Air Catch Sensor


Series ISA
For Workpiece Placement Confirmation

No-contact sensor for confirming


workpiece placement, with a
configuration that is less affected by
supply pressure change.

ZSE
ISE

ZSP
PS
ISA
PSE
IS
ISG
ZSM

Easy-to-set-up LED level meter Compliant with manifolds of up to 6 stations


Proper set position is steadily and easily set due to the Compliant with centralized wiring and piping
LED level meter and setting dial.

Above set position


Free mounting position
(Red)
Setting dial Stable detection is available at any mounting position
Set position (Green) due to the pressure sensor.
Below set position
(Green)

Wide adjustment range


Compliant between 10 and 300 μm

Stably detects 10 μm clearance IP66-compliant


The configuration is unlikely to be affected by supply Dustproof and dripproof type
pressure change due to the air pressure bridge circuit
and semi-conductor pressure sensor.

813
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 815

Air Catch Sensor

Series ISA
How to Order

Individual wiring/Centralized wiring ISA 01

Option
Nil ∗ DIN rail compliant ZSE
Output specifications B With bracket ISE
11 NPT open collector output G With gauge
15 PNP open collector output ∗ DIN rail must be ordered ZSP
separately.
PS
Stations 1 to 6
ISA
Wiring specifications
Ex. 1) NPN output, 4 stations, centralized wiring terminal block BOX (left), with bracket and gauge Nil Individual wiring (Without terminal block BOX)
PSE
ISA11-4L-01BG L Centralized wiring (With terminal block BOX, left side)
R Centralized wiring (With terminal block BOX, right side)
Ex. 2) PNP output, individual wiring, with gauge IS
ISA15-1-01G ISG
ZSM

Accessory
· Bracket: ISA-1-A
· Gauge: G33-3-01
· DIN rail: ISA-2-1 to 7

· Gauge: G33-3-01 · Bracket: ISA-1-A · DIN rail: ISA-2-1 to 7


10 (Hexagonal)

Material: SPC Material: Aluminum


(Nickel plated)

110
q we r t
100 L
4 x ø4.5 90 5 25 10 7.5
ø30

42
34
28

R 1/8
4.5
35

27

9
16.5 13
5.6

Part no. L Applicable model


Description ISA-2-1 105 ISA -1
No. Description Material ∗ Each part order comes with two M3 x 8 ISA-2-2 140 ISA -2 · ISA -1 RL
1 Cover glass glass tapping screws. ISA-2-3 175 ISA -3 · ISA -2 RL
2 Outer frame Stainless steel ISA-2-4 210 ISA -4 · ISA -3 RL
3 Inner frame Stainless steel ISA-2-5 245 ISA -5 · ISA -4 RL
4 Round head Phillips screw Stainless steel ISA-2-6 280 ISA -6 · ISA -5 RL
5 Socket Brass ISA-2-7 315 ISA -6 RL

815
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 816

Series ISA

Specifications

Fluid Dry air (filtered to 5 μm)


Operating pressure range 0.05 to 0.2 MPa
Recommended pressure range 0.1 to 0.2 MPa
Detection distance range 10 to 300 μm
Repeatability including temperature
±10 μm (0 to 60°C (standard 25°C))
characteristics
Hysteresis 10 μm or less (Detection distance: 10 to 150 μm)
Detection nozzle O.D. ø1.0 standard (Refer to page 820 for data when the nozzle diameter is modified.)
Display function Operating indicator light (Lights ON), Deviation level indicator light
Power supply voltage 12 to 24 VDC ±10%, Ripple (p-p) 10% or less (With power supply polarity protection)
Current consumption 30 mA or less (Output ON, All LEDs ON)
ISA11 NPN open collector: 30 V, 80 mA or less
Switch output
ISA15 PNP open collector: 80 mA or less
Operating temperature range 0 to 60°C (No condensation)
Operating humidity range 35 to 85 % RH (No condensation)
Noise resistance 1000 Vp-p, Pulse width 1 μs, Rise time 1 ns
Withstand voltage 1000 VAC in 50/60 Hz for 1 minute between live parts and case
Insulation resistance 2 MΩ or more between live parts and case (at 500 VDC by megameter)
Vibration resistance 1.5 mm amplitude in 10 to 500Hz or acceleration of 98 m/s2, whichever is smaller for 2 hours in X, Y, Z direction each (De-energized)
Impact resistance 980 m/s2 in X, Y and Z direction, 3 times each (De-energized)
Lead wire Oil-resistant vinyl cabtire code (3 cores, ø3.4, 5 m), Cross section: 0.2 mm2, Insulator O.D.: 1.1 mm
Mass 250 g (including gauge and 5-m lead wire)
Port size Rc 1/8
Enclosure IP66 (Dustproof and dripproof type)
pressure

0.10 MPa 16 l /min or less


Supply

Air consumption 0.15 MPa 21 l /min or less


0.20 MPa 25 l /min or less

Working Principle How to Set Pressure


Air catch sensor is adjusted by using the LED level meter and the setting
dial.
P1 EXH port

SUP port
S1 S3 LED level meter
Sensor Red ON: Output OFF
S2 S4 Green ON: Output ON
+
P2 Redq
Detection port Below set position
Large clearance
S1, S2: Fix orifice Redw
S3: Variable orifice (adjusted by setting dial)
S4: Detection nozzle
BEST POSITION Greenq Set position
In a bridge circuit as in the figure above, a detection gap is applied to the
detection nozzle (S4) while the setting dial S3 is adjusted to balance the Small clearance Greenw Above set position
pressure applied to the pressure sensor (P1 = P2). The pressure sensor

detects the differential pressure generated when the detection nozzle (S4)
is released. When the work piece comes close to the detection nozzle, the (1) For accurate setting, create the proper setting conditions by applying a
back pressure P2 increases until it is larger than P1 (P2 ≥ P1). Then the clearance gauge to the detection nozzle beforehand.
switch output turns on to notify that the pressure is below the detection (2) Confirm that pressure is being applied. At this time, if the setting dial is
gap. fully closed, all LEDs should be off.
(3) Turning the setting dial in a plus direction (counterclockwise) will cause
the LEDs to turn on in order: Red 1, Red 2, Green 1, Green 2.
(4) When the Green 1 LED level meter comes on, output will be switched
on, so please end the setting process at the point when Green 1
comes on.
(5) Apply a clearance gauge to the detection nozzle once more, and
confirm that Green 1 has switched on.
(6) Hold the setting dial with a finger, and tighten the lock nut with a
wrench. Tighten so that the setting dial will not turn.
816
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 817

Air Catch Sensor Series ISA

Internal Circuit and Wiring

NPN-type open collector Centralized wiring type


DC (+) Refer to the below figure for the relation between terminal block wiring in
Brown terminal box and switch.
Main circuit of switch

OUT OUT OUT OUT OUT

Load
OUT
1 2 3 4 5
Black +
12 to 24 VDC OUT
GND VCC NC
– 6
Max.80 mA
DC (–)
L side R side
Blue

PNP-type open collector


DC (+)
Brown
Main circuit of switch

OUT Max.80 mA +
Black 12 to 24 VDC
– q w e r t y
ZSE
Load

DC (–) ISE
Blue
ZSP
PS

Specific Product Precautions ISA

Read before handling. PSE


Refer to front matters 58 and 59 for Safety Instructions and pages 687 to 691 for Pressure Switch Precautions.
IS
Mounting Operating Environment
ISG
Caution Caution
1. If the detection nozzle is exposed to splashes of water or cutting oil, do 1. When an air catch sensor is contained in a box, provide an air outlet to ZSM
not allow backflow from the detection nozzle to the switch body. Install constantly keep the atmospheric pressure inside the box. Internal pressure
the switch body at a position higher than the detection nozzle wherever rises will hinder normal air discharge and may lead to possible malfunction.
possible. 2. The air catch sensor is IP66-compliant, but when there is a possibility of
water, oil, etc. from the exhaust port entering the case interior, use an M5
fitting to connect a tube, and discharge air in a place where water and oil
Piping will not enter the interior. When attached with a gauge, there is a danger of
materials entering the gauge interior and causing malfunction, so please
Caution remove the gauge and use a plug instead.
When mounting a gauge to the exterior, please use piping of as short a
1. Piping equipment length as possible. Failure to do so may result in slower response speed.
In the piping between the switch body and the detection nozzle, do not
use equipment or fittings that can possibly cause leakage or serve as
resistance. Maintenance
Do not use One-touch fittings in an environment where the air catch
sensor is exposed to water or other liquid.
Caution
1. How to change
Pressure Source After loosening the four mounting screws (M4 x 8), pull straight back on
the switch body. Pulling back diagonally can result in bending of the
Caution connector pin, etc., so take precautions.
2. When mounting the switch body to the base, push the pin (main body
1. Supply air side) straight into the connector (base side), and evenly mount with four
Since the orifice of the air catch sensor is small, prevent foreign matter mounting screws (M4 x 8). Be sure not to forget to include seals, etc.
from entering the equipment. For this purpose, use supply air that is dry (Tightening torque 0.45 N·m)
and filtered 5 μm or better.
2. Operating pressure
Since the product adopts a semiconductor pressure sensor, keep the Switch assembly
operating pressure not larger than 0.2 MPa.

