED 1 and heating operation. LED 1
contents.
2 blink alternately. and 2 blink alternately.

Are LEDs 1 and 2 on the outdoor NO


unit PCB OFF?

YES

Check that test run preparation is OK.


(Do not allow the short-circuited pins to remain short-circuited.)

Set the wired remote controller for test run.

Refer to the remote Does system operate?


NO Check and make corrections according to
controller test-run “Table of Self-Diagnostic Functions.”
settings. YES
Return remote control to normal mode
*1 Use a flathead screwdriver to short-circuit the pin on the PC board.
End test run. *2 A minimum of 5 hours must have passed after the power was turned ON to
the outdoor unit.
*3 All indoor units operate in all refrigerant systems where the power is ON.

Fig. 7-3

25

Mini_VRF_eng.indd 25 2011/08/26 13:45:22


7-3. Outdoor Unit PCB Setting

(for single-phase outdoor unit PCB)

S004

D303
(LED2)
CN-A.ADD

D302
(LED1)
CN-MODE

S003

S002

CN-TERMINAL

(for 3-phase outdoor unit PCB)

S004

D303
(LED2)
CN-A.ADD

D302
(LED1)
CN-MODE

S003

S002

CN-TERMINAL Fig. 7-4


26

Mini_VRF_eng.indd 26 2011/08/26 13:45:22


● Examples of the No. of indoor units settings 7-4. Auto Address Setting
Indoor unit setting (S004) Basic wiring diagram: Example (1)
No. of indoor units
(Rotary switch, gray)
• If link wiring is not used
(The inter-unit control wires are not connected to multiple
1 unit (factory setting) set to 1
refrigerant systems.)
Indoor unit addresses can be set without operating the
2 units set to 2 compressors.

No. 1 unit settings


System address No. of indoor units
(system 1 setting) (8 units setting)
(S003) (S002) (S004)
ON ON
9 units set to 9

8
1 2 OFF

● Examples of refrigerant circuit (R.C.) address settings


(required when link wiring is used)
System address System address Outdoor Unit
System address
(S003) (S002) Unit No. 1
No.
(2P DIP switch, black) (Rotary switch, yellow)
Both OFF
ON ON Inter-unit control wiring
System 1 (factory setting) set to 1

1 2 OFF

1 ON Indoor Unit 1-1 1-2 1-3 1-8


ON ON
System 11 set to 1 Remote controller
Remote communication wiring
controller
1 2 OFF
Fig. 7-6
2 ON (1) Automatic Address Setting from the Outdoor Unit
ON ON
System 21 set to 1 1 On the outdoor unit control PCB, check that the system
address rotary switch (S002) is set to “1” and that the DIP
1 2 OFF switch (S003) is set to “0”.
ON ON
1&2 ON
ON ON
System 30 set to 0 OFF
1 2
1 2 OFF (These are the settings at the time of factory shipment.)
2 To set the number of indoor units that are connected to the
outdoor unit to 8 on the outdoor unit control PCB, set the
No. of indoor units rotary switch (S004) to “8”.
3 Turn ON the power to the indoor and outdoor units.
4 On the outdoor unit control PCB, short-circuit the automatic
address pin (CN-A.ADD) for 1 second or longer, then
release it.

(Communication for automatic address setting begins.)

* To cancel, again short-circuit the automatic
address pin (CN-A.ADD) for 1 second or
longer, then pull it out.
The LED that indicates that automatic address
setting is in progress turns OFF and the
process is stopped.

(Automatic address setting is completed when LEDs 1 and


2 on the outdoor unit control PCB turn OFF.)

5 Operation from the remote controllers is now possible.

* To perform automatic address setting from the remote


controller, perform steps 1 to 3, then use the remote
controller and complete automatic address setting.
Refer to “Automatic Address Setting from the Remote
Controller.”

