You are on page 1of 10

Technical Note No 46

Introduction to building envelope energy transfer

This Technical Note is one of four on the effect of building envelope performance on energy
use in buildings. The series comprises:

TN 46 Introduction to building envelope energy transfer


TN 47 Overall building envelope U-values
TN 48 Energy loss through windows
TN 49 U-values of curtain walls

Introduction
Internal Internal
This Technical Note introduces the reader heating cooling
to the basic principles of heat transfer that required required
are required to understand the contribution
Heat gain Good Bad
that building envelopes can make to the
construction of energy efficient buildings. Heat loss Bad Good

Information is given on heat transfer Table 1 Effect of heat transfer


mechanisms, material properties and
general calculation principles. Energy efficient facades have to:

A guide to relevant UK legislation and • Be insulated to keep the external


standards is also given. surface as nearly the same as the
external temperature
(Reduces convection and radiation
Energy transfer losses/gains from the outer surface)
• Be sealed to prevent gross air
Energy is gained or lost from a building by: leakage (reduces mass transfer
losses/gains)
• Radiation or convection from the • Shield internal surfaces (Reduces
outer surface of the building radiation losses/gains from/to
And internal surfaces)
• Allow in sufficient daylight (Reduces
• Air leakage (mass transfer) into or energy used for artificial lighting)
out of the building.

Energy transfer through a building envelope Units


may cause heat gain or heat loss, either of
which may lead to increased energy use in Energy
a building depending on the external Energy is the same as work and the unit of
climate. The requirement for heating or energy is the Joule (J). The unit of force is
cooling may be constant in tropical or polar the Newton (N) and 1 Joule is 1 Nm.
regions but will otherwise vary seasonally Energy may also be measured in kilowatt-
as it does in the UK. hours (kWh), which is the common charging
unit for energy. 1 kWh = 3.6 x 106 J.

© CWCT 2004 October 2004


This document has been printed from the CWCT ‘Cladding Forum’, access to which is restricted to subscribing Members of the
Centre for Window & Cladding Technology. Information about the availability of CWCT publications and membership is
available at our website – www.cwct.co.uk - or from the address at the end of this note.
Introduction to building envelope heat transfer TN 46

Power Q = rate of heat flow


The unit of power is the Watt (W). Power is λ = thermal conductivity
the rate of work (energy) and 1 Watt is 1 A = cross-sectional area
Joule per second. d = thickness
T2 and T1 are temperatures at each end.
Temperature
Temperature is measured in degrees
Centigrade (oC) or degrees Kelvin (K). Both λ
units have the same magnitude so that a Material (W/mK)
change of 10 oC is the same as a change of
Aluminium 160
10 K. However 0 oC is taken as the
temperature at which water freezes. 0 K is Carbon steel 50
absolute zero (-273 oC) the temperature at Stainless steel 17
which a body has no thermal energy.
Marble 3.0
o
0 C is the same temperature as 273 K and Sandstone 2.3
20 oC is the same temperature as 293 K. Slate 2.0
Concrete 1.13 – 1.93
Energy transfer mechanisms Glass (soda lime) 1.0
Hardwood 0.18
Conduction is the mechanism by which
heat energy travels through solids and Softwood 0.13
stationary fluids and gases. Materials such Brick (outer leaf) 0.77
as metals are good conductors. Materials
Lightweight blocks 0.57
such as mineral wool are poor conductors
(good insulators). PVC-u 0.17
Mineral wool 0.035
Good conductors have a high thermal
Polyurethane board 0.025
conductivity λ as shown in table 2. Note
that λ has units of W / m K and is a property Air (still) 0.025
of the material not affected by its size or
shape. Table 2. Thermal conductivity of materials

Methods for determining the thermal


conductivity of building materials are given Radiation heat transfer occurs because all
in BS EN 12664, BS EN 12667, or BS EN bodies at temperatures above 0K emit heat
12939. energy. Two surfaces at different
temperatures will emit energy at different
Heat conduction through a component is rates and energy transfer will occur.
dependent on its shape and size. It will be
a better conductor if it is thinner (in the The rate at which energy is emitted from a
direction of heat flow) and has a large body depends on its absolute temperature
cross-sectional area. (K), the surface area, and a property of the
surface called emissivity. Black surfaces
Heat flow is given by: are the best radiators while white and shiny
surfaces are poorer radiators. Black
T2 - T1 surfaces are also the best absorbers.
Q = λA
d
The rate at which energy is emitted from a
surface is given by:
where:

2/10
Introduction to building envelope heat transfer TN 46

Q = εσAT 4 hc
Situation (W/m2K)
where: Horizontal
Warm face up 4.3
Q = rate of heat loss Cool face down 4.3
ε = emissivity Horizontal
σ = 5.64 x 10-4 (W/m2K4) Cool face up 1.5
A = surface area (m2) Warm face down 1.5
T = surface temperature (K) Vertical 3.0

Table 4. Convection coefficients for free


Material ε convection
Black body 1.0
Painted/coated surface 0.8 - 0.9
Air velocity C
Glass 0.845 (m / s)
Brick/block/concrete 0.0 – 0.9 0 1.0
Metal coated glass 0.05 – 0.2 0.5 1.3
Polished metal surfaces 0.01 – 0.2 1.0 1.7
2.0 2.4
Table 3. Surface emissivity of different
materials 3.0 3.1

Table 5. Factors applied to convection


Convection heat transfer occurs when a coefficients for forced convection
gas or fluid moves carrying heat with it.
When the movement is driven only by
temperature difference it is known as free Mass transfer of air through the building
convection, otherwise it is forced envelope will carry heat energy into or out
convection. of the building.

In practice it is only necessary to know the The rate of heat transfer is proportional to
rate at which heat is carried to or from a the rate of air leakage as follows:
surface by convection. This can be
calculated by: Q = qρC p ( Ti - Te )

Q = hc A( Ts - T f ) where:

where: Q = rate of heat transfer (W/m2)


q = rate of air leakage (m3/sm2)
Q = rate of heat transfer ρ = density of air (1.23 kg/m3)
hc = convection coefficient Cp = specific heat capacity
Ts = surface temperature (1008 J/kgK)
Tf = fluid/gas temperature Ti = internal temperature
Te = external temperature
The convection coefficients hc are multiplied The rate of air leakage depends on the air
by a factor C to account for forced permeability of the building envelope and
convection. the pressure difference across it.

q = α ( p e − pi ) 0.67

3/10
Introduction to building envelope heat transfer TN 46

conductivity of 0.035 W/mK that is faced on


where: both sides with a 1.5 mm aluminium sheet
with thermal conductivity of 160 W/mK.
α = air leakage coefficient
pe = external pressure If no additional heat transfer occurs at the
pi = internal pressure edges (see thermal bridging), and ignoring
thermal resistance at the surfaces, the
Although the wall is tested at a pressure thermal resistance of the panel can be
difference of 50 Pa the average pressure calculated as:
difference over time will be less. In the
absence of further information of actual 0.0015 0.120 0.0015
pressure difference the advice given in R = ∑ Rn = + +
160 0.035 160
CIBSE TM23. This states that:
R = 3.43 m2K/W
q
q = 50
20 The heat transfer through the panel is
proportional to the temperature difference
Where q50 = air leakage at 50 Pa. across the panel ∆T, and is given by:

∆T ∆T
Insulation Q= = W
ℜ 3.43
In a layered construction all layers resist
heat transfer but a layer that has a
Surface resistance
significantly greater resistance to heat flow
may be provided (an insulation layer) to
The heat transfer calculated above can only
reduce heat flow through the wall.
occur if heat is gained at one surface and
lost at the other by convection and/or
Thermal resistance is given by:
radiation.
∆T In practice when a building element is
ℜ=
Q exposed to the environments, the surface
temperature on the cool side will be warmer
Assuming the cross section area A = 1m2, than the air on that side. The surface
the thermal resistance for conduction is: temperature on the warm side will be cooler
than the air on that side. These
d temperature differences exist and cause
R= convection and radiation heat transfer at the
λ surfaces.
In layered constructions the resistance to It is possible to calculate the surface
heat flow may be calculated by considering temperatures but it is more convenient to
the layers as separate resistors connected calculate heat transfer knowing just the air
in series as follows: temperature on each side of the
construction.
R = R1 + R2 + R3 .......
The thermal resistance for convection and
radiation at each surface can be combined
Heat transfer through a sandwich panel into a surface resistance so that the total
resistance to heat flow becomes:
Assuming that a sandwich panel comprises
a 120mm core of mineral wool with thermal