O-ring

Gasket

Base

Switch assembly part no.


(O-ring: 2, Gasket: 1 enclosed)
ISA11-0 For NPN output
ISA15-0 For PNP output
817
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 818

Series ISA

Dimensions: Centralized Wiring Type (Terminal Block Box Type)

Body With bracket Manifold

Deviation level L1
Deviation level 75 Terminal
indicator light 34 L2 34 40

10
Terminal block box
indicator light 40 block box
10

SUP port
Rc 1/8

(94.4)
70
100
(94.4)
70

90
DIN rail center
100
90

SUP
40

(4.5)
30
Setting dial

10
12 35 Lead wire electrical entry
10

34 Lead wire electrical entry 8 x ø4.5 Gauge


Applicable O.D.ø6.5 to ø8.5 42 42 Applicable O.D.ø6.5 to ø8.5
4 x ø4.5 42 OUT3 9 x M3
Bracket Bracket
OUT2 OUT4
Gauge
OUT1 OUT5
EXH port Station 1 n EXH port
69.3 (Max.74.4)

69.3 (Max.74.4)
60

60
OUT

OUT OUT OUT OUT OUT OUT


2.1 19.5

2.1 19.5
GND OUT6

11.6 Detection port VCC


Detection port
Rc 1/8 11.6
Terminal block box wiring diagram Rc 1/8

Dimensions
When the bracket has two stations and the Station 2 3 4 5 6
terminal block box is on the right side, it L1 110 145 180 215 250
attaches to the second switch, while when L2 — 36 71 106 141
it is on the left side, it attaches to the first
switch. With n stations, it attaches to the
first switch and the nth switch.

Body With DIN rail Manifold


Deviation level L1 Terminal
indicator light 35 40 block box
Deviation level 75
Terminal
indicator light 40 block box SUP port
Rc 1/8

(94.4)
25

70
DIN rail center
90
(94.4)

25
70

SUP

4.5
90

40
30
(4.5)
4.5

Setting dial Gauge Lead wire electrical entry

12 L2 Applicable O.D.ø6.5 to ø8.5


Gauge
L3
105 OUT3
OUT4
Lead wire electrical entry OUT2
OUT5
Applicable O.D ø6.5 to ø8.5 OUT1 Station 1 n EXH port
69.3 (Max. 74.4)
60

OUT OUT OUT OUT OUT OUT


19.5

GND OUT6
VCC
4

11.6 Detection port


Rc 1/8
Terminal block box wiring diagram

Dimensions: With DIN rail


Station 2 3 4 5 6
L1 110 145 180 215 250
L2 140 175 210 245 280
L3 175 210 245 280 315

818
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 819

Air Catch Sensor Series ISA

Dimensions: Individual Wiring Type (Lead Wire Type)

Body With bracket Manifold

Lead wire (5 m)
Lead wire (5 m) L1
34 Bracket Bracket
34 L2 34

(18)

10
SUP port
10

Deviation level
Deviation level Rc 1/8 indicator light
indicator light DIN rail center

SUP
Gauge
100

100
90
90

40

(4.5)
30
Setting dial
10

35 4 x ø4.5 12 8 x ø4.5 Gauge


35 42

10
42 42
EXH port
69.3 (Max.78.4)

Station 1 n EXH port


ZSE

69.3 (Max.78.4)
60

OUT

ISE
2.1 19.5

60
ZSP
OUT OUT OUT OUT OUT OUT

Detection port

2.1 19.5
11.6
Rc 1/8

11.6
Detection port PS
Rc 1/8
Dimensions
When the bracket has two stations, it
Station 2 3 4 5 6
ISA
attaches to the first switch.
With n stations, it attaches to the first
L1 70 105 140 175 210
switch and the nth switch.
L2 — 36 71 106 141 PSE
IS
ISG
ZSM
Body With DIN rail Manifold

Lead wire (5 m) L1
35
(18)

Deviation level Deviation level


indicator light 25 SUP port indicator light
Rc 1/8 25
90

SUP

DIN rail center


4.5

90
35

4.5
35
40
30
(4.5)

35
70 Setting dial Gauge
Gauge
12 L2
L3

Station 1 n EXH port


69.3 (Max. 78.4)
60

OUT OUT OUT OUT OUT OUT


4 19.5

11.6 Detection port


Rc 1/8
Dimensions: With DIN rail
Station 2 3 4 5 6
L1 70 105 140 175 210
L2 105 140 175 210 245
L3 140 175 210 245 280

819
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 820

Series ISA

Operation guideline: Design data


When you design the pneumatic circuit using the air catch sensor, please refer to the data below. The detection distance of the
air catch sensor is between 10 and 300 μm. However, please note that stable detection cannot be done when supply pressure or
nozzle size are different.

Relation between Nozzle Diameter and Detection Distance


The data in the following charts are characteristics of hysteresis at the detection distance.
In case accuracy is required by the settings, the design should be made so that the hysteresis will stay within the optimum adjustment range not larger than
10 μm.
The smaller the hysteresis, the better the sensitivity. In cases where the hysteresis exceeds 10 μm, the air catch sensor should be used to check the
presence of the work piece.
Detection nozzle: ø1.0 Detection nozzle: ø1.5 Detection nozzle: ø2.0
Detection side piping: ø6 x ø4 tubing Detection side piping: ø6 x ø4 tubing Detection side piping: ø6 x ø4 tubing
70 70 70

60 60 60
Supply pressure Supply pressure
No
50 50 50 td
ete
cta
ble
Hysteresis (μm)

Hysteresis (μm)

Hysteresis (μm)
0.1MPa
0.1MPa
40 40 40
Supply pressure

30 30 30
0.1MPa

20 20 20
0.15MPa 0.15MPa
0.15MPa
10 10 10
0.2MPa 0.2MPa 0.2MPa

0 Optimum adjustment range 0 Optimum adjustment range 0 Optimum adjustment range


100 200 300 100 200 300 100 200 300

Detection distance (μm) Detection distance (μm) Detection distance (μm)

Ex. 1) To detect 300 μm, select a ø1.0 detection nozzle and supply pressure of 0.2 MPa.
Ex. 2) To detect 10 μm, select a ø1.5 detection nozzle.

Nozzle Shape
Please keep the nozzle shape as illustrated below.
Take every caution against chamfer on the detection surface and/or nozzle hole,
which could affect the characteristics as illustrated in Figure (1).
Figure (1)

Chamfer is not
ø1 ø1.5 ø2 allowed.
Detection
surface
2 or more

2 or more
2 or more

ø3 or more ø3 or more ø3 or more

820
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 821

Air Catch Sensor Series ISA

Response Time
Response time changes with detection distance and piping length. It is hardly influenced by the supply pressure and nozzle diameter (ø1.0 to ø2.0).
While both graphs assume a fixed set distance with changes in the detection distance, Fig. 2 shows responses at various set values and Fig. 3 shows
responses at various piping lengths. If the detection distance is equal to the set value, the response becomes quicker as the set value becomes smaller or
the piping length becomes shorter.