27

Mini_VRF_eng.indd 27 2011/08/26 13:45:23


Basic wiring diagram: Example (2) <Case 2> Automatic Address Setting (no compressor
• If link wiring is used operation)
* When multiple outdoor units exist, remove the socket that is ● Indoor and outdoor unit power can be turned ON for each
used to short-circuit the terminal plug (CN-TERMINAL) from system separately.
all outdoor unit PCBs except for 1. Alternatively, move the Indoor unit addresses can be set without operating the
sockets to the “OPEN” side. compressors.
Automatic Address Setting from Outdoor Unit
No. 1 unit settings 1 On the outdoor unit control PCB, check that the system
address rotary switch (S002) is set to “1” and that the DIP
System address No. of indoor units
(system 1 setting) (6 units setting) switch (S003) is set to “0”.
(S004) ON ON
(S003) (S002)
ON ON
6
1 2 1 2 OFF
OFF
(These are the settings at the time of factory shipment.)
2 To set the number of indoor units that are connected to the
Leave the socket outdoor unit to 6 on the outdoor unit control PCB, set the
Outdoor unit Unit that is used to No. of indoor units rotary switch (S004) to “6”.
system 1 No. 1 short-circuit the
terminal plug.
(CN-TERMINAL) 3 At the outdoor unit where all indoor and outdoor unit power
has been turned ON, short-circuit the automatic address
Inter-unit control wiring pin (CN-A.ADD) for 1 second or longer, then pull it out.

(Communication for automatic address setting begins.)
Indoor unit ↓
1-1 1-2 1-3 1-6
* To cancel, again short-circuit the automatic
address pin (CN-A.ADD) for 1 second or
Remote
controller Remote controller longer, then pull it out.
communication wiring
The LED that indicates automatic address
No. 2 unit settings setting is in progress turns OFF and the
process is stopped.
System address No. of indoor units
(system 2 setting) (7 units setting) (Automatic address setting is completed when LEDs 1 and
(S002) (S003)
ON ON (S004) 2 on the outdoor unit control PCB turn OFF.)

7

1 2
OFF 4 Next turn the power ON only for the indoor and outdoor
units of the next (different) system. Repeat steps 1 – 3 in
the same way to complete automatic address settings for
Leave the socket all systems.
Outdoor unit Unit that is used to ↓
system 2 No. 1 open circuit the 5 Operation from the remote controllers is now possible.
terminal plug
(CN-TERMINAL). * To perform automatic address setting from the remote
controller, perform steps 1 and 2, then use the remote
Inter-unit control wiring controller complete automatic address setting.
Refer to “Automatic Address Setting from the Remote
Controller.”
To other system Indoor unit 2-1 2-2 2-7
link wiring

Remote
Remote controller
controller
communication wiring

Make settings as appropriate for the cases listed below.

Indoor and outdoor unit power can be


turned ON for each system separately. <Case 2>

Indoor and outdoor unit power cannot


be turned ON for each system separately.
Automatic address setting in Heating mode <Case 3A>

Automatic address setting in Cooling mode <Case 3B>


Fig. 7-7

28

Mini_VRF_eng.indd 28 2011/08/26 13:45:24


<Case 3A> Automatic Address Setting in Heating Mode <Case 3B> Automatic Address Setting in Cooling Mode
● Indoor and outdoor unit power cannot be turned ON for each ● Indoor and outdoor unit power cannot be turned ON for each
system separately. system separately.
In the following, automatic setting of indoor unit addresses is In the following, automatic setting of indoor unit addresses is
not possible if the compressors are not operating. Therefore not possible if the compressors are not operating. Therefore
perform this process only after completing all refrigerant perform this process only after completing all refrigerant
tubing work. tubing work.
Automatic Address Setting from Outdoor Unit Automatic address setting can be performed during Cooling
operation.
1 Perform steps 1 and 2 in the same way as for <Case 2> .
Automatic Address Setting from Outdoor Unit
2 Turn the indoor and outdoor unit power ON at all systems. 1 Perform steps 1 and 2 in the same way as for <Case 2> .

3 To perform automatic address setting in <Heating mode>, 2 Turn the indoor and outdoor unit power ON at all systems.
on the outdoor unit control PCB in the refrigerant system ↓
where you wish to set the addresses, short-circuit the
automatic address pin (CN-A.ADD) for 1 second or longer, 3 To perform automatic address setting in <Cooling mode>,
then pull it out. on the outdoor unit control PCB in the refrigerant system
(Be sure to perform this process for one system at a time. where you wish to set the addresses, short-circuit the
Automatic address settings cannot be performed for more cooling side of the mode change 3P pin (CN-MODE). At
than one system at the same time.) the same time, short-circuit the automatic address pin
↓ (CN-A.ADD) for 1 second or longer, then pull it out. (Be
(Communication for automatic address setting begins, the sure to perform this process for one system at a time.
compressors turn ON, and automatic address setting Automatic address settings cannot be performed for more
in heating mode begins.) than one system at the same time.)
(All indoor units operate.) ↓
↓ (Communication for automatic address setting begins, the
* To cancel, again short-circuit the automatic compressors turn ON, and automatic address setting
address pin (CN-A.ADD) for 1 second or in Cooling mode begins.)
longer, then pull it out. (All indoor units operate.)
The LED that indicates automatic address ↓
setting is in progress turns OFF and the * To cancel, again short-circuit the automatic
process is stopped. address pin (CN-A.ADD) for 1 second or
longer, then pull it out.
The LED that indicates automatic address
(Automatic address setting is completed when the
setting is in progress turns OFF and the
compressors stop and LEDs 1 and 2 on the outdoor unit
process is stopped.
control PCB turn OFF.)

