Professional Documents
Culture Documents
Abstract – This paper proposes a simple current compensation method to improve the control
performance of B4 inverters. Four-switch inverters so called B4 inverters employ only four switches.
They have a split dc-link and one phase of three-phase motors is connected to the center-tap of split dc-
link capacitors in B4 inverters. The voltage ripples in the center tap of the dc-link generate unbalanced
three-phase voltages causing current ripples. To solve this problem, this paper presents a simple
compensation method that adjusts switching times considering dc-link voltage ripples. The validity of
the proposed method is verified by simulations and experiments carried out with a 1 HP induction
machine.
1062
Dong-Myung Lee, Jae-Bum Park and Hamid A. Toliyat
+ + Va = 3Vo sin ωt − π
6
( )
+ −
−
+
1
[ (
⇒ Ta = 1 + ma sin θ − π ⋅ Ts
2 6
)]
(1)
− Vb = 3Vo sin ωt − π
2
( )
+ 1
[ (
⇒ Tb = 1 + ma sin θ − π ⋅ Ts
2 2
)]
−
−
The reference pole voltage for Δ-connection can be
Fig. 1. Configuration of B4 inverters for Y or ∆-connected obtained as (2). Comparing to Y-connection, Δ-connection
motors or loads. has a 30 degree difference, and 3 times bigger phase
voltages.
the so called B4 inverter shown in Fig. 1 has four switches
and one of the motor phases is connected to the central Va = Vo sin ωt − π (
3
)
point of dc-link capacitors.
With conceptually applied the reverse phase voltage in
1
2
[ '
(
⇒ Ta = 1 + ma sin θ − π ⋅ Ts
3
)]
the motor phase connected to the middle point of dc-link, (2)
B4 inverters generate three-phase voltages as shown in Fig.
(
Vb = Vo sin ωt − 2π
3
)
2. As a result, the generated two inverter pole voltages has
components of balanced three-phase voltages and zero
1
2
[ '
(
⇒ Tb = 1 + ma sin θ − 2π ⋅ Ts
3
)]
sequence voltages, thus enable to control three phase
motors [1]. Fig. 2 shows voltage phasor diagrams for (a) Y In each connection, generated phase voltages according
and (b) Δ-connected motors with the condition that the to (1) and (2) have 4 different effective voltage vectors as
motor phase C is connected to the middle point of dc-link listed in Tables 1 and 2. Where, 0 or 1 represents the switch
capacitors. Through this paper, it is assumed that the phase in the lower side or the upper side of the leg is turned-on,
C of the motor is connected to the dc-link for the analysis respectively. Table 1 summarizes the phase voltages for Y-
as well as simulations and experiments. Where Va and Vb connected motors operated by B4 inverters. Where, V1 or
are the pole voltages. Vas, Vbs, and Vcs are motor phase V2 means the voltage magnitude in the capacitor at the top
voltages. or the bottom of dc-link. Where phase voltages of ∆-
Fig. 2 shows the magnitude of phase voltage for Y- connected motors are listed in Table 2.
connection is less by 1 / 3 compared to the inverter pole B4 inverters have no zero voltage and all 4 voltage
voltage. While, that of ∆-connection is the same as the vectors are effective vectors. These four switching states
magnitude of pole voltage. From Fig. 2(a) for Y-connection, are noted as four modes according to switching status. In
it can be known that Va and Vb can be expressed as (1). Ta mode 1(0,0) of Tables 1 and 2, it can be known that only
and Tb are switching time of S1 and S3 for generating Va and the bottom capacitor is involved in the power transfer to
Vb, having 60o difference between them. ma ranges from 0 motors, and in mode 4(1,1) only the top capacitor transfers
to 1, and Ta and Tb are obtained as that from sinusoidal power to the motor. Depending on the mode, the capacitor
PWM. Where, ma, Ts, or θ is modulation index, sampling transferring power to the motor is changed, so that the
time, or angle of reference voltage. Vo is the magnitude of power flow in and out of this neutral point of dc-link
phase voltage. causes voltage difference between the upper and lower
capacitors.