Detection nozzle: ø1.0


Detection nozzle: ø1.0 Operating piping: ø6 x ø4 tubing
Operating piping: ø6 x ø4 tubing (5m) Supply pressure: 0.1 MPa
Supply pressure: 0.2 MPa Set distance: 100 μm
2.5 Set value 4.0
50 μm 100 μm 200 μm 300 μm ZSE
2.0 3.5 ISE

ZSP
Response time (sec)

1.5 3.0
PS
Response time (sec)

1.0 2.5
ISA
Piping tubing length
0.5 2.0
10m PSE
8m
0
50 100 150 200 250 300 350 1.5
5m
IS
3m
Detection distance (μm) 1.0 ISG
1m

Fig. 2 Detection distance – Response time characteristics ZSM


0.5

0 50 100

Detection distance (μm)

Fig. 3 Response time – Piping tubing length

Supply Pressure Dependence


The charts illustrate changes in the detection distance with fluctuations in the supply pressure.

Detection side nozzle: ø1.0 Detection side nozzle: ø1.5 Detection side nozzle: ø2.0
Detection side piping: ø6 x ø4 tubing Detection side piping: ø6 x ø4 tubing Detection side piping: ø6 x ø4 tubing
300 300 300
Detection distance (μm)

Detection distance (μm)

Detection distance (μm)

200 200 200

100 100 100

0 0.1 0.2 0.3 0 0.1 0.2 0.3 0 0.1 0.2 0.3

Supply pressure (MPa) Supply pressure (MPa) Supply pressure (MPa)

821
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 793

Air Catch Sensor


Series ISA2
Non-Contact Sensor for Workpiece Placement Confirmation

Stable detection of 0.01 to 0.5 mm clearance


Due to the pneumatic bridge circuit and semiconductor pressure sensor, the non-contact type sensor is
hardly affected by fluctuations in the supply pressure.
Plug connectors (Centralized wiring) Modular construction
Requires less man hours to wire. Requires less man hours to wire.
Easy to add and remove manifold stations.
Terminal box

ZSE
ISE

ZSP

With regulator + 2 port solenoid valve


PS
ISA
With 2 port solenoid valve

PSE
IS
ISG
Optimum position is known at a glance. LED level meter ZSM
Easy-to-operate
large dial
Above set position Set position Below set position
Red Green Green
Extraneous
material
W W W

Scale provides
guidelines for set
position.

2 wiring methods
Individual Centralized
wiring Wiring

Minimum operating pressure 30 kPa (ISA2-G)


Energy consumption can be reduced compared with the conventional models (Conventional models: 50 kPa)
Position of supply port: Either right side or left side is available.
793
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 794

Air Catch Sensor

Series ISA2
How to Order

Manifold
Without control unit IISA2 N PL 3 B
With control unit IISA2 C SL 3 B 1 D E2
Pressure gauge of regulator Note 1)
A* Without pressure gauge Note 2)
E2 MPa single notation 0.2 Square embedded
pressure gauge
Control unit Z2* psi single notation MPa
C With regulator + 2 port solenoid valve E4 MPa single notation 0.4
V With 2 port solenoid valve Z4* psi single notation MPa
G2 MPa single notation 0.2 Roundgauge
pressure
P2* MPa-psi double notation MPa
G4 MPa single notation 0.4
Electrical entry and supply port position P4* MPa-psi double notation MPa
SR Centralized wiring with supply port on the right Note 1) Due to new Japanese weight and
Centralized wiring with supply port on the left measurement legislation, psi notation
SL
type cannot be sold or used in Japan.
PR Individual wiring with supply port on the right Note 2) The pressure gauge port is Rc 1/8.
PL Individual wiring with supply port on the left * Manufactured upon receipt of order.
Note) The supply port position is the one when the switch
is viewed from the front.
Stations Throttle/Manual lock of 2 port solenoid valve
1 1 station Nil Without throttle, without manual lock
2 2 stations C With throttle, without manual lock
3 3 stations W Without throttle, with manual lock
4 4 stations M With throttle, with manual lock
5 5 stations Throttle
6 6 stations

Option
Nil Without bracket Manual lock
B With bracket
With mounting
D
bracket for DIN rail
Note) DIN rail must be
ordered separately.
Electrical entry of 2 port solenoid valve
(Refer to page 808.)
D : DIN connector D0: DIN connector T : Conduit terminal
DL: DIN connector (Without connector) TL: Conduit terminal
Voltage of 2 port (With indicator light) (With indicator light)
solenoid valve
1 100 VAC
2 200 VAC
3 110 VAC
4 220 VAC
5 24 VDC
6 12 VDC
36 230 VAC

794
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 795

Air Catch Sensor Series ISA2

How to Order
For single and double notation type and additional stations
Air catch sensor
ISA2 G E2 1
Detection distance Electrical entry
G 0.01 to 0.25 mm Piping specifications Straight
H 0.03 to 0.5 mm Nil Rc 1/8 Output specifications
N NPT 1/8 1 NPN output Nil
F∗

Individual wiring
G 1/8 5 PNP output
∗ Manufactured upon receipt
of order.
Right angle
Pressure gauge Note 1)
A∗ Without pressure gauge Note 2) L∗
E2 MPa single notation 0.2 Square embedded
pressure gauge
Z2∗ psi single notation MPa
E4 MPa single notation 0.4 N Without lead wire
Z4∗ psi single notation MPa ZSE

Centralized wiring
G2 MPa single notation 0.2 Round pressure ISE
gauge
P2∗ MPa-psi double notation MPa
G4 MPa single notation 0.4 P Terminal block box ZSP
P4∗ MPa-psi double notation MPa
Note 1) Due to new Japanese weight and PS
measurement legislation, psi notation ∗ Manufactured upon receipt
type cannot be sold or used in Japan. of order.
Note 2) The pressure gauge port is Rc 1/8. ISA
∗ Manufactured upon receipt of order.
PSE
Ordering Example
IS
Without control unit
Centralized wiring Individual wiring Centralized wiring/Supply port right ISG
Individual wiring Centralized wiring
air catch sensor
Terminal box
Centralized wiring
air catch sensor
air catch sensor
ISA2-GE41N
Terminal
box ISA2-HE41P
ZSM
ISA2-GE41P
3 0 3 0 3 0 3 0 3 0

6
PU
L L SET

9
Supply port 6
PU
L L SET

9 6
PU
L L SET

9 6
PU
L L SET

9 6
PU
L L SET

9
Supply port
0.1
0.2
0.3 IN IN 0.1
0.2
0.3 0.1
0.2
0.3 0.1
0.2
0.3 0.1
0.2
0.3 IN
0 0.4 0 0.4 0 0.4 0 0.4 0 0.4
MPa MPa MPa MPa MPa

Right Left Right

Bracket DIN rail mounting DIN rail mounting


bracket bracket
Stations 1 Stations 1 Stations 1 2 3

IISA2NSR-1B1 set (1 station manifold part number) IISA2NPL-1D1 set (1 station manifold part number) IISA2NSR-3D1 set (3 stations manifold part number)
∗ISA2-GE41P1 set (Air catch sensor part number) ∗ISA2-GE41N 1 set (Air catch sensor part number) ∗ISA2-HE41P 3 sets (Air catch sensor part number)
Prefix the part number of the air catch sensor Prefix the part number of the air catch sensor Prefix the part number of the air catch sensor
with an asterisk (∗). with an asterisk (∗). with an asterisk (∗).

With control unit


Centralized wiring/Supply port left Individual wiring/Supply port right
Centralized wiring
air catch sensor Individual wiring
2 port solenoid valve ISA2-HE41P Terminal box air catch sensor 2 port solenoid valve
ISA2-GE41
3 0 3 0 3 0

Regulator
3 0 3 0 3 0

PU PU PU

Supply port
PU PU PU L L SET L L SET L L SET
L L SET L L SET L L SET

Supply port 6 9 6 9 6 9
6 9 6 9 6 9

0.2 0.2 0.2

IN
0.2 0.2 0.2 0.1 0.3 0.1 0.3 0.1 0.3
0.3 0.3 0.3
IN
0.1 0.1 0.1
0.1
0.05 0.15 0 0.4 0 0.4 0 0.4
0 0.4 0 0.4 0 0.4 MPa MPa MPa
MPa MPa MPa
0 0.2
MPa

Left Right

Bracket Bracket

Stations 3 2 1 Stations 1 2 3

IISA2CSL-3B5DLCE21 set (3 stations manifold part number) IISA2VPR-3B5DLC1 set (3 stations manifold part number)
∗ISA2-HE41P 3 sets (Air catch sensor part number) ∗ISA2-GE41 3 sets (Air catch sensor part number)
Prefix the part number of the air catch sensor with an Prefix the part number of the air catch sensor with an
asterisk (∗). asterisk (∗).