4 At the outdoor unit in the next (different) system, short- (Automatic address setting is completed when the
circuit the automatic address pin (CN-A.ADD) for 1 second compressors stop and LEDs 1 and 2 on the outdoor unit
or longer, then pull it out. control PCB turn OFF.)
↓ ↓
(Repeat the same steps to complete automatic address 4 At the outdoor unit in the next (different) system, short-
setting for all units.) circuit the automatic address pin (CN-A.ADD) for 1 second
↓ or longer, then pull it out.
5 Operation from the remote controllers is now possible. ↓
(Repeat the same steps to complete automatic address
* To perform automatic address setting from the remote setting for all units.)
controller, perform steps 1 and 2, then use the remote ↓
controller complete automatic address setting. 5 Operation from the remote controllers is now possible.
Refer to “Automatic Address Setting from the Remote
Controller.” * Automatic address setting in Cooling mode cannot be
done from the remote controller.

29

Mini_VRF_eng.indd 29 2011/08/26 13:45:25


Automatic Address Setting from the Remote Controller* Display during automatic address setting
Selecting each refrigerant system individually for automatic ● On outdoor unit PCB
address setting
LED 2 1
---Automatic address setting for each system: Item code “A1”
● Press the remote controller timer time button and
button at the same time. (Press and hold for 4 seconds or Blink alternately
longer.)
● Next, press either the temperature setting or * Do not short-circuit the automatic address setting pin
button. (CN-A.ADD) again while automatic address setting is in
(Check that the item code is “A1.”) progress. Doing so will cancel the setting operation and
will cause LEDs 1 and 2 to turn OFF.
● Use either the or button to set the system
No. to perform automatic address setting. * When automatic address setting has been successfully
completed, both LEDs 1 and 2 turn OFF.
● Then press the button.
(Automatic address setting for one refrigerant system * LED 1 is D302. LED 2 is D303.
begins.) * If automatic address setting is not completed
(When automatic address setting for one system is successfully, refer to the table below and correct the
completed, the system returns to normal stopped status.) problem. Then perform automatic address setting again.
<Approximately 4 – 5 minutes is required.>
● Display details of LEDs 1 and 2 on the outdoor unit control
(During automatic address setting, “ ” is displayed
on the remote controller. This message disappears when PCB
automatic address setting is completed.) ( : ON : Blinking ● : OFF)
● Repeat the same steps to perform automatic address setting LED 1 LED 2 Display meaning
for each successive system.
After the power is turned ON (and automatic address
setting is not in progress), no communication with the
indoor units in that system is possible.
After the power is turned ON (and automatic address
● setting is not in progress), 1 or more indoor units are
confirmed in that system; however, the number of
indoor units does not match the number that was set.

Automatic address setting is in progress.


Alternating
● ● Automatic address setting completed.
At time of automatic address setting, the number
of indoor units did not match the number that was
Simultaneous set. (when indoor units are operating) indication
appears on the display.

Refer to Table of Self-Diagnostic Functions and


Alternating Description of Alarm Displays.

Note: indicates that the solenoid is fused or that there is a


CT (current detection circuit) failure (current is detected
when the compressor is OFF).
● Remote controller display during automatic setting

