SCR-01~02Production M1 Area ACID SCRUBBER SYSTEM WP 53 Ducting works SBV 1200-1500, ACE VIETNAM 02 Sets
- Vertical Scrubber: MALAYSIA / TAIWAN
Scrubber: JAPAN / ITALY / USA
Type: Vertical Counter Flow
Capacity (m3/hr): 6,000
Dimension (mm): ID 1,200 x 4,800 (H), mm
Spray Nozzle:
Type: Full Cone Nozzle
Material: PP
Capacity: 62.9 lit/min x 0.7 bar
- Acid Exhaust Fan:
Type: Centrifugal Backward Curve
Capacity (m3/hr): 6,000
Static Pressure (Pa): 2,000
RPM 1,477
Motor Size (Kw): 7.50
VSD Operation
- Recirculation Pump:
Type: Vertical Pump
Capacity: 200 lit/min
Total Head: 12m
- Chemical Dosing Pump:
Type: Metering Pump
Capacity (m3/hr): 0.05 lit/min x 1.0 Mpa
1/1
Commercial Proposal
AIR TREATMENT SYSTEM
Submitted to
I. Design Basic
DESIGN BASIS
ABSORTION SCRUBBER FOR ACID FUME TREATMENT (SC-101)
INLET CONDITION
- PRESSURE : ATMOSPHERE
The absorbing liquid is re-circulated by the circulation pump made from anti corrosive
material to minimize the water consumption and operating cost. This pump use the
liquid from the sumptank below of scrubber to a network of discharge nozzles at the
main discharge header. It ensures the absorbing liquid is sprayed equally over the total
packing top. The the absorbing liquid flows down the packing media by gravity and is
collected and recirculated in the supmtank.
To ensure maximium efficiency, the pH of absorbing liquid is meansured continuously
by a pH controller and chemical dosing system.
The salt concentration inside the sumptank has to be limited to prevent crystallizing in
the absorbing liquid thus decreasing the absorption efficiency of this liquid. It is
controlled by the conductivity controller. The fresh water adding is controlled
automatically via a solenoid valve and level switches.
After that, the treated exhaust air will pass throught a demister layer before discharging
out. It is used to capture the water droplet in the treated exhaust and turn back to the
supmtank.
1. Vertical Scrubber
2. Exhaust Fan
3. Recirculation Pump
MRussell: Include dosing pump box for containment purposes. Typically on top of Dosing/Chemical Tank.
6. Instrument List
A. Level Switches for Scrubber
Be used for controlling the adding of fresh water to the sumptank
POWER : 20 VDC.
C. Pressure Gauge
Be used to monitor the pressure built up of the recirculation pump
PI-101 PRESSURE GAUGE TYPE : BOURDON TUBE & COIL SPRING MEASURING
D. Solenoid Valve
Be used to ON/OFF Valve automatically
MATERIAL : BRASS
E. pH Controller
Be ued to monitor the pH level of absorbing liquid
CABLE : 10 m
BODY : PVDF
I. Auto Damper
Be used to monitor the damper in front of scrubber; behind the scrubber and in front of
fan
MATERIAL : PP
TEMPERATURE
7. Accessories
Completed Accessories include
- The Ducting for Scrubber, complies PN2.5, material FRP (Vinyl Ester Resin)
- The Piping for circulating absorbing liquid, complies PN6, material PVC
- Support for the duct work
- Manual valve
- Electrical system:
Outdoor type
For controlling scrubber system, dosing pump
Automatic control with ON / OFF signal from the relay
Display pump / fan operation status via light
Emergency ON/OF System
MRussell: Indicate on attachments which pumps, sensors, valves, etc... that is being submitted on.
MRussell: Provide detail drawing from manufacturer (side, top, front, isometric view) for review.
MRussell: Review for
dosing pump that is
being submitted.
Does require
discharge piping back
to the dosing tank as
well?
SELF-PRIMING CHEMICAL PUMPS
༭ ถ टሗᢄՍ֝ԓϾᏱࣆ
قӗࠣ
ᐡఢໆࡍࣆᆤӬҭᓄ
SD/LD/HD/SG/SL/SE/HL/SAS SERIES
Pa 1-10 SD/LD/SL/HL SERIES
Page
Page 14-16
4 16 SE SERIES
Page 23 VP-480
Page 24-25 範例
Teflon Bellows Seal Series
SD - 40 02 2 N B L CCH 6
A - Fixed-Seal Socket
ۢڿᕘ৵
E - Self-Priming Cover
Ս֝๎
C - Recycle Hose
տࠔඊᕘᆔ
1
B - Bellows Bellows-seal
A - Fixed-Seal Cover SD/SL series, with the unique seal assembly, is easy to
combination
Socket !!ໆࡍៗဌ !ࠊໆࡍ disassemble and replace. The fixed seal socket can be
ۢڿᕘ৵
made of high temperature-resistant plastic PPS and is
capable of operating up to 130ʨ while dry running.
SD/SLԥᑀঢ়೪ॏໆࡍៗဌȂܼܷܿڤІඳȄ
ۢڿᕘ৵ѠຝϾᏱܓᒶᐆटାྤ؆፵QQT༮ᓂᇨԚȂණЁट
ޫᙾྤ࡚Ȅ
2
TE0ME0TM0IMTFSJFTQVNQT
The SD/LD/SL series are dependable, self priming pumps. The full motor horsepower is translated into
flow via the shaft. These pumps are used for a wide range of applications, from chemical transfer to
process solution recirculation to waste treatment. This series is capable of self-priming up to 20 feet of lift.
The mechanical seal is a self-cooling, Teflon bellows which is cooled by the solution being pumped. The
construction materials and seals avaiable make this pump extremely versatile. The horizontal design has
a working temperature from167ʩ to 185ʩ(70ʨ to 85ʨ), depending on the material of construction, and
can handle most chemical solutions. The SD/LD/SL series pumps are designed to run outside the tank or
process module. The SD/LD series pumps incorporate a FRPP molded base, frame and pump-to-motor
casing. There are no bolts or metallic parts in contact with the solution being pumped.
SD/LD/SLࣆѠᎭޠՍ֝ࣆȂ଼ႁӓഌ଼ޠΩစҦໆЗӓᙾϾ࣐ࢻ໕ȂԫࣆኅހӵٻңܼϾᏱЬ
ඊᕘܗђϏྚషඊᕘژኁЬ౪๊өᆎңഋȂࣆޠՍ֝Ω੬ȂٸੀϛӤȂഷାѠႁ31֑Ȃᐡఢໆࡍ
ՍשտࠔޠȂစҦܫଛྚޠషٿտࠔȂѠٽᔗޠϛӤ๗ᄻ؆፵ІໆࡍٻԫᆎࣆޠңഋߩளӼኻϾȂڐٸ๗
ᄻ؆ਠޠϛӤȂڐԓ೪ॏޠϏձྤ࡚Ҧ70ʨژ85ʨȂՅйѠ౪๙τഌӌޠөᆎྚషȂSD/LD/SL೪
ॏңܼѵܗђϏዂಣϟңȂSD/LDђΤΚঐFRPPৣяԚޠရ৵Ȃရ࢝Іࣆ଼ژႁޠѵဌȂءԥᖴܗ
ߝ឵ཽ௦ដܫܛژଛྚޠషȄ
HL Type
SD Type
S yp
SL Type
LD Type
3
Tqfdjgjdbujpot Testing fluid: Water(Specific gravity 1.0)
M L/min M
L/min
SD / LD 40012H 40x40 3 1 2 a 13 240 B 16 240 31 / 31
SD / LD 40014L 40x40 3 1 4 c 8 230 C 9 270 31 / 31
SD / LD / SL 40022L 40x40 3 2 2 d 17 360 D 20 320 39 / 39 / 75
SD / LD / SL 40022H 40x40 3 2 2 e 19 350 E 25 350 39 / 39 / 75
SD / LD / SL 40032H 40x40 3 3 2 f 25 400 F 28 410 43 / 43 / 80
SD / LD / SL 50032L 50x50 3 3 2 g 21 380 G 22 360 43 / 43 / 80
SD / LD / SL 50032H 50x50 3 3 2 h 23 400 H 30 430 43 / 43 / 80
SD / LD / SL 50052H 50x50 3 5 2 i 26 450 I 34 550 55(70#)/55/83
SD / LD / SL 75052H 75x75 3 5 2 j 26 750 J 33 800 56(71#)/ /84
SD / SL 75072H 75x75 3 7.5 2 k 26.5 900 K 38 960 120
SL 75102H 75x75 3 10 2 l 28 960 L 40 1000 125
HL 40032 40x40 3 3 2 o 24 370 82
HL 50032 50x50 3 3 2 p 24 400 82
HL 50052 50x50 3 5 2 q 32 430 85
HL 65052 65x65 3 5 2 r 29 660 86
HL 65072 65x65 3 7.5 2 s 30 780 122
HL 75072 75x75 3 7.5 2 t 30 820 122
HL 75102 75x75 3 10 2 u 35 880 127
The weight,(which is based on FRPP pump head) of SD series 3.75kW with cast iron frame are marked with #.
ພ݃ # ࣐ SD ᐡᆎ3.75kWཧପᠦ២ရ৵ϟ२໕Ȃ२໕অְпFRPP؆፵࣐ྦȄ
ɏFrame out of FRPP or cast iron are available for SD 3.75kW model.
ɏSD 3.75kWᐡရ৵ԥFRPP Іᠦ២ڎᆎ!
ɏпᄃޑ२໕爲ྦ!