795
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 796

Series ISA2

Specifications
Model ISA2-G1 ISA2-G5 ISA2-H1 ISA2-H5
Detection distance 0.01 to 0.25 mm 0.03 to 0.50 mm
Fluid Dry air (filtered to 5 μm)
Operating pressure range 30 to 200 kPa 50 to 200 kPa
Recommended detection nozzle ø1.5 ø2.0
pressure

Consumption 50 kPa 5 or less 10 or less


Supply

flow rate 100 kPa 8 or less 15 or less


l /min (ANR) 200 kPa 12 or less 22 or less
Power supply voltage 12 to 24 VDC ± 10%, Ripple (p-p) 10% or less (With power supply polarity protection)
Current consumption 15 mA or less
Switch output NPN PNP NPN PNP
open collector: one output open collector: one output open collector: one output open collector: one output
Maximum load current 80 mA
Maximum load voltage 30 VDC (at NPN output)
Residual voltage 1.5 V or less (at 80 mA)
Output protection Yes
Repeatability 0.01 mm or less (Detection distance range 0.01 to 0.15 mm, 0.01 mm or less (Detection distance range 0.03 to 0.15 mm,
(Including temperature characteristics) supply pressure 100 to 200 kPa) supply pressure 100 to 200 kPa)
Hysteresis Note 1) 0.01 mm or less (Detection distance range 0.01 to 0.15 mm) 0.01 mm or less (Detection distance range 0.03 to 0.15 mm)
LED level meter Note 2) with 1 red, 2 green
Indicator light
(Set value < detection distance: red, Set value = detection distance: green 1, Set value > detection distance: green 1 + green 2)
Enclosure IP66: with pressure gauge IP40: without pressure gauge
Operating temperature range Operating: 0 to 60°C, Stored: –20 to 70°C (No condensation or no freezing)
Environmental
resistance

Operating humidity range Operating/stored: 35 to 85%RH (No condensation)


Withstand voltage 1000 VAC or more in 50/60 Hz for 1 minute between live parts and case
Insulation resistance 2 MΩ or more between live parts and case (at 500 VDC by megameter)
1.5 mm amplitude in 10 to 500Hz or acceleration of 98 m/s2 without control unit and bracket mounted,
Vibration resistance
Others 30 m/s2, whichever is smaller for 2 hours in X, Y, Z direction each (De-energized)
Impact resistance Without control unit and bracket mounted: 980 m/s2, Others: 150 m/s2 in X, Y and Z direction, 3 times each (De-energized)
Port size Nil: Rc 1/8, N type: NPT 1/8, F type: G 1/8
Lead wire (Individual wiring type) 4 cores, oil-resistant cable (ø6, 5m) with M12 4-pin pre-wired connector, Conductor O.D.: 0.90 mm, Insulator O.D.: 1.72 mm
Terminal block box (Centralized wiring type) Front wiring (Electrical entry ø21)
Individual wiring type (body only): 253 g, common wiring type (body only): 250 g,
Mass
Terminal box: 205 g, lead wire: 278 g, connecting bracket with sealing for additional station: 4 g
Standard Compliant with CE marking
Note 1) Refer to “Relation between Nozzle Diameter and Detection Distance” (page 798) for hysteresis.
Note 2) Refer to “Setting Procedure” (page 801) for LED level meter.

Working Principle

P1 EXH port In a bridge circuit as in the left figure, a detection gap is


SUP port applied to the detection nozzle (S4) while the setting dial S3
S1 S3
Sensor is adjusted to balance the pressure applied to the pressure
S2 S4
sensor (P1 = P2). The pressure sensor detects the differential
P2
Detection port pressure generated when the detection nozzle (S4) is
S1, S2: Fix orifice released. When the work piece comes close to the detection
S3: Variable orifice (adjusted by setting dial) nozzle, the back pressure P2 increases until it is larger than
S4: Detection nozzle
P1 (P2 ≥ P1). Then the switch output turns on to notify that
the pressure is below the detection gap.

796
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 797

Air Catch Sensor Series ISA2

Internal Circuit and Wiring

NPN open collector output Circuit and Wiring for 2 Port Solenoid Valve
DC (+)

Without indicator light DC circuit Without display light AC Circuit


Main circuit of

OUT
Load
1 DC (+) 1 ( )
switch

MAX 80 mA 12 to 24 VDC Rectifying


device
ZNR ZNR
DC () SOL 12 to 24 VDC SOL 100 to 200 VAC

2 DC () 2 ( )

PNP open collector output Conduit terminal Conduit terminal


DC (+)
With indicator light DC circuit DIN type connector With indicator light AC Circuit
1 ( )
Main circuit of

1 DC (+)
MAX 80 mA Rectifying
switch

OUT device
Load 12 to 24 VDC ZNR ZNR
12 to 24 VDC SOL 100 to 200 VAC
SOL
DC ()
LED 2 DC () indicator 2 ( )
light

DIN type connector Refer to catalog and instruction manual of ZSE


With indicator light DC circuit Series VCA for wiring. ISE
1 DC (+)
Pay attention to the power supply voltage.
ZNR Use of incorrect power supply will cause ZSP
SOL 12 to 24 VDC damage to equipment.
LED 2 DC ()
PS
ISA
Wiring PSE

Individual wiring Centralized wiring IS


2: NC 1: Brown Terminal block
3 0 ISG
1 Brown DC (+)
OUT OUT OUT OUT OUT
2  NC 6 9
1 2 3 4 5 ZSM
3: Blue
3 Blue DC () DC DC OUT
4: Black NC
4 Black OUT () (+) 6

1. Insert the connector of the lead wire with its key groove at the
proper position.
2. Hold the knurl with 2 fingers and rotate it clockwise. Do not use 1. Mount the seal conduit on the terminal box. For mounting
tools. procedure, refer to the catalog and instruction manual provided
by the manufacturer of the seal conduit.
Lead wire with connector 2. Thread the cable through the seal conduit and arrange wiring
according to the polarity of the terminal block illustrated above.
Knurl
3. Fasten the seal conduit with a tightening torque not greater
than 5 N×m. Do not hold the terminal box or the switch.

3. Connect the colored wires coming from the cable terminal.


Refer to the circuit diagram and table above to avoid mistakes.

Seal conduit entry (ø21)

797
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 798

Series ISA2

Relation between Nozzle Diameter and Detection Distance

The data in the following charts are characteristics of hysteresis at the detection distance.
In case accuracy is required by the settings, the design should be made so that the hysteresis will stay within the optimum adjustment
range not larger than 0.01 mm.
The smaller the hysteresis, the better the sensitivity. In cases where the hysteresis exceeds 0.01 mm, the air catch sensor should be
used to check the presence of the work piece.