is blinking

30

Mini_VRF_eng.indd 30 2011/08/26 13:45:25


Request concerning recording the indoor/outdoor Remote Controller Test Run Settings
unit combination Nos. 1 Press the remote controller button for 4 seconds or
After automatic address setting has been completed, be sure to longer. Then press the button.
record them for future reference. ● “TEST” appears on the LCD display while the test run is
List the outdoor unit system address and the addresses of the in progress.
indoor units in that system in an easily visible location (next ● The temperature cannot be adjusted when in Test Run
to the nameplate), using a permanent marking pen or similar mode.
means that cannot be erased easily. (This mode places a heavy load on the machines.
Example: (Outdoor) 1 – (Indoor) 1-1, 1-2, 1-3… Therefore use it only when performing the test run.)
(Outdoor) 2 – (Indoor) 2-1, 2-2, 2-3… 2 The test run can be performed using the HEAT, COOL, or
FAN operation modes.
These numbers are necessary for later maintenance. Please be Note: The outdoor units will not operate for approximately
sure to indicate them. 3 minutes after the power is turned ON and after
Checking the indoor unit addresses operation is stopped.
3 If correct operation is not possible, a code is displayed on
Use the remote controller to check the indoor unit address.
the remote controller display.
<If 1 indoor unit is connected to 1 remote controller> (Refer to “7-6. Meaning of Alarm Messages” and correct
the problem.)
1 Press and hold the button and button for 4
seconds or longer (simple settings mode). 4 After the test run is completed, press the button
again. Check that “TEST” disappears from the remote
2 The address is displayed for the indoor unit that is
controller display.
connected to the remote controller.
(To prevent continuous test runs, this remote controller
(Only the address of the indoor unit that is connected to
includes a timer function that cancels the test run after 60
the remote controller can be checked.)
minutes.)
3 Press the button again to return to normal remote * If the test run is performed using the wired remote
controller mode. controller, operation is possible even if the cassette-type
ceiling panel has not been installed. (“P09” display does
not occur.)

7-5. Caution for Pump Down


Pump down means refrigerant gas in the system is returned
to the outdoor unit. Pump down is used when the unit is to be
moved, or before servicing the refrigerant circuit.

CAUTION
Number changes to indicate which ● This outdoor unit cannot collect more than the rated
indoor unit is currently selected.
refrigerant amount as shown by the nameplate on the
Indoor unit address
back.
<If multiple indoor units are connected to 1 remote ● If the amount of refrigerant is more than that
controller (group control)> recommended, do not conduct pump down. In this case,
use another refrigerant collecting system.
1 Press and hold the button and button for 4
seconds or longer (simple settings mode).
2 “ALL” is displayed on the remote controller.
3 Next, press the button.
4 The address is displayed for 1 of the indoor units which is
connected to the remote controller. Check that the fan of
that indoor unit starts and that air is discharged.
5 Press the button again and check the address of
each indoor unit in sequence.
6 Press the button again to return to normal remote
controller mode.

Number changes to indicate which


indoor unit is currently selected.
Indoor unit address

31

Mini_VRF_eng.indd 31 2011/08/26 13:45:27


7-6. Meaning of Alarm Messages Possible cause of malfunction
Alarm
message
Table of Self-Diagnostics Functions and Description of
Improper setting. This alarm message shows
Alarm Displays when the indoor unit for
L02
Alarm messages are indicated by the blinking of LED 1 and 2 multiple-use is not connected
(D302, D303) on the outdoor unit PCB. They are also displayed to the outdoor unit.
on the wired remote controller. Duplication of main indoor
unit address setting in group <L03>
● Viewing the LED 1 and 2 (D302 and D303) alarm displays control.
Duplication of outdoor R.C.
L04

Serial communication errors⁄Mis-setting


LED 1 LED 2 Alarm contents address setting.
Alarm display There are Priority set
LED 1 blinks M times, then LED 2 blinks N 2 or more remote
indoor units controller L05
times. The cycle then repeats.
M = 2: P alarm 3: H alarm 4: E alarm controllers
5: F alarm 6: L alarm which have
N = Alarm No. operation Non-priority
Alternating Example: LED 1 blinks 2 times, then mode priority set remote
controller L06
LED 2 blinks 17 times. The cycle then in 1 refrigerant
repeats. Alarm is “P17”. circuit.
Group control wiring is
( : Blinking) connected to individual control L07
indoor unit.
Alarm Indoor unit address is not set. L08
Possible cause of malfunction
message
Capacity code of indoor unit is
Remote controller Error in receiving serial <<L09>>
not set.
is detecting error communication signal. (Signal
signal from indoor from main indoor unit in case of <E01> Capacity code of outdoor unit
L10
unit. group control) Ex: Auto address is not set.
is not completed. Mis-matched connection of
Error in transmitting serial outdoor units which have L17
<E02> different kinds of refrigerant.
communication signal.
Indoor unit is detecting error signal from remote 4-way valve operation failure L18
<<E03>>
controller (and system controller). Protective device Thermal protector in indoor unit
<<P01>>
Indoor unit is Error in receiving serial in outdoor unit is fan motor is activated.
detecting error communication signal. When activated.
Improper wiring connections of
signal from main turning on the power supply, <<P09>>
ceiling panel.
outdoor unit. the number of connected indoor E04
units does not correspond to Float switch is activated. <<P10>>
the number set. (Except R.C. Operation of protective function
address is “0”.) <<P12>>
of fan inverter
Error of the outdoor unit in Compressor thermal protector
receiving serial communication <E06> is activated.
signal from the indoor unit. Power supply voltage is
P02
Improper setting Indoor unit address setting is unusual. (The voltage is more
E08 than 260 V or less than 160 V
of indoor unit or duplicated.
Activation of protective device