LD SD SL Series
40 40
30 30
h
20 20
e
F L
d l
10 10 K
k E G H I J
D
a i j B C
g f
c
0 100 200 300 400 500 600 700 800 900 1000 0 100 200 300 400 500 600 700 800 900 1000
HL Series
40
30
20
10 q
o p r u
s
t
0 100 200 300 400 500 600 700 800 900
4
SD/LD/SL MECHANICAL SEAL PUMPS
CFRPP FRPP CPVC PVDF
Ø12-4 N
280 P
-4 H E
Ø12
K
5
DIMENSION GRAPH
SD/LD 3.75 kW, 3" with FRPP frame ØW
A ØT
SD 5.5 kW, 3" with FRPP frame
SD/LD/SL MECHANICAL SEAL PUMPS
D
G
C
50
Ø12-4 N
280 P
-4
Ø12
H E
K
DIMENSION TABLE Unit:mm
MODEL A C D E G H K N P T W
SD75052 117 150 340 360 390 140 800 204 250 150 185
SD75072 117 150 340 360 390 140 815 204 250 150 185
ØW
A
ØT
SD/LD 3.75 kW, 2" with cast frame
SD/LD 5 HP, 2" ཧପᠦ២ရ৵Аωშ
D
G
C
50
Ø12-4 N
280 P
-4
Ø12 H E
DIMENSION TABLE K Unit:mm
MODEL A C D E G H K N P T W
SD/LD50052 132 295 362 263 390 160 813 190 250 120 155
Ø12-4 N
280 P
-4 H E
Ø12
K
6
DIMENSION GRAPH
D
C
Ø12X4 H N
K P
DIMENSION TABLE ɏАωߓCཽӱႬᐡࠣทϛӤՅᡑ Unit:mm
MODEL A B C D F H K N P T W
SL40022L 132 830 312 390 82 525 710 320 362 105 140
SL40022H 132 830 312 390 82 525 710 320 362 105 140
SL50032L 132 830 312 390 82 525 710 320 362 120 155
SL50032H 132 830 312 390 82 525 710 320 362 120 155
SL50052H 132 885 312 390 82 525 710 320 362 120 155
HL40032 132 833 327 405 82 525 710 320 362 120 155
HL50032 132 833 327 405 82 525 710 320 362 120 155
HL50052 132 888 327 405 82 525 710 320 362 120 155
HL65052 160 915 447 419 82 525 710 320 362 150 190
HL65072 160 995 447 419 97 590 780 320 362 150 190
HL75072 160 995 447 419 97 590 780 320 362 150 190
HL75102 160 995 447 419 97 590 780 320 362 150 190
D
C
Ø12X4 H N
K P
DIMENSION TABLE ɏАωߓCཽӱႬᐡࠣทϛӤՅᡑ Unit:mm
MODEL A B C D F H K N P T W
SL75052H 117 935 224 410 82 525 710 320 362 150 185
SL75072H 117 1015 224 410 97 590 780 320 362 150 185
SL75102H 117 1015 224 410 97 590 780 320 362 150 185
7
CONSTRUCTION
1/2~5HP
9
1 5C
9-1
9-5
5D 9-4
9-2
2 3B
9-3
9-6
5A 10-1
5B 10 10-1
11
9 12-1
12 13 14
19A
15 6
15-1
18
17 4
1 / 2 ~ 5 H P 9
1 9-1
5C 9-5
9-4
5D 9-2
9-3
9-6
2
8
8-1
5A 7
5B 7-1
3A
10-1
10
9 11
12-1
12 13 14
19A
6 16-1 10-2
15
15-1 16A
15
4
15-1 18 16
17 16-2
16-1 16A
16A
16-1
17A-1 16-1
16-1 17A 16A
16A
88
2~10HP
1.5~7.5kW2
9
1 9-1
9-5
9-4
9-2
9-3
9-6
5C
5D
20 2
20-1
2C 2B
2
2A
19 5A 5B 8
21 8-1 7
7-1
10-1
2A 10
2B
2C
3A
16-1 10-2
9 11
12-1 15 16A
12
13 14
15-1 6
15
4 15-1 18
16
17
16-2
16A 16-1
16-1 16A
NOTES OF FRAME For our 1/2HP model, the motor casing is same as the one for 1HP
motor (No. AVEF-80) to conform to our FRPP frame. Hence the
ရ৵ٻңᇴ݃ standard 1/2HP motor cannot match this frame.
ҐϵѨϲഌੀȈSD/LDᐡᆎȂ1/2HPᐡְ௵ң1HPᐡϟ༮ᓂရ৵
Ȃཧପߩርዀྦ଼ႁȂڐਲဵ࣐! AVEF-80Ȃࢉርዀྦϟ଼ႁณݳ
FRPP Frame
e
༮ᓂရ৵ ٻңȄ
For our 5HP model, the motor casing is same as the one for 3HP
motor (No. AVEF-100L) to conform to our FRPP frame. Hence the
standard 5HP motor cannot match this frame.
ҐϵѨϲഌੀȈSD/LDᐡᆎȂ5HPᐡְ௵ң3HPᐡϟ༮ᓂရ৵Ȃ
ཧପߩርዀྦ଼ႁȂڐਲဵ࣐ AVEF-100LȄ
Option:For
O our 5HP model with standard motor, the casing No. of
motor
m which conform to our cast iron frame is AVEF-112M. And name
the
th model as following:
Cast Iron Frame
me
e
ᠦ២ရ৵ Add
A a code "F" behind the model name. For example:SDC - 75052
5HP଼ႁዀྦң ң VBH
V CCH 6 - F
੬ੇᒶᐆȈཧପርዀྦ଼ႁȂਲဵ࣐!
੬ AVEF-112MȂ! ௵ңᠦ២ရ
৵ȂဵڐዀұРԓԄίȈӶဵࡤ८ђαхጇȄ!
৵
ጓ!;پ
ጓ SDC - 75052 VBH - CCH 6 - F
99
Ⴎӈхဵᄈྲߓ
1 2 2A 2B 2C 3A 3B 4
SL SD/LD SD/LD
FRPP /
FC FRPP FC CFRPP NBR / EPT
FC STEEL FC PP FRPP / VITON
3.75kW CPVC / PVDF
5A 5B 5C 5D 6 7 7-1 8 8-1
NBR / EPT
CARBON HASTELLOY-C NBR / EPT / VITON NBR / EPT CERAMIC / NBR / EPT NBR / EPT
/ SSIC TEFLON / SUS316 / VITON TEFLON / VITON SSIC / VITON / VITON
10
10
HD - 40 02 4 - V B L - SSH 6
(1) (2) (3) (4) (5) (6) (7) (8) (9)
(1) TYPE ᐡጢဵ 02:2HP (1.5kW) (6) B - ณՐ
HD-FRPP(PP+࣡ᡋ) 03:3HP(2.25kW) (7) L - մඵโ Low head
HDP-CFRPP(PP+ᆈᡋ) (4) Pole!྄!4-4P (8) ϲ၇ԓໆࡍੀ
(2) In-Outlet яΤπ৸ (5) Elastomer ᐝጳ؆፵ CCH SSH SCH
E - EPDM (9) Frequency ᓝ౦
40 - 1-1/2" 50 - 2"
65-2-1/2" 80-3" N - NBR 5:50Hz 6:60Hz
V - VITON
(3) Power (HP) ଼Ω ● FRPP/CFRPP constration.!
01:1HP (0.75kW) ● Solution temperature : FRPP/CFRPP- Under 85ʚ Ǵdepending
● ࣆᡞ؆፵ԥFRPP,CFRPPڎᆎȄ on the chemicals.
● ᎍңྤ࡚Ȉ85ʨпί 、ຝөᆎϾᏱܓϛӤՅۢȄ
● Unique chemical seal : Teflon Bellows seal is a self-cooling, has
● ᑀ੬ޠᐡఢໆࡍ೪ॏȈ௵ңTeflon Bellows Seal Ստԓ೪ॏ
!!ȂٯԥւտࠔඊᕘଠၰȂӶޫᙾਣཽւңࣆϲഌޠషᡞඊ patent of cooled recirculation. When idling solution in the pump
!!ᕘȃտࠔᐡఢໆࡍȂໆࡍ؆፵ȈSsic,Carbon,CeramicȄ will be cooled by recirculation. Seal material : SSIC , carbon ,
● Ս֝ԓ೪ॏȈՍ֝Ω੬ȂٸੀϛӤഷାѠႁѠႁ20ft。 ceramic.
● ᆼᇠܓȈ௵ңөᆎ੬ੇ༮ᓂ؆፵ᇨԚȂԥFRPPȂCFRPP-
● Self-priming : this series is capable of self-priming up to 20
!!ѠܱτഌӌޠሗᢄషȄ
feet of lift.
● ໆࡍៗဌᑀ੬೪ॏȈ௵ңѠϸ၍ԓ೪ॏܷܿڤඳȂٸϾᏱ
!!ܓᒶᐆϛӤटାྤ؆፵ᇨԚȂϛܿӱޫᙾՅᚾȄ ● Excellent chemical resistance: Various special plastic such as
ɏѯུಒ55894Ȃ141347ဵւȄ FRPP & CFRPP which can prevent the attack of most chemicals.
ɏϜᄃңུಒZL 96 22573.8ဵւȄ
● Unique seal cover : The unique seal assembly is easy to
ɏпᄃޑ२໕爲ྦ!
)ขၑࢻᡞȈЬ!Щ२2/1* disassemble and replace.