ISA2-G ISA2-H

Detection nozzle: ø1.0 Detection nozzle: ø1.0


Detection side piping: ø6 x ø4 tubing 5 m Detection side piping: ø6 x ø4 tubing 5 m
0.1 Supply pressure 0.1 Supply pressure
0.09 30 kPa 0.09 50 kPa
0.08 0.08
Hysteresis (mm)

Hysteresis (mm)
0.07 0.07
0.06 0.06 100 kPa
0.05 0.05
100 kPa
0.04 0.04
0.03 200kPa 0.03
200 kPa
0.02 0.02
0.01 0.01
Optimum adjustment range Optimum adjustment range
0 0
0 0.05 0.1 0.15 0.2 0.25 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
Detection distance (mm) Detection distance (mm)

Detection nozzle: ø1.5 Detection nozzle: ø1.5


Detection side piping: ø6 x ø4 tubing 5 m Detection side piping: ø6 x ø4 tubing 5 m
0.1 Supply pressure 0.1 Supply pressure
0.09 30 kPa 0.09
50 kPa
0.08 0.08
100 kPa
Hysteresis (mm)

Hysteresis (mm)

0.07 0.07
0.06 0.06
0.05 0.05
100 kPa
0.04 0.04
200 kPa
0.03 0.03
200 kPa
0.02 0.02
0.01 0.01
Optimum adjustment range Optimum adjustment range
0 0
0 0.05 0.1 0.15 0.2 0.25 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
Detection distance (mm) Detection distance (mm)

Detection nozzle: ø2.0 Detection nozzle: ø2.0


Detection side piping: ø6 x ø4 tubing 5 m Detection side piping: ø6 x ø4 tubing 5 m
0.1 Supply pressure 0.1 Supply pressure
0.09 30 kPa 0.09 50 kPa
0.08 0.08 100 kPa
Hysteresis (mm)

Hysteresis (mm)

0.07 0.07
0.06 0.06
0.05 0.05
100 kPa
0.04 0.04 200 kPa
0.03 0.03
200 kPa
0.02 0.02
0.01 0.01
Optimum adjustment range Optimum adjustment range
0 0
0 0.05 0.1 0.15 0.2 0.25 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
Detection distance (mm) Detection distance (mm)

798
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 799

Air Catch Sensor Series ISA2

Response Time

Response time changes with detection distance and piping length. It is hardly influenced by the supply pressure and nozzle diameter
(ø1.0 to ø2.0).
While all graphs assume a fixed set distance with changes in the detection distance, the upper charts show responses at various set
values and the lower charts show responses at various piping lengths. If the detection distance is equal to the set value, the response
becomes quicker as the set value becomes bigger or the piping length becomes shorter.

ISA2-G ISA2-H

Detection nozzle: ø1.5 Supply pressure: 100 kPa Detection nozzle: ø2.0 Supply pressure: 100 kPa
Detection side piping: ø6 x ø4 tubing 5 m Detection side piping: ø6 x ø4 tubing 5 m
2.5 Set value 2

2
0.05 mm 1.5 Set value
Response time (sec)

Response time (sec)


1.5
0.1 mm
0.1 mm
0.05 mm
1 0.15 mm
1 ZSE
0.3 mm ISE
0.5
0.5 mm
0.5 0.15 mm ZSP
0.25 mm
0 0 PS
0 0.05 0.1 0.15 0.2 0.25 0.3 0 0.1 0.2 0.3 0.4 0.5 0.6 ISA
Detection distance (mm) Detection distance (mm)
PSE
Detection distanceResponse time characteristics Detection distanceResponse time characteristics
IS
Detection nozzle: ø1.5 Supply pressure: 100 kPa Detection nozzle: ø2.0 Supply pressure: 100 kPa
Detection side piping: ø6 x ø4 Set distance: 0.15 mm Detection side piping: ø6 x ø4 Set distance: 0.3 mm ISG
3 Piping tubing length 1.5
Piping tubing length
10 m ZSM
2.5 10 m 1.2
Response time (sec)

Response time (sec)

2
8m
0.9
1.5 8m 5m

5m 0.6
1
3m
3m 0.3
0.5
1m 1m
0 0
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35
Detection distance (mm) Detection distance (mm)

Piping tubing lengthResponse time Piping tubing lengthResponse time


Nozzle Shape

Please keep the nozzle shape as illustrated below. Figure (1)


Take every caution against chamfer on the detection surface and/or nozzle hole,
which could affect the characteristics as illustrated in Figure (1). Chamfer is not
ø1 ø1.5 ø2 allowed.
Detection
surface
2 or more

2 or more

2 or more

ø3 or more ø3 or more ø3 or more

799
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 800

Series ISA2

Supply Pressure Dependence

The charts illustrate changes in the detection distance with fluctuations in the supply pressure.

ISA2-G ISA2-H

Detection nozzle: ø1.0 Detection nozzle: ø1.0


Detection side piping: ø6 x ø4 tubing 5 m Detection side piping: ø6 x ø4 tubing 5 m
0.4 0.6 0.5 mm
0.5
Detection distance (mm)

Detection distance (mm)


0.25 mm
0.3
0.4

0.2 0.3
0.15 mm
0.2 0.15 mm
0.1
0.1
0.01 mm 0.03 mm
0 0
0 50 100 150 200 250 0 50 100 150 200 250
Supply pressure (kPa) Supply pressure (kPa)

Detection nozzle: ø1.5 Detection nozzle: ø1.5


Detection side piping: ø6 x ø4 tubing 5 m Detection side piping: ø6 x ø4 tubing 5 m
0.4 0.6 0.5 mm
0.25 mm 0.5
Detection distance (mm)
Detection distance (mm)

0.3
0.4

0.2 0.3
0.15 mm
0.2 0.15 mm
0.1
0.1
0.01 mm 0.03 mm
0 0
0 50 100 150 200 250 0 50 100 150 200 250
Supply pressure (kPa) Supply pressure (kPa)

Detection nozzle: ø2.0 Detection nozzle: ø2.0


Detection side piping: ø6 x ø4 tubing 5 m Detection side piping: ø6 x ø4 tubing 5 m
0.4 0.6 0.5 mm
0.25 mm
0.5
Detection distance (mm)

Detection distance (mm)

0.3
0.4

0.2 0.3
0.15 mm
0.2
0.15 mm
0.1
0.1
0.01 mm 0.03 mm
0 0
0 50 100 150 200 250 0 50 100 150 200 250
Supply pressure (kPa) Supply pressure (kPa)

800
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 801

Air Catch Sensor Series ISA2

Setting Procedure

The detection distance is set with the LED level meter and setting 1. For accuracy in setting, apply a clearance gauge to the dete-
dial. ction nozzle to replicate the set condition in advance.
Keep the setting dial pulled out while in use. If released, it will 2. Confirm that the set pressure is applied. If the setting dial is
return to its original position and become unable to rotate. fully open, the LED level meter appears as .
3. Pull the setting dial and rotate it in the positive direction. The
lights will turn on in the order shown below.

Rotate in the
positive direction.
Red
Pull out

Before pulling out


Green 1

Green 2 ZSE
ISE

4. The sensor output comes on when the lights on the LED level ZSP
meter turn on as . Complete the setting when this condi-
tion is observed. PS
5. Apply the clearance gauge again to confirm that the lights turn
on as . ISA
Pulled out
PSE
Handling and setting of 2 port solenoid valve Handling and setting of limit gauge indicator
IS
Throttle setting for blowing to prevent water and cutting oil from OPEN arrow
1. Removal of cover
entering the nozzle. Hook the finger on the front ISG
(Clockwise: Close throttle; Counterclockwise: Open throttle) cover ridge and rotate it in
the direction of the OPEN
∗ The setting is not applicable to valves without throttle. arrow until it stops (15).
ZSM
Then pull out and remove
1. Power off the valve. the cover.
2. Rotate the throttle clockwise for adjustment so that the
detection nozzle will not suck up water or cutting oil. 2. Setting the installation needle
The installation needle should be moved by the fingertip.
Set the 2 green installation needles at the maximum and
minimum limits of pressure.

Example
Rotate
clockwise

IN

Maximum 0.24 MPa


Minimum 0.16 MPa

Throttle
3. Installation of cover
After setting the installation needles, locate the OPEN
arrow at the top right position and insert the claws on the
cover into the grooves on the case (indicated by in the
expanded view of A part). Rotate the cover clockwise until
it stops. Confirm that the cover is firmly secured.
Solenoid

3. Power on the valve, then off again. Expanded view A


Confirm that the detection nozzle does not suck up water of A part
or cutting oil.
Note) Do not rotate the throttle more than 5 turns or it will fall
out.
Finger

801
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 802

Series ISA2

Relation between Dial Scale and Detection Distance


Test procedure and conditions
Dial scales when the detection nozzle is under the following conditions;
Supplied pressure: 100 kPa
Piping: ø6 x ø4 tubing, 5 m in length.