remote controller. between L and N phase.)


Remote controller address
Serial communication errors⁄Mis-setting

connector (RCU. ADR) is Protective device Incorrect discharge


<<E09>> P03
duplicated. (Duplication of main in outdoor unit is temperature. (Comp. No. 1)
remote controller) activated.
Power supply circuit failure,
P05
During auto Starting auto address setting is missing-phase detection.
address setting, prohibited. Forgot to open service valve P13
number of This alarm message shows that
connected the auto address connector E12 O2 sensor (detects low oxygen
P14
units does not CN-A.ADD is shorted while level) activated.
correspond to other RC line is executing auto Compressor running failure
number set. address operation. resulting from missing phase
Error in auto address setting. in the compressor wiring, etc. P16
When turning (Start failure not caused by
(Number of connected indoor
on the power E15 IPM or no gas.)
units is less than the number
supply, number
set) Outdoor unit fan motor is
of connected P22
units does not Error in auto address setting. unusual.
correspond to (Number of connected indoor IPM trip (IPM current or
E16 H31
number set. units is more than the number temperature)
(Except R.C. set)
address is “0”.) Missing-phase/reverse-phase
No indoor unit is connected in the compressor wiring,
E20
during auto address setting. Compressor start-up failure P29
Main outdoor unit is detecting (Overcurrent at time of INV
error signal from sub outdoor E24 compressor starts up, etc.)
unit. continued
Error of outdoor unit address
E25
setting.
The number of connected main
and sub outdoor units do not
E26
correspond to the number set
at main outdoor unit PCB.
Error of sub outdoor unit in
receiving serial communication E29
signal from main outdoor unit.
Indoor unit Error of main indoor unit in
communication receiving serial communication
E18
error of group signal from sub indoor units.
control wiring.
32

Mini_VRF_eng.indd 32 2011/08/26 13:45:28


Possible cause of malfunction
Alarm
message
8. MARKINGS FOR DIRECTIVE 97/23/EC
Indoor thermistor Indoor coil temp. sensor (E1) <<F01>> (PED)
is either open or
Indoor coil temp. sensor (E2) <<F02>>
damaged. Rating nameplate figure
Indoor coil temp. sensor (E3) <<F03>>
Indoor suction air (room) temp.
<<F10>>
sensor (TA)
Indoor discharge air temp. Multi Type Air Conditioner
<<F11>> Сплит Система ᵫᶍᶂᶃᶊᴾᵬᶍᵌ ᵟᴾᵘᴾModel Name Various
sensor (BL) Кондиционер Мульти
Мульти‒Сплит
Thermistor fault