15 15
10 10
B
b f
a DA
5 de j 5
H I K J
i G
g h k
0 100 200 300 400 500 600 700 800 0 100 200 300 400 500 600 700 800
11
11
A
G
C
50
Ø12-4 N
280 F P
-4 H E
∅12
K
1/2~3HP
1
5C
5D
2
8
8-1
7
5A 5B 3A
7-1
10-1
10
9 11
12-1 12 13 14
19A
16-1 10-2
6
15
16A
15-1
4
15 6
15-1 18 16
17
16-2
16-1 16A
16A
16-1
12
2
Ⴎӈхဵᄈྲߓ
1 2 3A 3B 4 5A 5B 5C
଼ႁ ရ৵ ࡤࡍᇑ LDΚᡞԚ ࡤᇑOᕘ ໆЗ ໆ ໆЗۢڿ
Motor Frame Rear cover ࡤࡍᇑ Rear Cover Shaft Shaft Sleeve ᖴ
Combined Rear O-ring Shaft Screw
cover
HASTELLOY-C NBR / EPT NBR / EPT NBR / EPT NBR / EPT NBR / EPT
TEFLON / SUS316 / VITON / VITON TEFLON / VITON CERAMIC / SSIC / VITON / VITON
11 12 12-1 13 14 15 15-1 16
ဩᎉ ဩᎉᖴ ဩᎉᖴOᕘ Ϝࡍᇑ Ӫሩ! ݨЬᇑ ݨЬᇑOᕘ ඊᕘᆔ
Impeller Impeller Screw Impeller Screw Check Cover Check Valve Water Filling Cap Water Filling ֥௦ᓟ
O-ring Cap O-ring Recycle Hose
)ณՐ*
FRPP / FRPP / CFRPP NBR / EPT FRPP / NBR / EPT NBR / EPT
CFRPP FRPP /
CPVC /PVDF / VITON CFRPP / VITON TEFLON CFRPP / VITON TEFLON
NBR / EPT
NBR / EPT NBR / EPT / VITON
/ VITON FRPP / CFRPP PVDF / SUS / VITON TEFLON FRPP
13
SE - 25 SK - 1/2 6 N F - C C H
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
(1) TYPE ᐡጢဵ.SE (5) Frequency ᓝ౦ (8) Fixed-seal ۢڿᕘ
(2) In-Outlet яΤπ৸ 5-50HZ 6-60HZ !!!! C - Ceramic ഞ౯
25 - 1" 40 - 1-1/2" (6) Elastomer ᐝጳ؆፵ S - SSIC
(3) Specific Gravity Щ२ V - VITON (9) Rotational-seal ᙾᕘ
SK - 1.0 SP - 1.3 N - NBR C - Carbon ᆈષ
(4) Power (HP) ଼Ω E - EPDM S - SSIC
1/2 - 1/2HP !!3/4 - 3/4HP (7) Material ࣆᡞ؆፵ (10) Bellows Spring ኇᙌ
1 - 1HP 2 - 2HP F - FRPP H - Hastelloy - C
K - PVDF S - SUS316
● ᎍңྤ࡚ȈFRPPȃPVDF 85ʨпίȂຝөᆎϾᏱܓϟ ● Solution temperature: FRPP, PVDF Under 85ʨ, depending
!!ϛӤՅۢȄ
on the chemicals.
● ᑀ੬ޠᐡఢໆࡍ೪ॏȈ௵ңTeflon Bellows SealՍտԓ
● Unique chemical seal: Teflon Bellows Seal is a self-cooling,
!!೪ॏȂٯԥւտࠔඊᕘଠၰȂӶޫᙾਣཽւңࣆϲഌ
has patent of cooled recirculation. When idling solution in
!!ޠషᡞඊᕘտࠔᐡఢໆࡍȂໆࡍ؆፵ȈSSIC,Carbon,
the pump will be cooled by recirculation.Seal Material: SIC,
CeramicȄ
Carbon, Ceramic.
● Ս֝ԓ೪ॏȈՍ֝Ω੬ȂٸੀϛӤȄ
● Self-priming: This series is capable of self-priming up to 20
● ᆼᇠܓȈ௵ңөᆎ੬ੇ༮ᓂ؆፵ᇨԚȂ
feet of lift.
!!ԥFRPP,PVDFѠܱτഌϸޠሗᢄషȄ
● Excellent chemical resistance: Various special plastic such
ɏϜᄃңུಒ ZL 98 2 05952.3 ဵւ
as FRPP, PVDF prevent the attack of most chemicals.
)ขၑࢻᡞȈЬ!Щ२2/1*
In/Outlet Power଼ Ω 50HZ 60HZ
Model π৸(mm) Weight
ԓ २໕
In Out Phase Curve Max.Head Max.Flow Curve Max.Head Max.Flow kg
Τπ яπ ࣻ HP kW ԣጤ ӓඵโ M ӓࢻ໕ L/min ԣጤ ӓඵโM ӓࢻ໕ L/min
25SK-1/2 25 25 3ø 1/2 0.4 a 7.5 155 A 11 160 19
40SK-1/2 40 40 3ø 1/2 0.4 b 8 185 B 11 190 19
25SK-3/4 25 25 3ø 3/4 0.6 c 9.5 175 C 13 190 20
40SK-3/4 40 40 3ø 3/4 0.6 d 8 195 D 13 230 20
40SK-1 40 40 3ø 1 0.75 e 11 225 E 15 250 21
40SK-2 40 40 3ø 2 1.5 f 14.5 260 F 25 320 29
e f
a d
c b
14
C
B A K
I
H
G
J
E D
F
1 9-1
1A 9-5
9-4
9-2
2 9-3
3 9-6
5B 10-1
19A 10 9 11
12-1
12
4 13
16-1
10-2
16A
6
15
15-1 18
17 16
16-2
16A
16-1
16-1 17A-1
16A 17A
16-1 16A
15
Ⴎӈхဵᄈྲߓ
1 1A 2 3 4 5B 6 9
NBR / EPT
FC NBR GSQQ TEFLON FRPP / PVDF
FRPP / PVDF / VITON TEFLON
16
6
SG - 40 02 2 - N H - C C H - 5 N
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11)
(1) TYPE ᐡጢဵ 07Ȉ7.5HP 10Ȉ10HP (7) Fixed-seal ۢڿᕘ (10) Frequency ᓝ౦Ȉ
SG - ࣆᡞ؆፵FRPP 15Ȉ15HP C - Ceramic ഞ౯ !!!!5 - 50HZ 6 - 60HZ
SGK - ࣆᡞ؆፵PVDF (4) Pole!྄ 2Ȉ2P S - SSIC (11)N - 標準機型
(2) In-Outlet яΤπ৸ (5) Elastomer ᐝጳ؆፵ (8) Rotational-seal ᙾᕘ T - ◮ໆЗ
40!.!1-1/2" 50 .!2" N - NBR C - Carbon ᆈષ
75 .!3" 100 .!4" E - EPDM S - SSIC
125 .!5" V - VITON (9) Bellows Spring ኇᙌ
(3) Power (HP) ଼Ω (6) L - մඵโ!Low head H - Hastelloy - C
01Ȉ1HP 02Ȉ2HP H - ା྇โ!High head S - SUS316
03Ȉ3HP 05Ȉ5HP
● Solution temperature : FRPPǴPVDF Under 85ʚǴdepending on the
● ᎍңྤ࡚ȈFRPPȃPVDF!85ʨпίȂٸөᆎϾᏱܓ
chemicals.
!!ϟϛӤՅۢȄ
● The applicability : It can withstand various chemicals depend on the material
●!ᎍңϾᏱܓȈᒶᐆөᆎࣆᡞ؆፵ȂѠटሗᢄȄ
●!ᑀ੬ޠໆࡍ೪ॏȈ௵ңTeflon Bellows SealՍտԓȂ of pump.
!!ٸөᆎϾᏱܓᒶᐆໆࡍ؆፵Sic, Carbon,CeramicȄ ● The unique seal : The seal is made of different materials, SIC, Carbon,
●!ࡤࡍᇑ࣐ΚᡞԚȂಣ၇ᙐܿȂณտࠔඊᕘଠၰ೪ॏȂ Ceramic could be chose.
!!ϛѠޫᙾٻңȄ ● SG series, several parts are combined into one brand-new rear cover.
●!лᡞପӈԚҐၷմȂৡܿಣ၇ІᆱঔȄ It lower the cost of pump head and parts, and makes it more easy to
● ࣆԋ၇մܼష՞ȂΤπђ၇ᘯᆪȄ
disassemble and repair. But it’s easier to be damaged in dry running due to
30 50
25
40
20
k 30
15
J
20
10
k
e D E
h
5 a d j 10 C
c f g B F G H
b i A I
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 0 100 200 300 400 500 600 700 800 900 1000 1100 120013001400 1500
17
H
G L
C K
B
D
A
J E Ø12X4 I
F
1
1A 9-1
9-5
2 9-4
8 9-2
8-1 9-3
9-6
7
5B 7-1 3B
10-1
19A 10 9
11
12-1
12 6
16-1 10-2
16A
18
8
Ⴎӈхဵᄈྲߓ
1 1A 2 3B 4 5B 6 6-1
଼ႁ ໆЗҤ ௦Ӭ৵ ಣӬԓࡤࡍᇑ ΚᡞԚ ࡤᇑOᕘ ໆ лᡞࠊᇑ ࠊᇑ௷ሩ
Motor Oil-Seal Commected Rear cover ࡤࡍᇑ Rear Cover Shaft Sleeve Front Cover
Seat Rear cover O-ring
PPS / FRPP /
NBR / EPT
FRPP / CFRPP NBR / EPT CFRPP / VITON
VITON CPVC / PVDF / VITON CPVC / PVDF TEFLON CARBON TEFLON
(ؑѯ2)
/ SSIC
12 12-1 19A
ဩᎉۢڿᖴ ဩᎉᖴOᕘ SD/SE
Impeller Screw Impeller Screw 脚࢝
O-ring Base
for SD/SL
19
SAS - 40 2 - T 6 N - 5 2
(1) (2) (3) (4) (5) (6) (7) (8)
(1) SAS-ϾϏᐡ 3:3HP 5:5HP (6) Oᕘ؆፵ (8) ྄
(2) π৸-ϲвԓ 7:7.5HP N - NBR 2-2P
25-1", 40 - 1-1/2" 10:10HP E - EPT 4-4P
50-2", 65 - 2-1/2" (4) ໆࡍ؆፵ V - VITON
75-3" !!!T-Teflon Bellows Ssic T - TEFLON
(3) ଼Ω 1/2:1/2HP C-Κૢໆࡍഞ౯,ᆈષ (7) ᓝ౦
1:1HP 2:2HP (5) ࣆᡞ؆፵ 5:50Hz
6 - SUS316 6:60Hz
35
30 30
25 25
20 20
15 15
g G
10 e f E
h 10
d F
c D H
5 C
a 5 A
b B
0 100 200 300 400 500 600 700 800 900 1000 0 100 200 300 400 500 600 700 800 900 1000
20
0
9-1
9-5
9-4
9-2
9-3
9-6
11
6
6-1
1
5D
1A
19A
4
10-1
10
10-1
9
21
Ⴎӈхဵᄈྲߓ
1 1A 3 4 5D 6 6-1
10 10-1 11 19A 22 23
22
2
WQ.591ҦӉԓήଜЦሩ
VP - 480 40 - E 10 U E - H D
(1) (2) (3) (4) (5) (6) (7) (8) (9)
(1) VP - ᐡጢဵ (5) ᘯᆪؑМߞ࡚ (9) D - DIN
(2) 480 - ԥଜЦ౩ 10 - 10" J - JIS
(3) 40~1-1/2" 20 - 20"
50~2" (6) U - UPVC
65~2-1/2" P - PP
(4)Τπᘯᆪ (7) E - EPDM
T - T V - VITON
E - ΚԆ (8) H - ᆔԓ!