Vca (Vcs ) Vab (Vas )
Vcs Vcn − Vbn Table 1. Phase voltages in Y-connection
mode S1 S3 Vas Vbs Vcs
− Vcs Vas
Van 1 1 2
1 0 0 − V2 − V2 V2
− Vbn 3 3 3
Vbs − Vcn 1 1 1
Va Vbn 2 0 1 − ( 2V2 + V1 ) ( 2V2 + V1 ) (V2 − V1 )
3 3 3
Va
Vb 1 1 1
Va = 3 Vas Va = Vas 3 1 0 ( 2V1 + V2 ) − ( 2V2 + V1 ) (V2 − V1 )
3 3 3
Vbc (Vbs ) Vb
1 1 2
(a) (b) 4 1 1 V1 V1 − V1
3 3 3
Fig. 2. Voltage phasor diagrams of B4 inverters with (a) Y-
connection and (b)Δ-connection.
1063
A Simple Current Ripple Reduction Method for B4 Inverters
Table 3. Real and imaginary components for each connection Table 3 also shows that real voltage components are zero if
Y-connection ∆-connection V1=V2, but they are positive values for V2>V1. If Ta and Tb
mode
Re. Im. Re. Im. calculated by (1) or (2) applied without modification, it
u1 1 V2 0 3V2 0 results in the voltage vector slanted to the right compared
1 3 3 3
to the reference voltage obtained under the condition V1=V2
u4 2 (V2 − V1 ) − (V1 + V2 ) (V2 − V1 ) − (V1 + V2 ) as illustrated in Fig. 4(b).
2 2 2 2
1 3 3 3
As noted previously, real and imaginary components for
u2 3 (V2 − V1 ) (V1 + V2 ) (V2 − V1 ) (V1 + V2 ) Y and ∆-connection shown in Table 3 has the same form
2 2 2 2
−V1 − 3V1
with different scale. Even severity of the voltage distortion
u3 4 0 0
depends on |V1-V2|, the tendency that slanted to the right
when V2>V1 or toward to the left if V1>V2 is identical
u3 (1,1) − ∆
regardless of connection types. Therefore, the current
u 4 (0,1) − Y ripple reduction method can be applied to both connection
types (Y and ∆) in the same way.
u3 (1,1) − Y The proposed current ripple reduction method can be
explained as follows. From Fig. 4(b), it can be known that
in order to reduce voltage error, switching time for making
u 4 (0,1) − ∆ u 2 (1,0) − ∆
the voltage vector tilted to the right should be shortened
and that for the left direction should be lengthen. In case of
u1 (0,0) − Y u 2 (1,0) − Y V1> V2, the duration time for u1 should be decreased and
u1 (0,0) − ∆ that for u3 should be increased.
Fig. 5 shows the switching times and corresponding
Fig. 3. Four effective voltage vectors with based on u1 voltage voltage vectors, which are located in region I or II, by the
vector for each Y and Δ-connection. center aligned PWM method. Where, tx denotes the
duration time for ux such as t1 time for u1 vector and t3 for
2.3 Proposed current ripple reduction scheme u3, and Ts is the sampling time. Region I is the first and
second quadrants, and equivalent to the condition of Ta>Tb.
The voltage distortion in B4 inverters due to the One the other hand, region II is the third and fourth
discrepancy between V1 and V2 can be known from Fig. 4. quadrants, and the voltage vector in that region has the
In the left side of Fig. 4(a) illustrates four effective voltage switching time of Tb>Ta. As shown in (1) and (2), only Ta
vectors when V1=V2, and that under the condition V2>V1 is and Tb are involved, so that the vector duration time such
shown at the right side. The voltage vectors that are as t1 and t3 are required to be calculated by using already
orthogonal each other when V2=V1 are tilled to the right if determined values of Ts, Ta, and Tb for implementation. In
V2 > V1 . region I, from Fig. 5(a) it can be known that t1=Ts –Ta, and
As shown in Table 3, u1 becomes bigger than u3 if V2>V1. t3=Tb, Where, in region II t1=Ts–Tb, and t3=Ta.