4/10
Introduction to building envelope heat transfer TN 46

RT = Rsi + R1 + .... + Rn + Rse


Rsi = 0.13
where:
RT = ∑Rn = 3.212 m2K/W
RT = total thermal resistance
(environment to environment) and:
R1, Rn = thermal resistance of each layer
Rsi = internal surface resistance
1
Rse = external surface resistance U= = 0.311 W/m2K
R
Rsi and Rse can be calculated according to
heat transfer coefficients of convection and The temperature drop across any layer can
radiation at the surface. Standard values be calculated as:
for surface resistance are given in BS EN
ISO 6946. For horizontal heat flow, the Rn
surface resistances of a vertical surface are: ∆t n = ∆ T
RT
Rsi = 0.13 m2K/W
and for internal temperature of 20o C and
Rse = 0.04 m2K/W
external temperature 0o C

Internal and Point temperatures 0.04


t0 = 20 × = 0.25 oC
3.212
Temperatures throughout a layered
construction can be calculated from the 0.092
resistance of each layer. t1 = 0.25 + 20 × = 0.82 oC
3.212
For a layered construction of timber and
insulation shown in Figure 1.
2.857
t2 = 0.82 + 20 × = 18.61 oC
3.212
Rse = 0.04
0.092
0.012 t3 = 18.61 + 20 × = 19.18 oC
R1 = R3 = = 0.092 3.212
0.13

0.100
R2 = = 2.857
0.035

5/10
Introduction to building envelope heat transfer TN 46

Figure 1 Temperature distribution in a sandwich panel

Annual energy losses


∆T 1
Annual energy use for a building will E = Qt = ∑ t = ∑ ∆Tt
R R
depend on energy loss or gain due to:
where:
• Conduction
• Air leakage
• Radiation ∑ ∆Tt Is the number of degree heating
seconds (86400 x number of
degree heating days)
The rate of heat transfer through the
building envelope due to conduction The number of degree heating days for
depends on the conductivity of the envelope different locations in the UK can be found in
components and the temperature difference CIBSE Handbook A.
across the envelope, which for a constant
internal temperature depends only on the Note that the actual total annual energy
external temperature. transfer will differ from this calculated value
due to radiation and solar warming of the
The external surface temperature is not the outer surface.
air temperature but the solair temperature
that takes account of solar warming of the
surface by radiation. The effect of solar U-values
warming of the external surface will depend
on the surface materials and any air cavities Building components are used in different
behind the outer surface. For facades climates and it is desirable to measure their
containing 40 percent or more glass the thermal performance independent of climate
effect of solar heating of the outer surface is (temperature difference).
small compared with the effect of solar gain
through the glazing. The U-value is defined as the rate of energy
loss through a unit area of wall for a
Ignoring the effect of solair temperatures it temperature difference of one degree and:
is possible to calculate the total energy loss
due to conductance provided the number of Q 1
degree heating days (and or degree U= =
cooling) days is known. A∆T RT

6/10
Introduction to building envelope heat transfer TN 46

For the previous example of a sandwich Where the material causing the thermal
panel with R=3.212 m2K/W the U-value is bridge is prismatic and extends through the
0.311 W/m2K. full thickness of a layer and the heat flow
can be assumed to be one-dimensional.
The U-value has units of W/m2K and is The overall conductivity (thermal
always calculated using the principle of transmittance) may be calculated assuming
thermal resistance. the elements acts in parallel. A typical
example is the concrete mortar joints in a
The rate of energy loss Q for a panel of blockwork wall.
area A is given by:
According to the Building Regulations Part
Q = UA∆T L, the thermal bridging effect can be
disregarded where the difference in thermal
Provided account is taken of heat flow resistance between the bridging material
between components as well as through and the bridged material is less than 0.1
them (see lateral heat flow below), then for m2K/W, (Note this cannot be applied for
a collection of elements in parallel: construction containing materials with
higher conductivity such as metals).
Q = ∑UA∆T
Therefore, in the case of Figure 2 the
elements act in parallel and all of the heat
flow is assumed to be perpendicular to the
Thermal bridging parallel surfaces of the construction:
A thermal bridge occurs where a material or
Q = ∆T ∑UA
component of high conductivity pierces an
insulating layer of lower conductivity. This
allows heat to bypass the insulation with
two effects:

a) The rate of heat transfer through the


combined materials is greater than it
would have been through the insulation
alone.
b) The warm surface is cooler and the cool
surface is warmer

This second effect gives rise to the term


‘cold bridging’. In cool climates thermal
bridges cause localised cold patches on the
inner surface of the building envelope and
are associated with problems of
condensation, dampness and mould
growth.