L - L
VP-480 Type VP-480 Type
ņ
ŕ
ᇴġ݃
●!ᙠԓۼሩુޠѷ-ቩђࣆ֝Τπႇᘯ८ᑗȂ
ٻΚٳᚖ፵ϛܿߤኈ֝ΩІϛ्҇ޠ
ᚾȄ
●!֝Τπ८ᑗ຺τȂ຺ϛཽߣ༭ኈࢻ໕Ȃϛܿ
ആԚࣆޫޠᇠ౫ຬІޫᙾᚾȄ
●!ၽңӶᚖ፵ၷӼޠӵРȂ७մ֝Τπߣ༭Ȃ ō
ЎࣆఽޠዔІߴᎵᓝ౦Ȅ
●!Ѡٸ౫ൠݸޒՍᡑ֝ΤᘯᆔಣӬРԓȂቩ
ђᘯᆔ࡚ߞޠȄዀྦߞ࡚21#ȂѠٸሰؒђߞ
࣐31#Ȃቩђ֝Τπ८ᑗȄ
● Old style check valve has limited surface area which can be obstructed by particles. The new design will prevent
blockage and increase the surface area.
● Large filter surface area insures adequate flow which prevents vacuum or air in the pump.
● Reduce Inlet Blockage, Cleaning and Pump Maintenance .
● Can be fitted to integrate into the customer’s specifications and usage environment, filter piping length can be increase
from standard 10” to 20” which will increase the total filter surface area.
23
Example A
EXAMPLES 1. While applied to heat-exchanger, install a pressure gauge at the outlet to
ጓپ make sure no clog inside the pipeline.
2. Install a strainer at the inlet to stop articles or objects entering the pump.
It also cut down the bubbles.
A 3. Install valves at the inlet and outlet for easy maintenance.
4. The diameter of each hole in the strainer should be approximately
5~7mm and the total mesh area of the strainer should be
5~10 times the area of the inlet.
It's better to enlarge the inlet pipeline.For example,enlarged 2-1/2" inlet
pipeline could drop the resistance loss.
5. Set an overflow piping at the outlet pipeline and keep constantly opened to
allow little overflow.
1. ࿌ᔗңܼዦһඳᏣਣȂܼяπђ၇ᔇΩᒽȂпጃۢᆔၰϜԥءԥߣ༭Ȅ
2. ܼΤπђ၇ᘯᆪȂпߣЦѵໍޑΤࣆȂηཽЎޠݿя౫Ȅ
3. ܼяΤπޠᆔၰϜђ၇ሩߟȂп߰ᆱៗȄ
4. ᘯᆪᆪЍޣޠ৸ᔗ࣐ङ5~7mmȂйᘯᆪЍޠ८ᑗᔗ࣐Τπᆔ৸ϟ5~10ॼȄ
!!ΤπᆔၰഷԂђτᆔ৸ȂԄࣆΤπ࣐3#Ȃପ3.203#ΤπᆔȂႲ٪֝Τ໕ޠ
!!ϛ٘Ȅ
6/яЬπପԥӲࢻᆔȂҔளఃሩߟȂЎ໕ӲࢻȄ
Example B
1. In order to monitor the flow and to detect possible clog of the filter, please
set a pressure gauge at the outlet.
2. To eliminate damage caused by dry-running, please install a pressure
safety shutoff.
B 3. Please clean up particles in the pump after operation.
4. Strainer is easy to be clogged. Clean it as usual.
5. The diameter of each hole in the strainer should be approximately
5~7mm and the total mesh area of the strainer should be
5~10 times the area of the inlet.
It's better to enlarge the inlet pipeline.For example,enlarged 2-1/2" inlet
pipeline could drop the resistance loss.
6. Install valves at the inlet and outlet for easy maintenance.
7. Set an overflow piping at the outlet pipeline and keep constantly opened to
allow little overflow.
1.࣐ΠᆀຝషᡞࢻІขႇᘯᐡϜѠߣޠ༭Ȃܼ፝яπђ၇ᔇΩᒽȄ
2.፝ђ၇ᔇΩߴៗᘟႬᏣпᗘռӱޫᙾᚾȄ
4/ᐈձȂ፝ఽଷࣆϜޠѵޑٿȄ
5/ݨཏΤπᘯᆪৡܿߣڨ༭ȂᔗਣளఽࣀȄ
6/ᘯᆪᆪЍޣޠ৸ᔗ࣐ङ5~7mmȂйᘯᆪЍޠ८ᑗᔗ࣐Τπϟ5~10ॼȄΤπ
!!ᆔၰഷԂђτᆔ৸ȂԄࣆΤπ࣐3#Ȃପ3.203#ΤπᆔȂႲ٪֝Τ໕ޠϛ٘Ȅ
6/яЬπପԥӲࢻᆔȂҔளఃሩߟȂЎ໕ӲࢻȄ
6.ܼяΤπޠᆔၰϜђ၇ሩߟȂп߰ᆱៗȄ
8/яЬπପԥӲࢻᆔȂҔளఃሩߟȂЎ໕ӲࢻȄ
Example C
1. While applied to pump chemicals from the storage tank,
please have a valve set at the inlet for the safety and convenience
during maintenance.
2. Please monitor the level of the liquid in the tank to avoid dry-running.
3. Without check lid model is recommended.
C 4. Please install a check valve at the outlet while the height of piping
exceeds 8M. It's better to enlarge the inlet pipeline.For example,enlarged
2-1/2" inlet pipeline could drop the resistance loss.
5. Please fasten in-outlet piping perfectly.
6. The motor shield must be applied while the pump is installed
outdoors or in harsh conditions.
7. Set an overflow piping at the outlet pipeline and keep constantly opened to
allow little overflow.
1.࿌ᔗңܼܫଛᓾԇϜϟϾᏱЬਣȂܼ፝Τπђ၇ሩߟȂпᆱԋӓІᆱៗ
!!αϟ߰ւȄ
2.፝ᆀຝϲషᡞା࡚ȂпᗘռޫᙾȄ
3.࡛ឋ௵ңณӪሩᐡȄ
4.࿌ପᆔା࡚τܼ8ԾਣȂܼ፝яπђ၇ଜЦሩ-ଜЦሩᔗାܼష
!!՞пαȄΤπᆔၰഷԂђτᆔ৸ȂԄࣆΤπ࣐3#Ȃପ3.203#ΤπᆔȂႲ٪!!
!!֝Τ໕ޠϛ٘Ȅ
5.፝яΤπᆔጤۢڿԂȄ
6.࿌ࣆ၇ܼЙѵܗඍӜᕘძϜȂ଼ႁ҇ሰђᇑៗဌȄ
8/яЬπପԥӲࢻᆔȂҔளఃሩߟȂЎ໕ӲࢻȄ
24
4
EXAMPLES Example D
ጓپ 1. While applied to waste gas treatment tower, the tank should be large
enough and the water-level in the tank should exceeds the inlet 80cm.
2. In order to avoid foreign particles clogging the inlet, please lower the inlet
and install a strainer. (Mesh diameter approximately 5~7mm and the
D total mesh area of the strainer should be 5~10 times the area of the inlet.)
It's better to enlarge the inlet pipeline.For example,enlarged 2-1/2" inlet
pipeline could drop the resistance loss.
3. It should be easy to remove the strainer from the inlet for cleaning.
4. To avoid running out of liquid, please make sure that the water supplying
system functions well.
5. To prevent the pump from dry running , please install a safety shutoff.
6. The motor shield must be applied while the pump is installed outdoors or
in harsh conditions.
7. Install valves at the inlet and outlet for easy maintenance.
8. Set an overflow piping at the outlet pipeline and keep constantly opened
to allow little overflow.
1. ࿌ᔗңܼኁ༲ਣȂЬᔗτȂйϜЬ՞ᔗାܼΤπᘯᆪ80 ϵϸȄ
2. ࣐Πᗘռѵߣޑ༭ΤπȂ፝७մΤπ्ٯ၇ᘯᆪ)ᆪЍЍ৸ङ5~7mmȂ
!!йᘯᆪЍޠ८ᑗᔗ࣐Τπᆔ৸ϟ5~10ॼ*ȄΤπᆔၰഷԂђτᆔ৸ȂԄࣆ
!!Τπ࣐3#Ȃପ3.203#ΤπᆔȂႲ٪֝Τ໕ޠϛ٘Ȅ
3. ΤπᘯᆪᔗܼܿڦίఽࣀȄ
4. ፝ጃᇰٽЬقಜѓًԂȂпᗘռณЬၽᙾ)ђ၇Ս၅Ьقಜ*Ȅ
5. ፝ђ၇ߴㄕᘟႬᏣȂп٪ЦࣆޫᙾȄ
6. ࿌ࣆ၇ܼЙѵܗඍӜᕘძϜȂ଼ႁ҇ሰђᇑៗဌȄ
7. ܼяΤπޠᆔၰϜђ၇ሩߟȂп߰ᆱៗȄ
9/яЬπପԥӲࢻᆔȂҔளఃሩߟȂЎ໕ӲࢻȄ
Example E
1. To stop articles or objects entering the pump, install a foot valve or strainer.
2. To prevent the inlet from sucking in bubble, please keep liquid level at least 30cm above the strainer.
3. Check valve must be installed if the height of piping exceeds 8M.
4.To avoid dry-running, please install a safety shutoff.