Кондиціонер Мульти
Мульти‒спліт
спліт система ɎɯɤɵɵɫɤɽɬɶɿϨ
Outdoor Compressor No. 1 discharge
F04 㻼㻻㼃㻱㻾㻌㻿㻻㼁㻾㻯㻱㻌䠖㻌 ᵠᴾᵘᴾVarious
thermistor is either gas temp. sensor (TD)
open or damaged. 㻹㻭㼄㻌㻱㻸㻱㻯㼀㻾㻵㻯㻌㻵㻺㻼㼁㼀㻌 ᵡᴾᵘᴾ 㼗㼃 㻭 㼂㼍㼞㼕㼛㼡㼟
Outdoor No. 1 coil gas temp. 㼀㻵㻹㻱㻌㻰㻱㻸㻭㼅㻌㻲㼁㻿㻱㻌㻹㻭㼄㻌㻿㻵㼆㻱㻌㻦 ᵢᴾᵘᴾ 㻭 㼂㼍㼞㼕㼛㼡㼟
F06
sensor (EXG1) 㼁㻺㻵㼀㻌㻼㻾㻻㼀㻱㻯㼀㻵㻻㻺㻌㻦㻌㻵㻼㼄㻠
Outdoor No. 1 coil liquid temp. 㻻㼜㼑㼞㼍㼠㼕㼚㼓㻌㻿㼜㼑㼏㻚㻌㻭㼞㼑㼍㻌
F07 㼂㼍㼞㼕㼛㼡㼟㻌㻌㻌
sensor (C1) 㻔㻺㼛㼠㻌㼒㼛㼞㻌㼠㼔㼑㻌㻼㻱㻰㻕
Outdoor air temp. sensor (TO) F08
Compressor intake port
F12 㻹 㻭 㼄 㻚 㼃 㻻 㻾 㻷 㻵 㻺 㻳 㻌 㻼 㻾 㻱 㻿 㻿 㼁 㻾 㻱 㻌 㻦 㻴 㻵 㻳 㻴 㻌 㻿 㻵 㻰 㻱 ᵣᴾᵘᴾ 㻹㻼㼍㻌㼂㼍㼞㼕㼛㼡㼟
temperature sensor (TS)
㻸 㻻 㼃 㻌 㻌 㻿 㻵 㻰 㻱 ᵤᴾᵘᴾ 㻹㻼㼍㻌㼂㼍㼞㼕㼛㼡㼟
High pressure sensor failure F16 㻾 㻱 㻲 㻾 㻵 㻳 㻱 㻾 㻭 㻺 㼀 㻦 㻌 㻾 㻠 㻝 㻜 㻭 ᵥᴾᵘᴾ 㼗㼓 㼂㼍㼞㼕㼛㼡㼟
㻺㻱㼀䚷㼃㻱㻵㻳㻴㼀䠖 㼂㼍㼞㼕㼛㼡㼟㻌㻔㻺㼛㼠㻌㼒㼛㼞㻌㼠㼔㼑㻌㻼㻱㻰㻕
Low pressure sensor failure F17
EEPROM on indoor unit PCB failure F29 㻿㻱㻾㻵㻭㻸㻌㻌㻺㻻㻚㻌㻌㻦㻌㻌㻌㻌㼂㼍㼞㼕㼛㼡㼟 㻼㻾㻻㻰㻚㻌㻰㻭㼀㻱㻌㻌㻦 㻹㻹㻙㼅㼅㼅㼅
Серийный номер.㻌㻦㻌 㻙 㻙 㻙 㻙 㻙 㻙 㻙 Дата производства : 㻹㻹㻙㼅㼅㼅㼅㻌㻌
Protective device EEPROM on the outdoor unit Серійний номер.㻌㻦㻌㻌㻌㻌
F31 Дата виготовлення :
for compressor PCB is a failure.
No. 1 is activated. THE CAPACITY, CURRENT AND POWER INPUT ARE FOR THIS UNIT CONNECTED TO THE
Protective device for compressor is activated

Overcurrent of power supply FOLLOWING INDOOR UNITS.