Results of measurement Note 1)


 Relation between the detection distance and set dial scales Note 2) (Scale numbers)
ISA2-G ISA2-H
Detection nozzle diameter Detection nozzle diameter
Detection distance Detection distance
ø1.0 ø1.5 ø2.0 ø1.0 ø1.5 ø2.0
0.05 mm 0.3 to 0.7 0.9 to 1.4 0.3 to 0.7 0.1 mm 1.1 to 1.5 2.4 to 2.8 2.6 to 3.4
0.10 mm 1.1 to 1.5 2.3 to 2.8 2.0 to 2.5 0.2 mm 2.4 to 2.9 4.5 to 5.1 5.4 to 6.4
0.15 mm 1.9 to 2.3 3.4 to 4.1 3.7 to 4.6 0.3 mm 3.0 to 3.5 5.5 to 6.3 7.0 to 8.3
0.20 mm 2.5 to 3.0 4.4 to 5.5 5.3 to 7.0 0.4 mm 3.3 to 3.8 6.0 to 7.0 7.9 to 9.6
0.25 mm 3.0 to 3.5 5.2 to 7.0 6.6 to 10.7 0.5 mm 3.5 to 4.0 6.5 to 7.5 8.6 to 10.7

 Average variation per scale (Detection distance [mm])


ISA2-G ISA2-H
Detection nozzle diameter Detection nozzle diameter
Detection distance Detection distance
ø1.0 ø1.5 ø2.0 ø1.0 ø1.5 ø2.0
0.05 mm 0.010 0.005 0.006 0.1 mm 0.008 0.004 0.003
0.10 mm 0.007 0.004 0.003 0.2 mm 0.008 0.005 0.004
0.15 mm 0.010 0.005 0.004 0.3 mm 0.025 0.011 0.007
0.20 mm 0.010 0.005 0.003 0.4 mm 0.046 0.019 0.011
0.25 mm 0.010 0.007 0.003 0.5 mm 0.050 0.021 0.012
Note 1) This data provides reference values as a guide only, this should not be
viewed as a guarantee of our products performance.
Note 2) Set dial scales are as follows;

3
0.2

le
Sca

Between each major scales, it is sub divided into ten


A scale smaller settings (for example, between 2.0 to 3.0—2.1,
2.2, 2.3 etc.), settings are possible at 0.1 scale.

3 0

6 9

802
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 803

Air Catch Sensor Series ISA2

∗ When the SUP port is on the left, the stations are sequentially
Dimensions: Centralized Wiring Type numbered from the side of the terminal block box.

With bracket L1
3 60 38 L2 38 5
Terminal block box LED level meter

End plate L End plate R EXH port

3 0 3 0 3 0

PU PU PU
LL SET LL SET LL SET
81

6 9 6 9 6 9
Setting dial
0.2 0.2 0.2
0.1 0.3 0.1 0.3 0.1 0.3

0 0.4 0 0.4 0 0.4


MPa MPa MPa

12
Pressure gauge
12
21

Bracket
24
5.5

6.5 L3 SUP port


24 36 Rc, NPT, G 1/8
ZSE
OUT 3 36
OUT 2
ISE
OUT 4
OUT 1
OUT 5 Left Right ZSP
Stations 1∗ n
Stations 1 2 3 4 5 6 PS
63 (Max. 65)

L1 106 144 182 220 258 296


L2   38 76 114 152 ISA
L3  38 76 114 152 190
34

DC () OUT 6
17

DC (+) PSE
39
5

Detection port M4 x 8
19
Rc, NPT, G 1/8 (With HW, SW) IS
Terminal block box wiring diagram For the bracket attachment
position, refer to page 806.
Seal conduit entry ISG
(ø21)

With DIN rail ZSM


L1
3 60 38 L2 38 5
Terminal block box LED level meter

End plate L
End plate R EXH port

3 0 3 0 3 0

PU PU PU
LL SET LL SET LL SET
81

6 9 6 9 6 9

0.2 0.2 0.2


0.1 0.3 0.1 0.3 0.1 0.3

0 0.4 0 0.4 0 0.4


MPa MPa MPa
18
12
20.5

Pressure gauge SUP port


Rc, NPT, G 1/8
DIN rail mounting
5.25 bracket
11.2 DIN rail center
L3
L4 24
OUT 3 L5
OUT 2 OUT 4
OUT 1
OUT 5 Left Right
Stations 1∗ n

Stations 1 2 3 4 5 6
63(Max. 65)

L1 106 144 182 220 258 296


L2   38 76 114 152
L3  38 76 114 152 190
34

DC () OUT 6
17

L4 120 162.5 200 237.5 275 312.5


DC (+) L5 135.5 173 210.5 248 285.5 323
39
9.8

19 Detection port
Terminal block box wiring diagram Seal conduit entry Rc, NPT, G 1/8
(ø21)

803
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 804

Series ISA2

Dimensions: Individual Wiring Type

With bracket
L1
3 38 L2 38 5
LED level meter
Lead wire connector
EXH port End plate L EXH port

End plate R

3 0 3 0 3 0

92 PU PU PU
L L SE T L L SE T L L SE T

81 6 9 6 9 6 9

Setting dial
0.2 0.2 0.2
0.1 0.3 0.1 0.3 0.1 0.3

0 0.4 0 0.4 0 0.4


MPa MPa MPa
12

12
21

Bracket

SUP port Plug


Pressure gauge
5.5

24 6.5 L3
Rc, NPT, G 1/8
24
36 36

Left Right
Stations 1························· n
Stations 1 2 3 4 5 6
63(Max. 65)

L1 46 84 122 160 198 236


L2   38 76 114 152
L3  38 76 114 152 190
34
5 17

19 Detection port For the bracket attachment


M4 x 8
Rc, NPT, G 1/8 position, refer to page 806.
(With HW, SW)

With DIN rail


L1
3 38 L2 38 5
LED level meter Lead wire connector

EXH port End plate L EXH port


End plate R

3 0 3 0 3 0

DIN rail
92

PU PU PU
L L SET L L SET L L SET
Setting dial
81

center 6 9 6 9 6 9

0.2 0.2 0.2


0.1 0.3 0.1 0.3 0.1 0.3

0 0.4 0 0.4 0 0.4


MPa MPa MPa
18
12

Pressure
20.5

SUP port
gauge
Rc, NPT, G 1/8 Plug
24 DIN rail mounting
bracket
L3
5.25 11.2
L4
L5

Electrical entry dimensions Left Right


Straight union Right angle Stations 1························· n

Stations 1 2 3 4 5 6
63 (Max. 65)

L1 46 84 122 160 198 236


40.5

32.8

L2   38 76 114 152
 38 76 114 152 190
34

L3
17

L4 62.5 120 162.5 200 237.5 275


L5 73 135.5 173 210.5 248 285.5
The direction of a right angle Detection port
9.8

connector cannot be changed. 19 Rc, NPT, G 1/8


804
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 805

Air Catch Sensor Series ISA2

Dimensions: With Control Unit


SUP port on the left

EXH port EXH port

3 3

Throttle needle
SUP port PU
LL
SUP port PU
LL

6 6
Rc, NPT, G 1/4 Rc, NPT, G 1/4
118
143
144

0.1 0.1
0.1
0.05 0.15
0 0
0 MPa 0.2
178

DIN
64.4

connector Manual lock

ZSE
DIN ISE
connector
25 ZSP
82 Conduit terminal Conduit terminal
97 40 10 42 PS
ISA
With regulator + 2 port solenoid valve With 2 port solenoid valve PSE
IS
ISG
SUP port on the right ZSM

97
Conduit terminal Conduit terminal
82

DIN
connector
DIN connector

0 0

SET SET
9 9
162

0.3 0.3
0.1
133

0.05 0.15
128

0.4 0.4
0 MPa 0.2
103
64.4

SUP port
Rc, NPT, G 1/4 Throttle needle SUP port
Rc, NPT, G 1/4

42 10 40 25

With regulator + 2 port solenoid valve With 2 port solenoid valve

805
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 806

Series ISA2

Bracket Mounting Position

With 2 stations, the bracket is mounted on the second sensor from the left.
1 2
Left 1 2 Right 1 2

MPa MPa MPa MPa MPa MPa

With n stations, the bracket is mounted on the first and “n” th sensor from the left.
1 2  n



MPa MPa MPa

Addition of Manifold Stations

1. Disassembly 1. Loosen the screws and remove the 2 mounting brackets on the
front and back side.
2. Disassemble the switch carefully so that the O-ring on the SUP
port will not be detached.