5. For the safety of repair, the valve must be installed at the outlet.
6. 3" in/outlet models cannot do self-priming well. Install a self-priming tank to get it.
7. In order to avoid foreign particles clogging the inlet, please lower the inlet and install a strainer. (Mesh diameter
approximately 5~7mm and the total mesh area of the strainer should be 5~10 times the area of the inlet.)
It's better to enlarge the inlet pipeline.For example,enlarged 2-1/2" inlet pipeline could drop the resistance loss.
8. If the head of the outlet too high or the long transfer distance and the pressrue losing orve 1KG we suggest
that install the outlet tee hose for backflow to tube.This can avoid the pressure of the backflow and the hot air
can be exhausted will diminish the damage.
9. Set an overflow piping at the outlet pipeline and keep constantly opened to allow little overflow.
1. ђ၇ۼሩܗᘯᆪȂп٪ЦѵໍޑΤࣆȄ
2. ፝ߴࡼష՞ഷЎାܼΤπᘯᆪ30cmпαȂп٪Ц֝ΤݿȄ
3. ࿌ପᆔା࡚τܼ8ԾਣȂ҇ሰђ၇ଜЦሩȄ
4. ፝ђ၇ߴៗᘟႬᏣȂп٪ЦࣆޫᙾȄ
5. ࣐ΠᆱঔԋӓȂяπ҇ሰђ၇ሩߟȄ
6. яΤπ࣐ 3"ϟᐡณՍ֝ΩȂ፝ђ၇Ս֝ఞпᕖூՍ֝ΩȄ
7. ࣐Πᗘռѵߣޑ༭ΤπȂ፝७մΤπ्ٯ၇ᘯᆪȞᆪЍЍ৸ङ5~7mmȂйᘯᆪЍޠ८ᑗᔗ࣐Τπᆔ৸ϟ5~10ॼȟȄ
!!ΤπᆔၰഷԂђτᆔ৸ȂԄࣆΤπ࣐3#Ȃପ3.203#ΤπᆔȂႲ٪֝Τ໕ޠϛ٘Ȅ
9. яπඵโାܗᒰଛᚕၷߞȂᔇົႇ2lhпαٻޠңൠ࡛ܛឋӶяπђ၇ήӲࢻᆔȂٿ٪ЦЇᔇІዦ௷ܺ
!!ЎᚾȄ
:/яЬπପԥӲࢻᆔȂҔளఃሩߟȂЎ໕ӲࢻȄ
ɏԄԋ၇ΡѯࣆȂϛӔңΤπᆔၰ
25
ॐᗋਣ፝ණٽίӗၦਠ;
2/షӈ;!ӫᆏ_____0ྤ࡚_____0ᐩ࡚_____0
!!Щ२_____0ᘈ࡚_____
3/ሰؒࢻ໕; _________L/min
4/ሰؒඵโ; ________M
5/଼ႁ;!Ⴌᔇ0ᓝ౦
αୣ ኅݎୣ
ԱងࣹЋঙҀؔྪᚋ۱ ኅࣹݎቩ࠳Ҁུ༯ᚋ
еୣᚋіၰ27ဵ!326511 ኅϵၰᯬ๚؇ࢳ
༮ᕘߴᐡఢ Ёᐡఢ
Tel:0512-53303388 Tel:020-82691835
53303398 82602341~3
Fax:0512-53303588 Fax:020-62351272
OCT. 2013
PDF-A 0033-07
Metering pumps
LK-32VC LK-32VCH LK-32VCU LK-21S6 LK-21TC
1
Metering pumps
Iwaki's systematic LK series metering pump consists of the worm gear type dual-
cam driving section, which is compact yet rigid and reliable, and wet-end materials
of which there are seven types for various applications.
With long and market-proven experience, Iwaki has employed state-of-the-art pump
technologies in the development of an ideal type of chemical feeding pump which
has advantages such as quality, performance, ease of operation and cost
efficiency.
The LK series is suitable for many chemical liquid feeding processes used in a wide
range of fields, including water treatment, chemicals, fabrics, paper mill, food
processing, and medicine.
2
Construction
• Power source :
• Motor output :
Detection terminal
Adjustment meter
Positioner
3
Metering pumps
Specifications
Capacity Max. Pressure Stroke speed Efective Max. Connection Motor Approx net
diaphragm stroke output weight
Model Flange Union Hose
dia. length
(JIS10K)
50Hz 60Hz PVC SUS 50Hz 60Hz PVC SUS
LK-11
21
22
31
32
45
47
55
57
LK-A55
A57
A65
B65
B75
C76
C86
C87
Materials
LK-11 to LK-57 LK-A55 to LK-C87
2
2 3
3
6
6
1 1
4 5
4
Pump identification
1 2 3 4 5 6 7 8 9 10
Item LK (IWAKI original motor type) LK-F / A / B / C (JEM or IEC motor type)
1 Simplex / Duplex
2 Series name
3 Drive section
4 Type No.
5 Material symbol
6 Joint
7 Motor output
8 Special motor
9 Servo unit
10 Special symbol
Hose type PVC Union type PVC Flange type PVC Flange type SUS PVC SUS
Model Model
LK-1 LK-A5
2 A6
3 B6
4 B7
5 C7
47VS C8
LK-F1 to F5
Hose type PVC Union type PVC Flange type PVC Flange type SUS
Model
LK-F1
2
3
4
5
47VS
5
Metering pumps
Optional accessories
Siphon preventing valve Model BVC-1P L- H BVC-1P - H
Applicable capacity
Setting pressure
Material
Connection Inlet
Outlet
A-1V
A-2V
PVC A-5V
N40A-10V(2)-F
N50A-20V(2)-F
A-05S6-( )
A-1S6-( )
SUS316 A-5S6-( )
A-10S6-( )
A-20S6-( )
A-36S6-( )
6
Metering pumps
Measures
Measures
List of the specifications for the selection of LK series inverter control system
Capacity Max. Pressure Control range Stroke speed Inverter Motor Description
Full stroke length frequency
Model
PVC, PVDF SUS
LK- 11
21
22
31
32
45
47
55
57
LK-F 11
21
22
31
32
45
47
55
57
LK-A 55
57
65
LK-B 65
75
LK-C 76
86
87
EN
Lev e l r e g u l a t ors
ITA
REGOLATORI DI LIVELLO
Signal
Our products for level
regulation
Levels
Level Regulators
Hydraulic Vave
Mac3 was born with the production of self-titled Float switch. In the following years the
Float switches
range was extended to cover all areas: tanks, drainage, sewage water, clear water, wells, etc.
Together with float switch, Mac3 offers a wide range of devices:
Float switches
Device: electromechanical level regulator based on microswitch.
Application: main application is control of pumps, filling or emptying, dry running protection.
Key
The most flexible float switch, particularly suitable for tank.
Sma ll
The most popular for drainage pumps
M ac3
The historical device, with double liquid proof chamber for maximum reliability, important
dimensions for bigger buoyancy.
M ac5 65
Tilting regulator for sewage water.
Rek a
Regulator suitable for various liquids, also for food application, easy to use.
Agm a
Compact device normally installed on drainage pumps. Clear water and water with debris
models are available.
HYDRAULIC VAVE
Device: instant closure valve for pipe.
Application: used in the storage tank to keep a reserve of water.
Q u ickS to p
QuickStop is a hydraulic level regulator, Its main feature and an intrinsic part of the patent (Pat.
FI/96/A/000083) is the rapidity of operation of the system which goes from open to closed ensuring
a high flow avoiding the dripping water. Version with adjustable levels of intervention is available.
MONITORING LEVELS
Device: electronic device for water level monitoring.
Application: used to make control systems and alarm generation based on the level of
liquids.
M acN i v e l
Based on the principle of level probes, can monitor the water level in a storage tank.
Sen ti nel
Connected to a level control allows acoustic signal based on the level of the liquid.
Float Switch
Level regulator with electrical equipment
The level regulator is a float switch that allows electrical equipment to start and stop automa-
tically (usually pumps, but also electric control valves, alarms, etc.) when a prefixed level has
been reached. inside the device there is a microswitch that, depending on the level of the liquid,
opens or closes the contact that powers the pump. The models with cable 3X1 or cable 4G1 can
be used for the filling or emptying function according to the cables that have been connected.
The models with 3G1 cable (with ground) or UL cable are set for one function only, and that is
for filling or emptying.
Key
High reliability, is the most universally used float switch in the world for the automation of pumps and storage tanks. Due to its size makes
it the most versatile for any application.
Small
It’s essential characteristic is to have small size, high reliability, and a high breaking capacity. He is the most used by pump- manufacturers
that mount directly to the factory on their products.
EN
LEVEL REGULATORS
Mac3
Thanks to its large size and its shape which has no edges, for which it is particularly suitable for sewage water, this device is made with a
double liquid proof chamber which assures the maximum reliability of the inside.
Mac5
Counterweight
On request, all MAC3 level regulators may come equipped with a piggy back plug, this allows pump operation by direct powering from the piggy
back plug connected to the float switch code and inserted in the power supply.
EN
LEVEL REGULATORS
Low current microswitch
This version provides the possibility of connecting the level regulator to personal computers or PLC, were are requested low current, The
particular type of microswitch used, with gold contacts, makes it possible:
- AC: up to 0,1(0,05)A max 250V ~
- DC: 1mA ÷100mA voltages 5V- ÷ 24V
Antistatic plastic
Special version (for environments that risk explosion) in which the superficial resistance of the regulator needs to be very low in order to
avoid the accumulation of electrostatic charges which may generate sparks. Please remember that even if this material does have antistatic
features, is not anti-explosion approval certificate.
