Laboratory: B-118 Phase-li, Noida, U.P.

201305
AES LABORATORIES (P) LTD. Ph.: 0120-4646700,4646711, 4646731, 011-45066390
E-mail: support@aeslabs.com
analyz:ng today Jr an assured tomorrow
GSTIN : 09AkACP0857B1ZQ
TC-6308 MSME No. : UP28E0011437
CIN No. U74699DL1991PTC045168

Issued To: Report No.: 20-260523.07


M/s. Jakson Ventures Pvt. Ltd Report Date: 05-06-2023
A-43, Phase-Il, Extension Noida Analysis Date: 26-05-2023
Gautam Budh Nagar, Uttar Pradesh -201305
Page No.: lot 1

DISSOLVED GAS ANALYSIS

SAMPLE & EQUIPMENT IDENTIFICATION


21/05/2023 at
Condition of Oil: Oil in Service Sample Drawn On: Capacity: 2.5 MVA
11:35 PM
Equipment ID: NA Sample Drawn By: Customer Voltage (Ky): 33
Transformer No: NA Sampling Point: Bottom Serial No: CPGO81/80
Sample Description: Transformer OiL, Grid Name: NA Mfd. Year: 10-2016
Plant Location: LCR-05, Sample Quantity: 500 ml. Make: Kirloskar
packed in aluminium bottle

ANALYSIS RESULTS

Nominal Values, max


Gases Method Result Units Detection Limit
(IEEE C57.104.2019)
Hydrocarbons & Hydrogen
Methane (CH4) IS : 9434: 2019 305 * 1 50
Ethane (C2H6) IS :9434: 2019 36 .il/L 1 40
Ethylene (C2H4) IS : 9434 : 2019 1 .11/L 100
Acetylene (C2H2) IS : 9434 : 2019 5 .tI/L 1 7
Hydrogen (H2) IS :9434: 2019 3949 * .dlL 5 90
Carbon Oxides
Carbon Monoxide (CO) IS :9434: 2019 121 sIlL 25 600
Carbon Dioxide (CO2) 5:9434 : 2019 275 lulL 25 7000
Non-Fault Gases
Oxygen (02) IS : 9434 : 2019 17539 .il/L 50
Nitrogen (N2) IS : 9434 : 2019 57245 .d/L 50

Total Dissolved Combustible Gases (TDCG, lsl/L): 4417

Note: A value of 0 in the results column indicates that the particular gas is below detection limits.
Remark(s), based on IEEE C57.104-2019
Gas levels marked with a are higher than normal
Fault Analysis as per IEEE C57. 104-2019! IEC 60599:2015 (Duval Trian ale method)
Fault Code: PD
Corona partial discharges. Possible causes: Discharges in gas-filled cavities resulting from
Diagnosis: incomplete impregnation, highhumidity in paper, oil super saturation or cavitation, and
leading to X-wax formation

Carbon Dioxide to Carbon Monoxide Ratio Analysis

CO2/CO ratio Not applicable since one or both of these gases is in normal range.

Diagnosis: Not Applicable

Disclaimer: The above mentioned remarks and interpretations are computer generated and suggestive in nature. Please correlate with other factors
before making a decision.

ULR No. TC630823500022452 F

AUTHORISED SIGNATORY

VIsIt us at http:I! www.aeslabs.com AESIQCD/F-7.8-I


Terms & Conditions
• The results indicated only refer to the tested samples and listed parameters and do not endorse any product.
• Total liability of the laboratory is limited to the invoiced amount.
• This certificate shall not be reproduced wholly or in part without prior written consent of the laboratory.
• Samples received shall be destroyed after four weeks from the date of issue of the certificate unless specified otherwise.
• This certificate shall not be used in any advertising media or as evidence in the court of law without prior written consent of the laboratory.

You might also like