DISSOLVED GAS ANALYSIS

SAMPLE & EQUIPMENT IDENTIFICATION


20/05/2023
Condition of Oil: Oil in Service Sample Drawn On: Capacity: 2.5 MVA

Equipment ID: NA Sample Drawn By: Customer Voltage (Ky): 33


Transformer No: NA Sampling Point: Bottom Serial No: CPGOB1/126
Sample Description: Transformer OiL, Grid Name: NA Mfd. Year: 02-2017
Plant Location: LCR-01, Sample Quantity: 500 ml. Make: Kirloskar
packed in aluminium bottle

ANALYSIS RESULTS

Nominal Values, max


Gases Method Result Units Detection Limit
(IEEE C57.104-2019)
Hydrocarbons & Hydrogen
Methane 1CH4) 15:9434: 2019 40 sl/L 1 50
Ethane (C2H 6) IS : 9434: 2019 7 tilL 1 40
Ethylene (C2H4) IS : 9434: 2019 3 tilL 1 100
Acetylene (C2H2) IS :9434 : 2019 0 tilL 1 7
Hydrogen (H2) IS:9434 : 2019 796 * pilL 5 90
Carbon Oxides
Carbon Monoxide (CO) IS : 9434 : 2019 . 61 pJ/L 25 600
Carbon Dioxide )CO2) IS: 9434: 2019 431 pi/L 25 7000
Non-Fault Gases
Oxygen (021 IS : 9434 : 2019 19185 pilL 50
Nitrogen (N2) IS :9434 : 2019 55655 pilL 50

Total Dissolved Combustible Gases (TDCG, pi/L): 907

Note: A value of 0 in the results column indicates that the particular gas is below detection limits:

Remark(s), based on IEEE C57.104-2019

Gas levels marked with a are higher than normal

Fault Analysis as per IEEE C57.104-2019 / IEC 60599:2015 (Duval Trianqie method)
Fault Code: Ti
Thermal fault, t < 300CC. Possible causes: Overloading of the transformer in emergency
Diagnosis: situations. Blocked item restricting oil flow in windings. Stray flux in clamping beams of
yokes.

Carbon Dioxide to Carbon Monoxide Ratio Analysis

COZ/CO ratio Not applicable since one or both of these gases is in normal range.

Diagnosis: Not Applicable

Disclaimer: The above mentioned remarks and interpretations are computer generated and suggestive in nature. Please correlate with other factors
before making a decision.

ULR No. 10630823500022742 F


AUTHORISED SIGNATORY

VIsIt us at http:ll www.aeslabs.com AESIQCD/F-7.8-I


Terms & Conditions
• The results indicated only refer to the tested samples and listed parameters and do not endorse any product.
• Total liability of the laboratory is limited to the invoiced amount.
• This certificate shall not be reproduced wholly or in part without prior written consent of the laboratory
• Samples received shall be destroyed after four weeks from the date of issue of the certificate unless specified otherwise.
• This certificate shall not be used in any advertising media or as evidence in the
court of law without prior written consent of the laboratory.

You might also like