Special cables
If temperature exceeds 60°C it’s not possible to use PVC or H07RN-F cables. For temperatures higher than 60°C we recommend H07BN4-F
cable that is suitable for temperatures up to 90°C, this cable is suitable also for use in chemically aggressive environments. In any event
we advise that tests be carried out in order to determine the exact degree of resistance under your specific conditions. 69
Approval certificates
On specific request it is possible to provide level regulators with special approval certificates, that are:
- UL/CSA for North America market
- ACS for drinking water
- SASO for Saudi Arabia market
During 2012 will be available ATEX approval certificate for MAC5 model.
Reka
REKA
General Technical Features
Chars. Output Relay 250V-10(4)A
Power Supply 12/24Vcc-Vca 117Vca 230Vca
Rigid. dielectric 1500V
Differential 9 ±1cm (related to water)
Approval CE EN60730
T. operating 0°÷+ 50°C
Storage Temperature -20°C ÷+ 80°C
70 Protection rating IP 68
Dimensions mm 93X250
Weight gr. 240
Parallelism
Measurement Check
Container Non-toxic polypropylene (PP)
Dyes Non-toxic
Delayed version of nautical 0 ±8 sec.
Fixture Standard cable 4G1
Slot Control
Circuit
Pump
Upper Level
Level Maximum Liquid
[“threshold”] Level
Sensor Blade
Sensor Blade
Lower
110-130mm
110-130mm
Level
[“threshold”]
30-40mm
Sensor Sensor
Base Base
The Reka2000 level regulator is a device that controls electronic equipment once it has reached a pre-established level. A capacity sensor
is integrated in the plastic structure and this makes it suitable for a wide range of liquids. It can be operated by battery or electricity and
thanks to an internal relay 10 (4) it is able to control pumps with up to 1 HP. It is easy to install near the pump itself thanks to two holes on
the structure. Models with 12/24Vcc, with delay on/off, are suitable for nautical applications.
EN
LEVEL REGULATORS
Agma 22
AGMA 22
General Technical Features
Features microswitch 10(8)A 250V ~20(8)A 250 V
Approval ENEC/CE (mod. B) CE (mod. A)
Service Continuous
Differential switching cm. 7-8
T. operating 0°÷+ 50°C
Storage Temperature -20°C ÷+ 80°C
Protection rating IP 68
76.6 Max pressure use 0,5 bar
Dimensions mm 37x100x235
Weight gr. 300
30.6 30.6 container Non-toxic polypropylene (PP)
Dyes Non-toxic
Type B H07RN-F 3G1 (mod. B)
Standard version H07RN-F 2X1 (mod. B)
Cavo standard
ENEC approved with PVC 3x1
H07RN-F 2x1 2 or 3 cables flame retardant PVC (form A)
or H07RN-F 3G1 cable 201
Note Model B also available UL
10 Version is also available with a manual selector
Type A
5 Standard version
19.8
34 with 2 PVC wires
or 3PVC wires.
Standard length d.47.1
5.3 25 cm. 71
Agma 22 level regulator is a patented device with magnetic coupling. The microswitch is placed in an upper room completely sealed, This
ensures a long life to the device. Agma22 is available the model “A” with flameproof cable or model “B” with H07RNF cable, in both cases
is possible to have ground or without ground version and a manual selector version.
Agma W
AGMA W
General Technical Features
Features microswitch 20(8)A 250 V~
Approval CE
Service Continuous
differential switching cm. min5-max15
T. operating 0°÷+ 50°C
Storage Temperature -20°C ÷+ 80°C
Protection rating IP 68
Max pressure use 0,5 bar
235 mm
Dimensions mm 60x100x235
Weight gr. 200
Container Non-toxic polypropylene (PP)
Dyes Non-toxic
60 mm
H07RN-F 3G1
Standard Cable PVC 3x1
H07RN-F 2x1
Notes also available UL
With the same switching mechanism from AGMA22, this device is useful even in the presence of debris in the water. If it is not possible
to use a floating tilting, can also be used in the presence of waste water in compliance with a periodical verification and cleaning of the
mechanisms of buoyancy.
Hydraulic Valve
Quickstop
QuickStop is a hydraulic level regulator of advanced design that eliminates the classic defects of such devices. Its main feature is the velocity
of operation of the system which goes from open to closed and viceversa in a fraction of a second, avoiding long noise periods and the dripping
due to choked filling. It’s available in a wide range of models, from 3/8” to 1 ½”, it’s also available an ADJ version with adjustable close levels,
the mechanism of regulation is very simple, it operates on the angle of the joint and the length and angle of the arm.
EN
LEVEL REGULATORS
Level Monitors
MacNivel
This product allows to view the water level present in a storage tank. The device, powered by a battery, applies a voltage across the wires
inserted in the terminal block. These wires are positioned into the tank at different heights. The liquid level is detected, because water, being 73
a conductor, allows current to pass on the immersed wires.
1 2 3 4 5
Max
Test
Min
5
4
3
2
Sentinel 2
This device, is normally connected with an electronic or electromechanical level regulator, such as a float switch; is equipped with a dry
contact relay output for activate an alarm signal at a distance. When the regulator level gives the consent of the Sentinel2 activates its
internal buzzer and activate any alarm connected to the relay. The relay operates only when the device is powered from the mains.
p4:Layout 6 7/8/09 1:58 PM Page 1
®
Magnehelic Differential Pressure Gages
Series
2000
ø4-31/64 CONNECTION
[113.89]
1/2
[12.70]
1/8 FEMALE NPT
11/16 LOW PRESSURE 15/32 ø4-3/4
[17.46] CONNECTION [11.91] [120.65]
1-11/16 1/2
[42.86] [12.70]
Patent Nos. 4,030,365 Dimensions, Standard Series 2000 Magnehelic® Pressure Gages.
5,012,678 (Slightly different on medium and high pressure models)
Select the Dwyer® Magnehelic® gage for high accuracy — guaranteed within 2% SPECIFICATIONS
of full scale — and for the wide choice of 81 models available to suit your needs precise- Service: Air and non-combustible, compatible gases. (Natural Gas option
ly. Using Dwyer's simple, frictionless Magnehelic® gage movement, it quickly indicates available.)
Wetted Materials: Consult factory.
low air or non-corrosive gas pressures — either positive, negative (vacuum) or differ- Housing: Die cast aluminum case and bezel, with acrylic cover. Exterior finish
ential. The design resists shock, vibration and over-pressures. No manometer fluid to is coated gray to withstand 168 hour salt spray corrosion test.
evaporate, freeze or cause toxic or leveling problems. It's inexpensive, too. Accuracy: ±2% of full scale (±3% on - 0, -100 Pa, -125 Pa, 10MM and ±4%
The Magnehelic® gage is the industry standard to measure fan and blower pres- on - 00, -60 Pa, -6MM ranges), throughout range at 70°F (21.1°C).
sures, filter resistance, air velocity, furnace draft, pressure drop across orifice Pressure Limits: -20˝ Hg. to 15 psig.† (-0.677 bar to 1.034 bar); MP option:
plates, liquid levels with bubbler systems and pressures in fluid amplifier or fluidic 35 psig (2.41 bar), HP option: 80 psig (5.52 bar).
systems. It also checks gas-air ratio controls and automatic valves, and monitors Overpressure: Relief plug opens at approximately 25 psig (1.72 bar),
blood and respiratory pressures in medical care equipment. standard gages only.
Temperature Limits: 20 to 140°F.* (-6.67 to 60°C).
Size: 4˝ (101.6 mm) Diameter dial face.
Note: May be used with Hydrogen. When ordering a Buna-N diaphragm pres- Mounting Orientation: Diaphragm in vertical position. Consult factory for
sures must be less than 35 psi. other position orientations.
Process Connections: 1/8˝ female NPT duplicate high and low pressure taps
- one pair side and one pair back.
Mounting Weight: 1 lb 2 oz (510 g), MP & HP 2 lb 2 oz (963 g).
A single case size is used for most Standard Accessories: Two 1/8˝ NPT plugs for duplicate pressure taps, two
models of Magnehelic® gages. 1/8˝ pipe thread to rubber tubing adapter and three flush mounting adapters
They can be flush or surface with screws. (Mounting and snap ring retainer substituted for 3 adapters in MP
mounted with standard hardware & HP gage accessories.)
supplied. With the optional A-610 *Low temperature models available as special option.
†For applications with high cycle rate within gage total pressure rating, next higher rating is rec-
Pipe Mounting Kit they may be con- Flush...Surface... or Pipe Mounted ommended. See Medium and High pressure options at lower left.
veniently installed on horizontal or
vertical 1-1/4˝ - 2˝ pipe. Although calibrated for vertical position, many ranges OPTIONS AND ACCESSORIES
above 1˝ may be used at any angle by simply re-zeroing. However, for maxi- Transparent Overlays
mum accuracy, they must be calibrated in the same position in which they are Furnished in red and green to highlight and emphasize
critical pressures.
used. These characteristics make Magnehelic® gages ideal for both stationary
and portable applications. A 4-9/16˝ hole is required for flush panel mounting. Adjustable Signal Flag
Complete mounting and connection fittings plus instructions are furnished with Integral with plastic gage cover. Available for most mod-
each instrument. els except those with medium or high pressure con-
struction. Can be ordered with gage or separate.
Vent Valves
In applications where pressure is continuous and the LED Setpoint Indicator
Magnehelic® gage is connected by metal or plastic tub- Bright red LED on right of scale shows when setpoint is
ing which cannot be easily removed, we suggest using reached. Field adjustable from gage face, unit operates
Dwyer A-310A vent valves to connect gage. Pressure on 12-24 VDC. Requires MP or HP style cover and
can then be removed to check or re-zero the gage. bezel.
4
p5:Layout 7 7/8/09 1:59 PM Page 1
Pressure
Bezel provides flange for flush mounting in panel. O-ring seal for cover assures pressure integrity of
case.