One-dimensional heat flow occurs in


layered structures with homogenous
material layers, Figure 1, and where cold Figure 2 Blockwork wall
bridges exist but the bridging material has
conductivity similar to that of the bridged
material. For the example in Figure 2:

7/10
Introduction to building envelope heat transfer TN 46

Figure 1 with the addition of 50mm wide


1 1 timber studs within the insulation at 400mm
U blockwork = = centres.
RBlock d
Rsi + + Rse
λblock The temperature gradient assuming one-
dimensional flow through section B-B alone
1 (through the insulation) is the one
= calculated earlier but for one-dimensional
0.101
0.13 + + 0.04 flow thorough section A-A alone (through a
0.57 stud) the temperature gradient is linear as
shown.
= 2.88 W / m 2 K
In this case the construction cannot be
considered as components simply in
1 1 parallel or series.
U mortar = =
Rmortar d
Rsi + + Rse
λmotar
Lateral heat flow occurs between the
1 insulation and studs and along the facing
=
0.101 timber. This occurs because on planes
0.13 + + 0.04
1.33 parallel to the surfaces the temperature is
not constant and a temperature gradient
= 4.07 W / m 2 K exists perpendicular to the principal
direction of heat flow.

and:
Heat flux
Q = ∆t( 2.88 × 3 × 0.075 × 0.305
+ 4.07 × 2 × 0.010 × 0.305 ) The flow of heat is called heat flux and it
may be plotted as shown in Figure 4. A
= 0.222 ∆t W further example of a steel stud wall can be
seen in Figure 6.
Q 0.222
U Overall = =
A∆t (3 × 0.075 + 2 × 0.01) × 0.305
Isotherms
2
= 2.98 W/m K
Lines of equal temperature are called
isotherms and these may be plotted to show
Two-dimensional heat flow occurs where the temperature distribution as shown in
the conditions described above do not Figure 5. A further example of a steel stud
apply. Figure 3 shows an insulating layer of wall can be seen in Figure 6.
a construction bridged by a material of .
higher conductivity. This is the example of

8/10
Introduction to building envelope heat transfer TN 46

Figure 3 Timber stud wall

Figure 4 Flux lines for timber stud wall

Figure 5 Isotherms for timber stud wall

Figure 6 Isotherms and heat flux for steel stud wall

9/10
Introduction to building envelope heat transfer TN 46

Notation References

Building Regulations Part L2, Conservation of


A Area M2
heat & power in buildings other than dwellings
d Thickness m (2002 edition).

Cp Specific heat capacity J/kgK BS EN 673: 1998, Glass in building -


e Emissivity Determination of thermal transmittance (U value)
– Calculation method.
h Convection coefficient W/m2K
BS EN 12664: 2001, Thermal performance of
hc Forced convection factor W/m2K
building materials and products. Determination
P Pressure Pa of thermal resistance by means of guarded hot
plate and heat flow meter methods. Dry and
q Rate of air leakage m3/sm2 moist products of medium and low thermal
q50 Rate of air leakage at m3/sm2 resistance.
pressure difference of 50
Pa BS EN 12667: 2001, Thermal performance of
building materials and products. Determination
Q Rate of heat flow W of thermal resistance by means of guarded hot
R Thermal resistance m2K/W plate and heat flow meter methods. Products of
high and medium thermal resistance.
ℜ ???
BS EN 12939: 2001, Thermal performance of
RSE External surface resistance m2K/W building materials and products. Determination
RSI External surface resistance m2K/W of thermal resistance by means of guarded hot
plate and heat flow meter methods. Thick
t Time s products of high and medium thermal resistance
T Surface temperature K
CIBSE Handbook Part A, CIBSE, 1986, pp 270,
o
∆T Temperature difference C ISBN 0 900953 29 2.
U U-value W/m2K TM23: Testing buildings for air leakage. CIBSE,
tn Temperature o
C 2000, ISBN 1 903287 10 3.

α Air leakage coefficient

λ Thermal conductivity W/mK

ρ Density kg/m3

σ Constant

1,2,n Numbers referring to a


layer or position

© CWCT 2004

University of Bath, Claverton Down, Bath,


BA2 7AY
Tel: 01225 386541; Fax: 01225 386556
Email: cwct@bath.ac.uk;
Website: www.cwct.co.uk

10/10

You might also like