1064
Dong-Myung Lee, Jae-Bum Park and Hamid A. Toliyat
u2 (1,0) u2 (1,0)
u3 (1,1) u1 (0,0)
u3 (1,1) u1 (0,0)
u4 (0,1) u4 (0,1)
Ta Ta − Tb > 0
Tb
t1 2 t 2 2 t3 t 2 2 t1 2 t1 2 t4 2 t3 t4 2 t1 2
t1 = Ts − Ta , t3 = Tb t1 = Ts − Tb , t3 = Ta
(0,0) (1,0) (1,1) (1,0) (0,0) (0,0) (0,1) (1,1) (0,1) (0,0)
∆Ta = k (V2 − V1 ) / Vdc ⋅ t1 ∆Ta = k (V2 − V1 ) / Vdc ⋅ t3
(a) (b) ∆Tb = k (V2 − V1 ) / Vdc ⋅ t3 ∆Tb = k (V2 − V1 ) / Vdc ⋅ t1
Fig. 5. Determination of region by using the magnitude of
Ta and Tb with voltage vector located in (a) region I
and (b) region II.
Ta* = Ta + ∆Ta
Tb* = Tb + ∆Tb
In order to reduce the voltage error due to V2>V1, as
previously mentioned, t3 for u3 should be increased, and t1
for u1 should be decreased. Fig. 5(a) shows that making t1
longer and t3 shorten is equivalent to increasing both Ta and
Fig. 6. Flow chart for the proposed method.
Tb. By contrast, in case of V1>V2, it is necessary to decrease
both Ta and Tb, which is the same as making t1 larger and t3
smaller.
3. Verifications
The rule for changing switching times in region I can be
applied in region II with an identical manner. When V2>V1,
it is required to increase t1 and reduce t3, which is the same 3.1 Simulation results
as increment of Ta and Tb. Hence, regardless of regions, for
current ripple compensation, in case of V2>V1, Ta and Tb Figs. 7(a), (b) show simulation waveforms carried out by
should be increased, and required to be shorten when a Y-connected 1-HP induction motor without and with the
V1 > V2 . proposed current ripple reduction method, respectively. In
In the implementation, the switching time obtained by (1) Fig. 7, from top to bottom, C and A-phase voltages and
or (2) is modified with the form of t+Δt corresponding to phase currents of C and B-phase are illustrated. Comparing
the voltage difference in dc-link capacitors. Where, the with Figs. 7(a) and 7(b), it is obvious that the proposed
region is simply determined by comparing the magnitude method makes phase currents more sinusoidal and reduces
of Ta and Tb, i.e. when Ta>Tb, region is I, and if Tb>Ta the the magnitude difference between phase currents. THD of
voltage vector is located in region II. The compensation ics and ibs with 15.31% and 11.23% before compensation
time (Δt) consists of V2–V1, t1, t3, and k. Where, k is the has been reduced to 5.91% and 5.09% after the compensation.
compensation constant. It has nominal value of 1/2 to Figs. 8(a), (b) show simulation results obtained from ∆-
reflect the impact of the voltage difference equally to the connected induction motor. The waveforms in Fig. 8 are
switching time making the generated voltage vector to the V1&V2, Vbs, Vas, ics, and ibs. The amount of current ripple in
right and that to the left. In some noisy environments, this Fig. 8(a) without compensation is reduced remarkably by
k value can be adjusted to smaller than 1/2 to reduce the the proposed method as shown in Fig. 8(b). Besides the
effect caused by the detection error in voltage measurement. current ripple reduction, the ripple reduction in the voltages
The voltage distortion is proportional to the voltage of dc-link capacitors (V1 and V2) is observed.
difference in dc-link (V2–V1), and to compensate the The peak value of the waveforms showing phase voltage
distortion duration times of u1 and u3 are utilized. in Fig. 8 has the voltage magnitude listed in Table 2. The
Therefore, compensation time in region I is expressed as magnitude of A-phase voltage has -V1-V2 in mode 2, and
(3). Similarly, the amount of compensation in region II can V1+V2 in mode 4, otherwise zero voltage so that voltage
be obtained as (4). Fig. 6 illustrates the flow chart of the ripples are not shown in Vas of ∆-connected motors. On the
proposed compensation scheme. other hand, the voltage ripples in V1 and V2 are shown in
Vbs waveforms because the B-phase voltage has the form of
V2 and –V1 corresponding to different mode as listed in
V −V V −V
∆Ta = k 2 1 t1 , ∆Tb = k 2 1 t3 (3) Table 2. From Figs. 7 and 8, it can be known that all the
Vdc Vdc phase voltages in Y-connected motors are affected by
V −V V −V voltage ripples in V1 and V2, but in case of ∆-connection A-
∆Ta = k 2 1 t3 , ∆Tb = k 2 1 t1 (4)
Vdc Vdc phase voltage is not affected by voltage ripples.