Clear plastic face is highly resistant to breakage.
Provides undistorted viewing of pointer and scale. Blowout plug of silicone rubber protects against
overpressure on 15 psig rated models. Opens at
approximately 25 psig.
Precision litho-printed scale is accurate and easy to
read. Die cast aluminum case is precision made and
iridite-dipped to withstand 168 hour salt spray
Red tipped pointer of heat treated aluminum tubing is corrosion test. Exterior finished in baked dark gray
easy to see. It is rigidly mounted on the helix shaft. hammerloid. One case size is used for all standard
pressure options, and for both surface and flush
Pointer stops of molded rubber prevent pointer over-travel mounting.
without damage.
Silicone rubber diaphragm with integrally molded
“Wishbone” assembly provides mounting for helix, helix O-ring is supported by front and rear plates. It is
bearings and pointer shaft. locked and sealed in position with a sealing plate and
retaining ring. Diaphragm motion is restricted to
Jeweled bearings are shock-resistant mounted; provide vir- prevent damage due to overpressures.
tually friction-free motion for helix. Motion damped with
high viscosity silicone fluid.
Calibrated range spring is flat spring steel. Small
Zero adjustment screw is conveniently located in the amplitude of motion assures consistency and long
plastic cover, and is accessible without removing cover. life. It reacts to pressure on diaphragm. Live length
O-ring seal provides pressure tightness. adjustable for calibration.
CALL TO ORDER: U.S. Phone 219 879-8000 • U.K. Phone (+44) (0)1494-461707 • Asia Pacific Phone 61 2 4272-2055 5
qrsttuvuqrswt
394GC875P57T55
34G5;<85<50573H5
3947B9HH1B6
05725Q9CBDB5405̀9714759
17B585
`B9S1
x53F>53218fy
zFH
5 1B765C61B659I583H5SB3759456737C6
x5F;3
zFC7
5 9
3758571
@1B37CB1589
@14637594
x5
5̀9547533H5SB37594
z{@
5 57957095@9547583H5SB375945
x5|38fH5027
z|3
5 8fH57Y5>3<5G56@H3T5
;215b_44561B51659I58947B9HH1B659}1B5673715
9I572153B756@185~83759465I9B5T9CB5@B981665
8947B9H15;21T58345S15894~0CB1G5I9B5Z9 !"#$#"%&#'() *+,-- *+,.-
ZQQY5@B9@9B75943HY5̀_59B5̀_<58947B9H15;234f65 4145795661657898
:55 4145795661657898
:55
7959CB51d8HC65P15718249H90TY5721T58345S15 23 4579566657898
:5 4579566657898
:5
8C679
5c1G5795S1675~75T9CB53@@H583759415 4144579561665
898
:55 4144579561665
898
:55
414579566165
898
414579566165
898
Y5467BC
147[5\\5d5\\5d545
e15027 15f05?a1V5HS1A
23825b_44534G5b_45
9G1H55656C@@H51G505725
9C475405SB38f176534G55467BC8759461
Kl'')!Mm'nhM"'($#jnh%&#'(
*+,--oo.p.M GC3H5617@9547Y59499II534G5̀_<58947B9H6Y5343H9059C7@C7Y5V]
ghi!h#(jM *+,--oo.poMM GC3H5617@9547Y59499II534G5̀_<58947B9H6Y5343H9059C7@C7Y5
a4]
+($'hk%&#'( *+,.-oo.p.M GC3H5617@9547Y59499II534G5̀_<58947B9H6Y5343H9059C7@C7Y5V]
*+,.-oo.poMM GC3H5617@9547Y59499II534G5̀_<58947B9H6Y5343H9059C7@C7Y5
a4]
*+,.-ooop.M GC3H5617@9547Y59499II534G5̀_<58947B9H6Y5/8\^V59C7@C7Y5V]
*+,.-ooopoMM GC3H5617@9547Y59499II534G5̀_<58947B9H6Y5/8\^V59C7@C7Y5
a4]
u
uuuuuuuuu
1
0001234435467189
Catalogue 8659/GB
NEW
Also available with
ATEX G & D
Explosion-proof
electrical parts
8659/GB 7321B, 7322B Series – Diaphragm pilot operated valves
Technical specifications
General description The 7321B, 7322B water valves series are diaphragm pilot operated valves
and require a minimum differential pressure to operate
Applications They are used for general applications with high flow rates and media such
as water, hot water and steam, provided they are compatible with the
component materials.
Typical applications can be found in: Washing machine, car wash
installations, cooling of machine tools, Hydrocleaners, autoclaves, irrigation
systems etc
Temperatures Admissible ambient temperatures: -10 to +50 qC
Working fluid temperature: see table
Material specifications Valve body: CW617N UNI EN 12165:98 Forged Brass
Enclosing tube: AISI 304 stainless steel
RoHs compliant Plunger: AISI 430F St. Steel
Spring: AISI 302 St. Steel
Seals: NBR (Buna N) – EPDM
Shading ring: Copper
Installation The valves can be mounted in any position. It is however recommended to
install them with the coil in vertical position above the body.
Electrical parts Detailed description: see page 8
* The fixing nut and nameplate are integrated in the valve itself, so that the standard housing type “2995” MUST
NOT be specified in valve numbering: see next page
Numbering system
A complete valve is usually composed of 3 elements: the valve itself, the housing and the coil which need to be
ordered separately. For “integrated coil/housings”, the “housing reference” corresponds to the fixing nut and
nameplate.
x Valve Numbering
The classic “7000” numbering system will NO LONGER be in use for the Water Valve family and will be
replaced by the following (please see the complete cross reference at page 2).
REMARK: each reference, that is valve, housing (when requested) and coil, has to be ordered separately. To
order the assembled valve please contact the Gessate factory for agreement on Minimum Order quantity and do
not indicate the housing reference
Numbering examples
7321BAN00 valve body, including the housing “2995”; box quantity: 10pcs
483510S6 coil, box quantity: 10pcs
7321BCN 481865C2 complete valve body, box quantity: 10pcs; (*)
7321BDN 4270 4810003D complete valve body, box quantity: 10pcs; (*)
Note (*): Minimum Order Quantity (MOQ) and a Minimum Shipment Quantity (MSQ) requested for complete
valve. Please contact the Gessate factory.
Specification
Dimension
Max.
Note
ref.
Maximum admissible
Admissible differential fluid Seals Cross Refernce
Port Size Orifice Kv Qmax pressure (bar) temperature material Order N° (Old numberings)
G mm m3/h m3/h min DC AC °C NEW N°
2-way valves, pilot operated, normally closed, for water
3/8 " 13 3.00 3.00 0.10 20 20 90 NBR (*) 7321BIN00 PM133IN 7321BBG3TN00 1 -
1/2" 13 3.00 3.00 0.10 20 20 90 NBR (*) 7321BAN00 PM133AN 7321BBG4TN00 1 -
3/4" 20 8.40 8.40 0.10 20 20 90 NBR (*) 7321BCN00 PM133CN 7321BBG53N00 1 -
1" 25 9.6 9.6 0.10 20 20 90 NBR (*) 7321BDN00 PM133DN 7321BBG64N00 1 -
1 1/4 " 35 25.20 25.20 0.10 10 10 90 NBR 7321BEN00 PM133.2EN 7321BBG78N00 1 -
1 1/2" 40 30.00 30.00 0.10 10 10 90 NBR 7321BFN00 PM133.2FN 7321BBG88N00 1 -
2" 50 37.20 37.20 0.10 10 10 90 NBR 7321BGN00 PM133GN 7321BBG99N00 1 -
2-way valves, pilot operated, normally closed for water, with manual override
3/8" 13 3.00 3.00 0.10 20 20 90 NBR (*) 7321BIN01 PM133IN CM 7321BBG3TN00 1 -
1/2" 13 3.00 3.00 0.10 20 20 90 NBR (*) 7321BAN01 PM133AN CM 7321BBG4TN00 1 -
3/4" 20 8.40 8.40 0.10 10 10 90 NBR (*) 7321BCN01 PM133CN CM 7321BBG53NM0 1 2
1" 25 9.6 9.6 0.10 10 10 90 NBR (*) 7321BDN01 PM133DN CM 7321BBG64NM0 1 2
1 1/4 " 35 25.20 25.20 0.10 5 5 90 NBR 7321BEN01 PM133.2EN CM 7321BBG78NM0 1 2
1 1/2" 40 30.00 30.00 0.10 5 5 90 NBR 7321BFN01 PM133.2FN CM 7321BBG88NM0 1 2
2" 50 37.20 37.20 0.10 5 5 90 NBR 7321BGN01 PM133GN CM 7321BBG99NM0 1 2
2/1/2" 65 63.00 63.00 0.20 10 10 90 NBR 7321BLN02 PM133LN CMV 7321BBGCBNM1 1 1
3" 75 83.00 83.00 0.20 10 10 90 NBR 7321BMN02 PM133MN CMV 7321BBGDCNM1 1 1
2-way valves, pilot operated, normally closed for hot water and steam
3/8 " 13 3.00 3.00 0.10 10 10 140 EPDM 7321BIH00 PM133IH 7321BBG3TE00 1 3
1/2" 13 3.00 3.00 0.10 10 10 140 EPDM 7321BAH00 PM133AH 7321BBG4TE00 1 3
3/4" 20 8.40 8.40 0.10 10 10 140 EPDM 7321BCH00 PM133CH 7321BBG53E00 1 3
1" 25 9.6 9.6 0.10 10 10 140 EPDM 7321BDH00 PM133DH 7321BBG64E00 1 3
1 1/4 " 35 25.20 25.20 0.10 10 10 140 EPDM 7321BEH00 PM133.2EH 7321BBG78E00 1 3
1 1/2" 40 30.00 30.00 0.10 10 10 140 EPDM 7321BFH00 PM133.2FH 7321BBG88E00 1 3
2" 50 37.20 37.20 0.10 10 10 140 EPDM 7321BGH00 PM133GH 7321BBG99E00 1 3
2-way valves, pilot operated, normally open, for water
3/8 " 13 3.00 3.00 0.10 20 20 90 NBR (*) 7322BIN00 PM143IN 7322BBG3TN00 2 -
1/2" 13 3.00 3.00 0.10 20 20 90 NBR (*) 7322BAN00 PM143AN 7322BBG4TN00 2 -
3/4" 20 8.40 8.40 0.10 20 20 90 NBR (*) 7322BCN00 PM143CN 7322BBG53N00 2 -
1" 25 9.6 9.6 0.10 20 20 90 NBR (*) 7322BDN00 PM143DN 7322BBG64N00 2 -
1 1/4 " 35 25.20 25.20 0.10 10 10 90 NBR 7322BEN00 PM143.2EN 7322BBG78N00 2 -
1 1/2" 40 30.00 30.00 0.10 10 10 90 NBR 7322BFN00 PM143.2FN 7322BBG88N00 2 -
2" 50 37.20 37.20 0.10 10 10 90 NBR 7322BGN00 PM143GN 7322BBG99N00 2 -
2/1/2" 65 63.00 63.00 0.20 10 10 90 NBR 7322BLN06 PM143LN CMV 7322BBGCBNM1 2 -
3" 75 83.00 83.00 0.20 10 10 90 NBR 7322BMN06 PM143MN CMV 7322BBGDCNM1 2 -
Note: (*) available also with FKM diaphragm. Order N° example: 7321BAV
Manual override plus closure ..00 changes to ..02 in the reference No.