End plate removal


Slot for removal

Hook the fingers on the top and


bottom removal grooves to pull out
the plate.
Existing joint brackets It can be removed by pulling
horizontally.

2. Insertion Recess Protrusion 1. Fit seal for additional station (ISA-7-B) to the recess of the
SUP port of the additional switch.
2. Fit the protrusion of the additional switch into the existing
switch.
3. Mount joint brackets (ISA-3-A) at 2 positions.
Note) Perform temporary tightening of screws.
4. Confirm that the recess of the SUP port of the existing switch
has seal for additional station attached.
5. Fit the protrusion of the existing switch into the recess of the
additional switch.
Existing joint brackets Joint brackets (ISA-3-A) 6. Mount the existing joint bracket.
Note) Perform temporary tightening of screws.
The switch for adding stations

3. Assembly
1. Tighten the joint brackets with the prescribed tightening torque
of 1.2 N×m.
2. Arrange pneumatic piping and confirm that there is no air leak-
age from new joints.

806
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 807

Air Catch Sensor Series ISA2

Parts List
End plate R
ISA-6-B

Terminal block box

Switch
mounting

t
h
bracket

ig
End plate L

R
ISA-3-A
ISA-6-A
Seal for additional station
ISA-7-B ZSE
Throttle
ISE
2 port solenoid valve
ZSP
Spacer
Regulator Y20 PS
ISA
Terminal block box
ISA-11-L (Centralized wiring/Supply port left)
PSE
ISA-11-R (Centralized wiring/Supply port right) IS
IN ISG
t
ef
L

ZSM
Spacer Seal for additional station End plate L End plate R
Y20 ISA-7-B ISA-7-A ISA-6-A ISA-6-B
When 2 air catch sen- When a 2 port solenoid
sors are connected or valve is connected to the
when a 2 port solenoid right:
valve is connected to the
left:

Joint bracket Lead wire with connector (Individual wiring type) Bracket DIN rail mounting bracket
ISA-3-A ISA-8-A ISA-8-B ISA-4-A ISA-9-A
A pair consists 1 set. Straight, 5 m Right angle, 5 m

With mounting
screw 2 pcs.

807
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 808

Series ISA2

DIN Rail
ISA-5-
L
Applicable models
1.25 8 4.5 7.5 Part no. L
Individual wiring type Centralized wiring type
ISA-5-1 73.0 IISA2P-1 —
ISA-5-2 135.5 IISA2P-2 IISA2S-1
ISA-5-3 173.0 IISA2P-3 IISA2S-2
ISA-5-4 210.5 IISA2P-4 IISA2S-3
5.5

35
35

ISA-5-5 248.0 IISA2P-5 IISA2S-4


ISA-5-6 285.5 IISA2P-6 IISA2S-5
ISA-5-7 323.0 — IISA2S-6

Pressure Gauge for Air Catch Sensor


Square embedded pressure gauge Round pressure gauge Connection
GC3 4 AS G36 4 01 thread
Notation Maximum Nil R 1/8
Maximum pressure P NPT 1/8
Notation pressure specifications
indication
specifications indication Nil MPa single notation
MPa-psi 2 0.2 MPa
Nil MPa single notation 2 0.2 MPa P Note) double 4 0.4 MPa
notation
P psi single notation 4 0.4 MPa
Note) For double notation of MPa and psi, add “-X30” at the end of part number.
Example) G36-P4-01-X30

Regulator 2 Port Solenoid Valve

AR 20 02 E 1 VCA27A 5 DL S 4 02 Q
Thread type Port size
Voltage 02 Rc 1/4 CE
Nil Rc 1 100 VAC marked
02N NPT 1/4
N NPT 2 200 VAC 02F G 1/4
F G 3 110 VAC
Option (The shape of pressure gauge) Note 2) 4 220 VAC Throttle
Nil None 5 24 VDC Nil Without throttle and manual lock
E Square embedded pressure gauge (With limit indicator) 6 12 VDC S With throttle
G Note 1) Round pressure gauge (With limit indicator) 36 230 VAC B With manual lock
Note 1) The pressure gauge port is 1/8. The pressure gauge is K With manual lock and throttle
included in the package (not assembled).
Electrical entry
Note 2) Order individually when 0.4 MPa gauge is required.
D DIN connector
Option specification DL DIN connector (With light)
Nil None D0 DIN connector (Without connector)
N Non-relieving T Conduit terminal
R Flow direction: Right to left TL Conduit terminal (With light)
Z Note 1) Unit representations on the label and pressure gauge are psi and °F
When specifying more than one option, enter symbols first in numerical, then Standard Specifications
in alphabetical orders. Valve type Direct operation poppet
Note 1) Compatible with thread type NPT. Under the New Measurement Law, Fluid Air, Inert gas
this type is only sold outside Japan. (The SI unit is used inside Japan.)
Valve specifications

Withstand pressure MPa 2.0


In all cases, with the exception of NPT, add “-X2025” at the end of the
order number. Example) AR20-02E-1-X2025 Body material Al
Seal material HNBR
Standard Specifications
Ambient temperature °C –20 to 60
Model AR20 Fluid temperature °C –10 to 60 (No freezing)
Port size 14
Enclosure Dustproof and jetproof (Equivalent to IP65)
Fluid Air Atmosphere Environment with no corrosive or explosive gas
Proof pressure 1.5 MPa Valve leakage cm3/min (ANR) 0.2 or less
Maximum operating pressure 1.0 MPa Mounting orientation Free
Set pressure range 0.02 to 0.2 MPa Vibration resistance/Impact resistance m/s2 Note 2) 30/150 or less
Gauge port size Note 1) 18
Rated voltage 24/12 VDC, 100/110/200/220 VAC (50/60 Hz)
Coil specifications

Set pressure + 0.05 MPa Allowable voltage fluctuation ±10% rated voltage
Relief pressure
{at relief flow of 0.1 l/min(ANR)} Type of coil insulation B type
Ambient and fluid temperature –5 to 60°C (No freezing) Power consumption DC VCA2: 6.5 W
Construction Relieving type Apparent Note 1) 50 Hz

Mass (kg) power AC VCA2: 7.5 VA


0.29 60 Hz
Pressure Round Note 2) G36-2-01 Note 1) Since the AC specifications include a rectifying device, there is no difference
gauge 0.2 MPa Square embedded Note 3)
GC3-2AS between the apparent power required for starting and holding.
Note 1) The type with square embedded pressure gauge does not have connection. Note 2) Vibration resistance: No malfunction resulted in a one-sweep test in a 10 to
Note 2) The “” in the part number of the round pressure gauge indicates the type of 300 Hz range in the axial and right angle directions of the main valve and
connection threads, no symbol for R and N for NPT. Contact SMC for supply of the armature, for both energized and de-energized states.
connection thread type NPT and the pressure gauge of psi unit representation. Shock resistance: No malfunction resulted in an impact test using a drop im-
Note 3) With an O-ring (1 pc.) and mounting screws (2 pcs.). pact tester. The test was performed in the axial and right angle directions of
the main valve and armature, for both energized and de-energized states.
808
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 809

Series ISA2
Specific Product Precautions 1
Be sure to read before handling. Refer to front matters 58 and 59 for Safety Instructions
and pages 687 to 691 for Pressure Switch Precautions.