1065
A Simple Current Ripple Reduction Method for B4 Inverters
(a) (b)
Fig. 7. Simulation results with Y-connected motors (a) without and (b) with the proposed method.
(a) (b)
Fig. 8. Simulation results with ∆-connected motors (a) without and (b) with the proposed method.
(a) (b)
Fig. 9. Experimental results with Y-connected motors, (a) without and (b) with the proposed method.
3.2 Experimental results upper and lower dc-link capacitors. Each capacitor in dc-
In order to verify the validity of the proposed system, link has the capacitance of 100µF for Y-connected and
experiments using an induction motor were performed with 940µF for ∆-connected motors. As shown in Table 2 for ∆-
the same condition of simulations. The proposed algorithm connection, the magnitude of voltage transition between
was implemented by TM320F28335 digital signal processor modes is larger than that for Y-connection. In addition,
with 8 kHz sampling time, and voltage measurements of when remaining voltage to frequency ratio (V/F ratio) for
1066
Dong-Myung Lee, Jae-Bum Park and Hamid A. Toliyat
(b)
(a)
Fig. 12. Experimental results with the proposed compensa-
tion method applying for ∆-connected motors.
1067
A Simple Current Ripple Reduction Method for B4 Inverters
on differential equations were developed. The compensation No. 1, pp. 164- 172, Jan. 2003.
method based on modification of switching time was [10] M. N. Uddin, T. S. Radwan, and M. A. Rahman,
applied to both connection types. The simulation and “Fuzzy-logic-controller-based cost-effective four-
experimental results applied in an induction motor with Y switch three-phase inverter-fed IPM synchronous
and ∆-connection have verified the control performance motor drive system,” IEEE Trans. on Industry Appli.,
and the validity of the proposed method. Vol. 42, No. 1, pp. 21-30, Jan./ Feb. 2006.
[11] C. T. Lin, C. W. Hung, and C. W. Liu, “Position
sensorless control for four-switch three-phase
Acknowledgements brushless DC motor drives,” IEEE Trans. on Power
Elect., Vol. 23, No. 1, pp. 438-444, Jan. 2008.
This work was supported by the National Research [12] B. A. Welchko, T. A. Lipo, T. M. Jahns, and S. E.
Foundation of Korea Grant funded by the Korean Schulz, “Fault tolerant three-phase AC motor drive
Government MEST, Basic Research Promotion Fund) topologies: a comparison of features, cost, and
(NRF-2012S1A2A1A01030731) limitations,” IEEE Trans. on Power Elect., Vol. 19,
No. 4, pp. 1108-1116, July 2004.
[13] H. G. Park, S. H. Jang, D. C. Lee, and H. G. Kim,
References “Low-cost converters for micro wind turbine systems
using PMSG,” ICPE '07, Oct. 2007, p. 483-487,
[1] H. van der Broeck, and J. van Wyk, “A comparative [14] S. Dasgupta, S. N. Mohan, S. K. Sahoo, and S. K.
investigation of a three-phase induction machine with Panda, “Application of four-switch-based three-phase
a component minimized voltage-fed inverter under grid-connected inverter to connect renewable energy
different control options,” IEEE Trans. on Indus. source to a generalized unbalanced microgrid system,”
Appli. Vol. 20, No. 2, pp. 309-320, Mar./Apr. 1984. IEEE Trans. on Indus. Elect., Vol. 60, No. 3, pp. 1204-
[2] F. Blassbjerg, H. Kragh, D.O. Neacsu, and J. K. 1215, Mar. 2013.
Pedersen, “Comparison of modulation strategies for
B4-inverters,” EPE, Vol. 2, 1997, p. 378-385.