H01
current (CT) sensor ПРОИЗВОДИТЕЛЬНОСТЬ, ТОК И ПОТРЕБЛЯЕМАЯ МОЩНОСТЬ ДАННОГО БЛОКА ПРИ
ЕГО ПОДКЛЮЧЕНИИ К СЛЕДУЮЩИМ ВНУТРЕННИМ БЛОКАМ.
PAM failure H02 ПРОДУКТИВНІСТЬ, СТРУМ ТА СПОЖИВАНА ПОТУЖНІСТЬ ДАНОГО БЛОКУ ПРИ ЙОГО
ПІДКЛЮЧЕННІ ДО НАСТУПНИХ ВНУТРІШНІХ БЛОКІВ.
Power supply current (CT) 4-Way Cassette, 56 type × 2 /4-сторонняя кассета, 56 тип × 2 /4-стороння касета, 56 тип × 2
sensor failure (Current is not
H03 FOR OTHER COMBINATIONS, REFER TO MANUAL.
detected at time of compressor ИНФОРМАЦИЮ ПО ДРУГИМ КОМБИНАЦИЯМ СМОТРИТЕ В ИНСТРУКЦИИ.
ON.) ЗА ІНФОРМАЦІЄЮ СТОСОВНО ІНШИХ КОМБІНАЦІЙ ЗВЕРТАЙТЕСЯ ДО ІНСТРУКЦІЇ.
㻭㼡㼠㼔㼛㼞㼕㼦㼑㼐㻌㼞㼑㼜㼞㼑㼟㼑㼚㼠㼍㼠㼕㼢㼑㻌㼕㼚㻌㻱㼁 㻼㼍㼚㼍㼟㼛㼚㼕㼏㻌㻹㼍㼞㼗㼑㼠㼕㼚㼓㻌㻱㼡㼞㼛㼜㼑㻌㻳㼙㼎㻴
Discharge gas temperature 㻼㼍㼚㼍㼟㼛㼚㼕㼏㻌㼀㼑㼟㼠㼕㼚㼓㻌㻯㼑㼚㼠㼞㼑 㼃㼕㼚㼟㼎㼑㼞㼓㼞㼕㼚㼓㻌㻝㻡㻘㻌㻞㻞㻡㻞㻡㻌㻴㼍㼙㼎㼡㼞㼓㻘㻌㻳㼑㼞㼙㼍㼚㼥
of the comp. No. 1 is not Made in China
detected. H05 Panasonic Corporation Сделано в Китае
Вироблено в Китаї
Temp. sensor is not seated at 㻝㻜㻜㻢㻌㻷㼍㼐㼛㼙㼍㻘㻌㻷㼍㼐㼛㼙㼍㻌㻯㼕㼠㼥㻌㻻㼟㼍㼗㼍㻘㻌㻶㼍㼜㼍㼚 Fabricado en China
the sensor holder.
Low pressure switch is
H06
activated. Tabulation of Various data
Low oil level. H07 A U-4LE1E5 U-5LE1E5 U-6LE1E5
Oil sensor fault. Comp. No. 1 oil sensor B 220 – 240 V ~ 50 Hz
(Disconnection, H08
etc) C 4.84 kW, 21.0 A 5.64 kW, 24.5 A 6.45 kW, 28.0 A
Alarm messages displayed on system controller D 25 A 35 A 35 A
Serial communication errors⁄

Error in Indoor or main outdoor unit is E 3.80 MPa


transmitting serial not operating correctly.
communication Mis-wiring of control wiring F 2.70 MPa
C05
signal between indoor unil, main
G 3.5 kg 3.5 kg 3.5 kg
Mis-setting

outdoor unit and system


controller.
A U-4LE1E8 U-5LE1E8 U-6LE1E8
Error in Indoor or main outdoor unit is
receiving serial not operating correctly. Mis- B 380 – 415 V ~ 50 Hz
communication wiring of control wiring between
C06 C 5.62 kW, 8.5 A 6.61 kW, 10.0 A 7.94 kW, 12.0 A
signal indoor unit, main outdoor unit
and system controller. D 20 A 20 A 20 A
CN1 is not connected properly.
Protective device When using wireless remote E 3.80 MPa
protective device

of sub indoor unit controller or system controller,


Activation of

F 2.70 MPa
in group control is in order to check the alarm
activated. message in detail, connect P30 G 3.5 kg 3.5 kg 3.5 kg
wired remote controller to
indoor unit temporarily.

NOTE
1. Alarm messages in << >> do not affect other indoor unit
operations.
2. Alarm messages in < > sometimes affect other indoor unit
operations depending on the fault.

33

Mini_VRF_eng.indd 33 2011/08/26 13:45:28


Compliance with regulation 842/EC/2006 Article 7(1) requirements
DO NOT VENT R410A INTO THE ATMOSPHERE: R410A IS A FLUORINATED GREENHOUSE GAS,
EN COVERED BY THE KYOTO PROTOCOL, WITH A GLOBAL WARMING POTENTIAL (GWP) = 1975.

Conformité aux exigences de l’article 7 (1) de la réglementation 842/EC/2006


NE PAS METTRE LE R410A À L’AIR LIBRE: LE R410A EST UN GAZ À EFFET DE SERRE FLUORÉ,
FR RÉGULÉ PAR LE PROTOCOLE DE KYOTO AVEC UN POTENTIEL DE RÉCHAUFFEMENT DE LA PLANÈTE (GWP) = 1975.

Kompatibilität mit den Anforderungen der Vorschrift 842/EC/2006, Artikel 7 (1)


R410A NICHT IN DIE AUSSENLUFT ABLASSEN: R410A IST EIN FLUORIERTES TREIBHAUSGAS, DAS IM
DE KYOTO-PROTOKOLL ENTHALTEN IST UND EIN ERDERWÄRMUNGSPOTENTIAL (GWP) VON 1975 AUFWEIST.