Air Catch Sensor Series ISA2 Pressure Source


Operating Environment Caution
Warning 1. Supply air
Since the orifice of the air catch sensor is small, prevent
1. Do not use in an environment where vibration or foreign matter from entering the equipment. For this purpose,
impact occurs. Use a bracket in an environment use supply air that is dry and filtered 5 μm or better.
with vibration exceeding 30 m/s2. 2. Operating pressure
2. The enclosure of the switch conforms to IP66 Since the product adopts a semiconductor pressure sensor,
and that for the solenoid valve to IP65. The keep the operating pressure not larger than 0.2 MPa.
pressure gauge and the regulator have open
constructions. Take proper protection 2 Port Solenoid Valve Series VCA
measures in an environment where water Precautions on Design
splashes, oil or spatters from welding may
adhere to the product. Warning ZSE
ISE
3. Since steel piping lacking flexibility is easily 1. Energized continuously
affected by moment loads or propagation of Please consult with SMC if the product is to be energized ZSP
vibration, employ flexible tubing, etc., to continuously for long periods of time.
prevent interactions of such factors. PS
Selection
4. Although CE accredited, this air catch sensor is
not equipped with surge protection against Caution ISA
lightning. Necessary countermeasures for 1. Leakage voltage
possible lightning surge should be fitted to Take special precautions if a resistor is used in parallel with
PSE
system components as required. the switching element or a C-R element (for surge voltage
5. Do not operate in locations having an protection) is used for protection of the switching element. The IS
atmosphere of flammable, explosive or valve may fail to turn off due to leakage current flowing
corrosive gases, which can result in fire, through the resistor or C-R element. ISG
explosion or corrosion. The air catch sensor Switching element
does not have an explosion proof rating.
ZSM
OFF

Caution C R
Leakage
voltage
supply
Power

1. When an air catch sensor is contained in a box, Valve


provide an air outlet to constantly keep the
Leakage voltage
atmospheric pressure inside the box.
Internal pressure rises will hinder normal air discharge and
may lead to possible malfunction.
AC coil DC coil
2. The air outlet is provided on the setting dial 10% or less rated voltage 2% or less rated voltage
section of the air catch sensor. Do not turn off
air supply to the switch if water or cutting oil
splashes around the setting dial. Mounting

Mounting Warning
1. Do not use the air catch sensor if the leakage
Caution amount increases or the equipment does not
1. If the detection nozzle is exposed to splashes operate properly.
of water or cutting oil, do not allow backflow After installation, connect compressed air and electricity and
from the detection nozzle to the switch body. conduct an appropriate functionality inspection to confirm that
Install the switch body at a position higher the air catch sensor is installed properly.
than the detection nozzle wherever possible. 2. Do not apply external force to the coil.
Apply a wrench to the exterior surface of the piping joint at the
Piping time of tightening.
3. Do not use heat insulators, etc. to keep the
Caution temperature at the coil assembly.
1. Piping equipment Do not use a tape heater for freeze prevention except on the
In the piping between the switch body and the detection piping and body. If may cause the coil to burn.
nozzle, do not use equipment or fittings that can possibly
cause leakage or serve as resistance.
Do not use One-touch fittings in an environment where the air
catch sensor is exposed to water or other liquid.
809
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 810

Series ISA2
Specific Product Precautions 2
Be sure to read before handling. Refer to front matters 58 and 59 for Safety Instructions
and pages 687 to 691 for Pressure Switch Precautions.

2 Port Solenoid Valve Series VCA Regulator Series AR

Electric Circuit Mounting and Adjustment

Caution Warning
1. The adjustment knob must be handled manually. Use of tools may
In case of series VC (B type coil) cause damage to the product.
Conduit terminal, DIN type connector 2. Check the inlet and outlet pressure indications on the pressure
Rectifying gauge while setting. If the knob is turned to excess, it may cause
DC circuit ZNR AC circuit ZNR device
1 (+, -) internal parts to fracture.
1
3. Since products for 0.02 to 0.2 MPa settings come with a pressure
gauge for 0.2 MPa, do not apply pressure exceeding 0.2 MPa. It
SOL. SOL.
may cause damage to the pressure gauge.
2 (-, +) 2
Without indicator light Without indicator light
Caution
Conduit terminal, DIN type connector
DC circuit AC circuit Rectifying
1. Unlock the knob before pressure adjustment and lock it again when
ZNR ZNR device the adjustment is over.
1 (+, -) 1 Incorrect procedure may cause damage to the knob or lead to the
outlet pressure fluctuation.
SOL. SOL. • Pull the adjustment knob to release the lock. An orange colored
line is provided at the bottom of the adjustment handle for visual
2 (-, +) 2 checking.
Indicator light Indicator light • Push the pressure regulation knob to engage the lock. If it does
With indicator light With indicator light not lock easily, turn the knob slightly clockwise or counterclock-
wise until the orange colored line goes out of sight.
2. When the product is installed, leave a space of 60 mm on the side
Maintenance of the valve guide (opposite to the knob) for maintenance and
inspection.
Warning
1. Low-frequency operation
Perform valve switching at least every 30 days to prevent
malfunction. Also, conduct a periodic inspection at intervals of
approximately 6 months to use the product in its best condi-
tion.

Manual Operation

Warning
How to operate manually
Locking type (tool required)
To open valve: Rotate to the right by 90° using a flat head
screwdriver. It will still hold open even when the
driver removed.
To close valve: Rotate to the left by 90° to achieve the former
closed position.
Electrical operations should be undertaken when the valve is closed.

Valve closed (vertical slit) Valve open (horizontal slit)

810
P0756-P0822-E.qxd 08.8.27 6:37 PM Page 811

Series ISA2
Specific Product Precautions 3
Be sure to read before handling. Refer to front matters 58 and 59 for Safety Instructions
and pages 687 to 691 for Pressure Switch Precautions.

2 Port Solenoid Valve Series VCA

Disassembly and Assembly Wiring

Caution Caution
• Before the product is disassembled, DIN connector (B type only)
shut off the power and pressure The internal wiring of the DIN connector is illustrated below. Connect
supply and exhaust the residual each terminal to the power supply.
pressure.
Mounting
• Disassembly procedure 1: +
screw + 3
()

1
1. Remove the top mounting screws.

2
2. Remove the solenoid coil, spring  2: 
(+)
and armature assembly.
3. If there is any foreign matter ZSE
adhering on the surface, take ISE
appropriate measures to clear it
off such as an air blow or washing ZSP
with neutral detergent. Terminal no. 1 2
• Assembly procedure Solenoid DIN terminal + (-) - (+) PS
Reverse the above procedure to coil ∗ No polarity.
assemble the product. • A cabtire cable with an O.D. ø6 to 12 mm is applicable. ISA
In case the electrical entry is • Tighten each part with an appropriate tightening torque shown below.
Spring
changed, also change the Connector PSE
mounting orientation of the Bind screw with a flange
solenoid coil before assembly.
Note 1) Tighten the 4 mounting screws by Armature
Tightening torque 0.5 to 0.6 N⋅m IS
each pair of corners on a diagonal assembly
line at the proper tightening torque ISG
shown below.
O-ring
ZSM
Fitting cable Note)
Washer (Cable O.D.
Body ø6 to 12 mm)
Rubber seal

Proper Tightening Torque N⋅m Small bind screw


Tightening torque 0.5 to 0.6 N⋅m
VCA27 0.4 to 0.5
Gasket

Note) With a cable O.D. ø9 to 12 mm, hollow the rubber sealing before use.

Wiring Conduit terminal


In case of a conduit terminal, refer to the marks below for wiring.
Caution • Tighten each part with an appropriate tightening torque shown
1. Use electrical wires with a conductive sectional below.
area of 0.5 to 1.25 mm2. Make sure that no • Seal the piping part (G 1/2) securely with a dedicated electric
excessive force is applied to the wires. wiring pipe, etc.
2. Adopt an electrical circuit which will not cause Terminal cover
chattering at the contact. Round head combination screw
3. The voltage variation must stay within the –10% M3 A G 1/2
Tightening torque 0.5 to 0.6 N⋅m
to +10% range of the rated voltage. In case Tightening torque
0.5 to 0.6 N⋅m
importance is attached to response
+ Mark
- Mark

characteristics due to use of a DC power source, 2 1


- +
keep the variation within the –5% to +5% range.
A
The voltage drop is the value at the lead wire to
which the coil is connected.
Round head combination screw
M3 tightening torque 0.5 to 0.6 N⋅m
Conduit terminal
View A-A
(Internal connection diagram)