speed control The closure time of certain types can be changed by means of the
adjusting screw (fig. 3 and 4). The latter, by acting as a throttle on the inlet
equalisation (pilot) hole of the valve, slows down the closure speed of the
valve, thus reducing the water hammer effect. The regulation range is as
follows: Fig. 3 - Screw fully open: max. closure speed. Fig. 4 - Screw
fully closed: valve always open.
Fig. 3
Fig. 4
Section drawing
| |
{ {
{
2 1/2” 3”
Dimension drawings
Size
G A B C D
3/8 69 99.5 40 44
1/2 72 101.5 40 44
3/4 100 107 65 44
1 104 112.5 65 44
1 1/4 145 134 102 44
1 1/2 145 134 102 44
2 173 148 118 44
2 1/2 245 195 184 44
3 250 195 184 44
Size
G A B C D
3/8 69 110 40 44
1/2 72 112 40 44
3/4 100 117.5 65 44
1 104 123 65 44
1 1/4 145 144.5 102 44
1 1/2 145 144.5 102 44
2 173 158.5 118 44
2 1/2 245 205.5 184 44
3 250 205.5 184 44
Fig. 8
Voltage
code
Q3
Q1
3D
R5
C1
C2
C4
C5
C7
A1
A2
A4
A5
E5
A7
A9
B2
K8
B7
B8
S2
P0
S4
P2
S5
P9
S6
S2
0A
4K
0P
5P
F4
J3
6J
100/50, 115/60
Coils /
110/50-115/50
220/50-230/50
110/60-115/60
200/60-230/60
220/60-240/60
220/50-230/60
220/50-240/60
380/50-440/60
220-240/50-
24/50-24/60
48/50-48/60
110-115/50,
Electrical
110/50-60
220/50-60
230/50-60
240/50-60
parts
110/DC
220/DC
110/50
115/50
220/50
230/50
380/50
115/60
220/60
230/60
240/60
12/DC
24/DC
48/DC
12/50
24/50
48/50
24/60
Ref. No. Code
Coils
481000 EZ0
481865 DZ0
482740 DZ1
483510 DZ0
485100 EZ0
486265 EZ9
492425 DZ0
492453 DZ0
Electrical parts
483371 HZ0
492070 VZ0
492190 VZ0
492670 HZ0
493640 HZ0
495870 -
495875 -
495880 -
495905 HZ9
496110 -
496155 -
FLOW METER
HV, HK, HT
FEATURES
Low cost
Large variety of flow ranges
TYPICAL APPLICATIONS
Process industry
• For liquid or gas
Chemical industry
• Good corrosion resistance Water treatment plants
• Threaded or socket type Flow measurement in PVC piping
connections General liquid and gas
measurement
• Scales up to
22 m³/h H₂O OPTIONS
14 Nm³/min air Scales for alternative liquids and
gases
Special scale markings
ISO 9001:2008 ISO 14001:2004
Viton® or EPDM seals
Low and high flow alarm
HV TECHNICAL DATA
Model HV
Connection size BSP/NPT 1/2” or 20 mm socket
Weight 120 g
Max. pressure 10 bar at 20°C (*10 bar at 80°C)
Max. temperature 50°C at 2 bar (*120°C at 2 bar)
Flow tube Grilamid (PA-12) (*PES)
Connectors PVC (*AISI 316, PVDF)
Float AISI 329 or AISI 329/PTFE (depending on range)
Seals Nitrile (*Viton®, EPDM)
Accuracy ±5% F.S. (H₂O +20°C) *Special construction on request
H V– – Ø 43
Connections
Without PVC connectors blank
Socket type connections, Ø20mm H
NPT 1/2” connections N
BSP 1/2” connections R
Flow Range
H2O m³/h Air Nm³/min
0.02 – 0.11 0.015 – 0.07 6H
0.04 – 0.2 0.03 – 0.13 3H
0.075 – 0.3 0.04 – 0.18 3K
180
210
0.15 – 0.5 0.06 – 0.28 3L
0.15 – 0.6 0.075 – 0.3 3M
0.2 – 1.0 0.1 – 0.5 4D
0.2 – 1.3 0.1 – 0.65 4E
0.3 – 1.8 0.2 – 0.9 4F
Scale
H2O (m3/h) at +20°C C
Air (Nm3/min) at +20°C/101.3 kPa S
Special Feature
Grilamid flow tube, nitrile seals blank
PES flow tube, nitrile seals V
PES flow tube, Viton® seals W Ø 20 NPT (BSP) 1/2
Grilamid flow tube, Viton® seals X
Standard feature: leave blank HHV HNV
Special feature: choose Character
Kytola Instruments Oy
Olli Kytölän tie 1
FI-40950 Muurame, Finland
Tel. +358 20 779 0690
Fax +358 14 631 419
www.kytola.com E-mail info@kytola.com
HK TECHNICAL DATA
Model HK
Connection size BSP/NPT 3/4” or 25 mm socket
Weight 280 g
Max. pressure 10 bar at 20°C (*10 bar at 80°C)
Max. temperature 50°C at 2 bar (*120°C at 2 bar)
Flow tube Grilamid (PA-12) (*PES)
Connectors PVC (*AISI 316, PVDF)
Float AISI 329 or AISI 329/PTFE (depending on range)
Seals Nitrile (*Viton®, EPDM)
Accuracy ±5% F.S. (H₂O +20°C) *Special construction on request
H K– – Ø 53
Connections
Without PVC connectors blank
Socket type connections, Ø25 mm H
NPT 3/4” connections N
BSP 3/4” connections R
Flow Range
H2O m³/h Air Nm³/min
0.3 – 1.2 0.14 – 0.6 4F
0.5 – 2 0.25 – 1 4E
0.6 – 2.6 0.25 – 1.2 4A
0.8 – 3.4 0.4 – 1.7 4B
255.5
281.5
0.8 – 3.6 0.4 – 1.8 4C
1 – 4.75 0.4 – 2.2 4D
Scale
H2O (m3/h) at +20°C C
Air (Nm3/min) at +20°C/101.3 kPa S
Special Feature
Grilamid flow tube, nitrile seals blank
PES flow tube, nitrile seals V
PES flow tube, Viton® seals W
Grilamid flow tube, Viton® seals X
Standard feature: leave blank
Special feature: choose Character Ø 25
BSP 3/4
HHK HRK
Kytola Instruments Oy
Olli Kytölän tie 1
FI-40950 Muurame, Finland
Tel. +358 20 779 0690
Fax +358 14 631 419
www.kytola.com E-mail info@kytola.com
HT TECHNICAL DATA
Model HT
Connection size BSP/NPT 1 ¼” or 50 mm socket
Weight 980 g
Max. pressure 10 bar at 20°C (*10 bar at 80°C)
Max. temperature 50°C at 2 bar (*120°C at 2 bar)
Flow tube Grilamid (PA-12) (*PES)
Connectors PVC (*AISI 316, PVDF)
Float AISI 329 or AISI 329/PTFE (depending on range)
Seals Nitrile (*Viton®, EPDM)
Accuracy ±5% F.S. (H₂O +20°C) *Special construction on request
Copyright© Kytola Instruments Oy 2016. Dimensions and measurements are given within normal tolerances. Manufacturer reserves the right to changes without prior notification. File H_es10_en Published 4/2016.
H T– – Ø 83.7 55
Connections
Without PVC connectors blank
Socket type connections, Ø50mm H
NPT 1¼” connections N
BSP 1¼” connections R
Flow Range
H2O m³/h Air Nm³/min
0.5 – 3 0.35 – 2 4E
0.6 – 6.4 0.4 – 3 4A
0.5 – 9.5 0.5 – 4.25 4F
396.5
1.5 – 12 1–6 4B 382
2 – 18 1 – 8.5 4C
4 – 22 2 – 14 4D
Scale
H2O (m3/h) at +20°C C
Air (Nm3/min) at +20°C/101.3 kPa S
Special Feature
Grilamid flow tube, nitrile seals blank
PES flow tube, nitrile seals V
PES flow tube, Viton® seals W
Grilamid flow tube, Viton® seals X Ø 50 BSP 1 1/4
Standard feature: leave blank
Special feature: choose Character
HHT HRT
Kytola Instruments Oy
Olli Kytölän tie 1
FI-40950 Muurame, Finland
Tel. +358 20 779 0690
Fax +358 14 631 419
www.kytola.com E-mail info@kytola.com