[3] C.B. Jacobina, and B.R. Correa, “Induction motor Dong-Myung Lee He received his B.S.
drive system for low-power applications,” IEEE Trans. and M.S. in Electrical Engineering
on Indus. Appli., Vol. 35, No. 1, pp. 52-61, Jan./Feb. from Hanyang University, Seoul, Korea,
1999. in 1994 and 1996, respectively, and his
[4] F. Blaabjerg, D. O. Neacsu, and J. K. Pederson, Ph.D. in Electrical and Computer
“Adaptive SVM to compensate dc-link voltage ripple Engineering from the Georgia Institute
for four-switch three-phase voltage-source inverter,” of Technology, Atlanta, Georgia, USA,
IEEE Trans. on Power Elec., Vol. 14, No. 4, pp. 743- in 2004. From 1996 to 2000, He worked
752, July 1999. for LG Electronics Inc., Seoul, Korea. From 2004 to 2007,
[5] D. M. LEE, J. Y. Oh, and D. H. Cheong, “A voltage he was employed by the Samsung SDI R&D Center,
compensation method to improve the control perfor- Yongin, Korea, as a Senior Engineer. From 2007 to 2008,
mance for B4 inverters,” Power Elect. Annual Conf., he was with the Department of Electrical Engineering,
2000, p. 317-320 Hanyang University, as a Research Professor. Since 2008,
[6] J. H. Kim, J. S. Hong, and K. H. Nam, “A current he has been an Associate Professor with the School of
distortion compensation scheme for four-switch Electronic and Electrical Engineering, Hongik University,
inverters,” IEEE Trans. on Power Electronics, Vol. Seoul, Korea. He was a visiting scholar of Texas A&M
24, No. 4, pp. 1032-1040, April 2009. University in 2012. His current research interests include
[7] M.B. de R. Correa, C.B. Jacobina, E.R.C.da Silva, variable speed drives, power quality compensation devices,
and A.M.N. Lima, “A general PWM strategy for four- and power conversion systems for renewable energy
switch three-phase inverters,” IEEE Trans. on Power sources.
Elect., Vol. 21, No. 6, pp. 1618-1627, Nov. 2006.
[8] R. Wang, J. Zhao, and Y. Liu, “A comprehensive
investigation of four-switch three-phase voltage Jae-Bum Park He received the B.Sc
source inverter based on double Fourier integral degree in electrical engineering in 2002
analysis,” IEEE Trans. on Power Elect., Vol. 26, No. and the M.Sc degree in Electrical
10, pp. 2774-2787, Oct. 2011. Engineering from the ECL(Energy
[9] B. K. Lee, T. H. Kim, and M. Ehsani, “On the Conversion Laboratory) at Hanyang
feasibility of four-switch three-phase BLDC motor University, Seoul, Korea in 2005. His
drives for low cost commercial applications: topology M.Sc thesis topic was “Single-Phase
and control,” IEEE Trans. on Power Elect., Vol. 18, Switched Reluctance Motor Optimum
1068
Dong-Myung Lee, Jae-Bum Park and Hamid A. Toliyat
Design Using Response Surface Methodology and Finite Paper Award. His main research interests and experience
Element Method”. During his time as a graduate student, include analysis and design of electrical machines, variable
he completed an internship which focused on a control speed drives for traction and propulsion applications, fault
system of PM Linear machines for the baggage claim at diagnosis of electric machinery, and sensorless variable
Nuremberg Airport with SIEMENS AG in Erlangen, speed drives. Prof. Toliyat has supervised more than 50
Germany. Then he joined Motor Lab. in LG Components graduate students, published over 385 technical papers
R&D Center, Korea as a research engineer in 2004. He has (over 115 papers are in IEEE Transactions), presented more
worked on machine design and control drives for ODD and than 80 invited lectures all over the world, and has 13
EV applications. In August 2010, he began working issued and pending US patents. He is the author of DSP-
towards a Ph.D in electrical engineering at Texas A&M Based Electromechanical Motion Control, CRC Press,
University and He is associated with the EMPE(Electrical 2003, the co-editor of Handbook of Electric Motors - 2nd
Machines & Power Electronics) Laboratory working with Edition, Marcel Dekker, 2004, and the co-author of Electric
Dr. Hamid A. Toliyat. Jae-Bum’s research interests include Machines – Modeling, Condition Monitoring, and Fault
machine design (such as IPM, SPM, PMa-SynRM, SRM, Diagnosis, CRC Press, Florida, 2013.
IM, and BF-SRM) and DSP based control drives (power He was the General Chair of the 2005 IEEE Inter-
converters & inverters) for HEV and EV applications. He national Electric Machines and Drives Conference in San
is currently working on multi-phase PMSM & BF-SRM Antonio, Texas. Dr. Toliyat is a Professional Engineer in
design for green car applications and inverter circuit for the State of Texas.
6MW PMSM and 3kW PMa-SynRM.
1069