Osservanza delle richieste dell’Articolo 7(1) delle regolamentazioni 842/EC/2006


NON DISPERDERE R410A NELL’ATMOSFERA: L’R410A È UN GAS FLUORATO CAUSA DI EFFETTO SERRA E
IT COPERTO DAL PROTOCOLLO DI KYOTO CON UN POTENZIALE DI RISCALDAMENTO GLOBALE (GWP) = 1975.

Conformidade com o regulamento 842/EC/2006 Requisitos do Artigo 7(1)


NÃO DEIXE O R410A ESCAPAR PARA A ATMOSFERA: O R410A É UM GÁS FLUORADO COM EFEITO DE ESTUFA,
PT REGULADO PELO PROTOCOLO DE QUIOTO, COM UM POTENCIAL DE AQUECIMENTO GLOBAL (GWP) = 1975.

Συμμόρϕωση με τις απαιτήσεις του κανονισμού 842/EC/2006 Άρθρο 7(1)


ΜΗΝ ΑΠΕΛΕΥΘΕΡΩΣΕΤΕ ΤΟ R410A ΣΤΗΝ ΑΤΜΟΣΦΑΙΡΑ: ΤΟ R410A ΕΙΝΑΙ ΦΘΟΡΙΟΥΧΟ ΑΕΡΙΟ ΘΕΡΜΟΚΗΠΙΟΥ ΠΟΥ
GR ΚΑΛΥΠΤΕΤΑΙ ΑΠΟ ΤΟ ΠΡΩΤΟΚΟΛΛΟ ΤΟΥ ΚYΟΤΟ, ΜΕ ΔΥΝΑΜΙΚΟ ΠΛΑΝΗΤΙΚΗΣ ΑΥΞΗΣΗΣ ΤΗΣ ΘΕΡΜΟΚΡΑΣΙΑΣ (GWP) = 1975.

Cumplimiento de los requisitos del Artículo 7 (1) de la Directiva 842/EC/2006


NO LIBERAR R410A AL AIRE LIBRE: EL R410A ES UN GAS FLUORIZADO DE EFECTOS DE INVERNADERO,
ES INCLUIDO EN EL PROTOCOLO DE KYOTO, CON UN POTENCIAL DE CALENTAMIENTO GLOBAL (GWP) = 1975.

Voldoet aan de eisen van regeling 842/EC/2006 artikel 7(1)


LAAT R410A NIET ONSNAPPEN IN DE DAMPKRING: R410A IS EEN FLUORHOUDEND BROEIKASGAS ZOALS
NL BEDOELD IN HET KYOTO PROTOCOL, MET EEN AARDOPWARMINGSVERMOGEN (GWP) = 1975.

Съответствие с изискванията на 842/EC/2006 член 7(1)


НЕ ИЗПУСКТАЙТЕ R410A В АТМОСФЕРАТА: R410A Е ПАРНИКОВ ГАЗ, СЪДЪРЖАЩ ФЛУОР, ВКЛЮЧЕН В
BL ПРОТОКОЛА ОТ КИОТО С ПОТЕНЦИАЛ ЗА ГЛОБАЛНО ЗАТОПЛЯНЕ (GWP) = 1975.

Соответствие требованиям Статьи 7(1) правил 842/EC/2006


НЕ ДОПУСКАЙТЕ ВЫБРОСОВ R410A В АТМОСФЕРУ: R410A ЯВЛЯЕТСЯ ФТОРИРОВАННЫМ ПАРНИКОВЫМ ГАЗОМ,
RU ОХВАТЫВАЕМЫМ КИОТСКИМ ПРОТОКОЛОМ, С ПОТЕНЦИАЛОМ ГЛОБАЛЬНОГО ПОТЕПЛЕНИЯ (GWP) = 1975.

Згідно норм 842/EC/2006 стаття 7(1)


НЕ ВИПУСКАЙТЕ R410A В АТМОСФЕРУ: R410A – ФТОРОВМІСНИЙ ПАРНИКОВИЙ ГАЗ, ЩО ПІДПАДАЄ ПІД ДІЮ
UK КІОТСЬКОГО ПРОТОКОЛУ, З ПОТЕНЦІАЛОМ ГЛОБАЛЬНОГО ПОТЕПЛІННЯ (GWP) = 1975.

DC0611-10811

Printed in China

Mini_VRF_Cover.indd 2 2011/09/06 9:29:22

You might also like